3.6.4 containment pressure
-0.1 to 1.0 psig
3.6.5 containment temperature
The average inlet temperatures of the running RCFCs shall be <=120F
If CRDM exhaust air temperature increases above ____ proceed to unit shutdown and reduce Tave to below ____.
165F
350F
What is temperature limit on the CRDM coils?
392F
With ____ or more CRDM exhaust fans inoperable: ____.
3
Shutdown and Tave<350F
RX vessel head cooldown during Nat. circ.
-45F to 54F per hour
with fans
-1 F/hr no fans
CNMT charcoal unit fans trip on ____ or _____.
Overcurrent
or
Deluge activated
CRDM booster fans controlled from ___ and CRDM exhaust fans controlled from _____.
0PM02J
0PM02J and RSP
U1 peak LOCA P
U2 peak LOCA P
42.8 psig
38.4 psig
CNMT charcoal filter DP alarms
Prefilter
Hepa
1.0” H20
2.0” H20
CRDM fans must be on whenever ____ or _____.
CRDM coils energized
or
RCS T >350F
Power supplies of purge and exhaust fans
133x/134x
Initiation signals for CVI
-Any SI
-Manual Phase A
-Manual CS
-Cnmt air area rad monitor
AR011J controls train ____ dampers
AR012J controls train ____ dampers.
Train A
Train B
Which dampers close on CVI?
TrainA
VQ001a, 002A, 004A, 005A and C
Train B
VQ001B, 002B, 003, 004B, 005B
Sources of hydrogen post LOCA?
- Radiolytic decomposition.
- Zirc water reaction
- Hydrogen release from RCS.
- Plant material corrosion
Normal purge supply fan starting interlocks
1VQ001y open
VQ001A and B open
Other fan disch shut
Auto trips of purge supply fan (4)
Starting interlocks not met
Inlet air temp <40F
Smoke detected in air supply. w/purge CS in normal.
Overcurrent
Purge exhaust fan starting interlocks
VQ002A/B open
Other fan disch shut
Either supply running
Mini purge exhaust fan start interlocks
VQ005a/b/c all open
Function of post-loca purge
Backup to hydrogen recombiners to purge the cnmt atmosphere of hydrogen. Maintain h2 <4% post loca
Purge dampers must be _____ in modes _____.
De-energized closed
Modes 1-4
When swapping RCFC from high to low speed there is _____.
20 second time delay whether SI present or not
CNMT chilled water response to SI actuation
- Cnmt isolation valves close on Phase A.
- Running CW pump trips.
- Chiller trips
- SX112 & 114A/B close
- SX147A/B open