What are the MFP trips?
What causes a Feedwater Isolation (FWI)?
What supplies the normal steam supply to the MFPs?
What happens on a FWI?
MFPs Trip
MFP Disch Valves Close
FRVs Close
FMOs Close
What must you do to clear a FWI that is associated with P-4 with Tavg < 554°F)?
Will all 4 MFW FRVs close on loss of 250v DC ctrl pwr?
Yes
When will the MFP Seal Water Pump auto start?
less than 15 psid between CBP Disch pressure and MFP suction pressure
Where can the MFP seal water pump get its suction from?
What is the FW designed to handle on a load rejection?
-10% step change
OR
- 5%/min ramp load change w/o steam dump
When is a MFP forced to Speed Ctrl?
What flow do the MFP ELOs modulate to maintain?
4000 GPM (Suction flow)
How much flow can each string of MFW heaters handle?
80% flow
How much flow can MFW heaters bypass valve (FMO-260) handle?
20% flow
Where does the E MFP ELO discharge to?
B Condenser
Where does the W MFP ELO discharge to?
A Condenser
Which FW heaters on Unit 1 receive HP steam?
Heaters 5 and 6
Which FW heaters on Unit2 receive HP steam?
Heaters 4, 5, and 6
Can you manually close the MFP ELOs?
Does the U-2 DC Lube Oil Pp go thru the Lube Oil Cooler?
For a FWI, is the closure of the FRVs Train Specific?
No, either train of RPS will get all 4 FRVs
For a FWI, is the closure of the FMOs Train Specific?
Yes! Interlocked to the Rx Trip Breakers, so if one doesn’t go open, you don’t get that train of FMOs to close
What is the purpose of the Air Assist Check Valves in the MFW System?
keeps check valve out of flow stream
What is the purpose of the MFP Seal Water FRV?
Maintains seal water leak off temperature at 150°F
What are the MFP Speed Control Inputs?
SG Pressure, FP Discharge Pressure and Total Steam Flow