Practice Test 2 Flashcards
Prepare for the UPC exam with practice tests and review questions. (240 cards)
Fill in the blank:
Shower compartments shall have a finished interior space capable of encompassing a ______ inch circle.
30
Calculate the measurement for a special case 90 degree offset using 45 degree elbows for M if the spread between pipes is 14”.
10 5/8’
Fill in the blank:
The maximum distance between manholes shall not exceed ______ feet.
300
Fill in the blank:
The maximum temperature allowed from a steam pipe into an indirect waste receptacle shall be ______ degrees Fahrenheit.
140
What are the required dimensions for a work platform in front of an appliance in an attic or under the floor?
30” x 30”
Using the standard method for calculating indoor combustion air, how many cubic feet shall be required per 1000 BTU per hour?
50
What is the required vent diameter given the following information?
Type B Double-Wall Gas Vent
Single Category 1 Appliance Connected Directly to Ven,
Vent Height: 30’
Vent Lateral: 12’
Natural Draft
Appliance Input 160,000 BTU
5 pipe”
What is the size for a storm drain gutter with a slope of 1/8” per foot in a location with 4 inch per hour rainfall and a roof surface area of 2,000 square feet?
8”
Convert:
37.4 gallons to cubic feet
Semi-Rigid Copper Tubing Type K
Natural Gas
Inlet Pressure Less Than 2 psi
Pressure Drop 0.5 in. w.c.
Specific Gravity 0.60
Longest Length: 30 feet
Cubic Feet per Hour: 40
5 cubic feet
What are the total drainage fixture units at point C?
32 DFU
True or False:
Regulator vent piping may be vented into the appliance flue or exhaust system.
False
Fill in the blank:
A Type B gas vent shall terminate at least ______ feet above the highest connected appliance.
5
True or False:
Multiple buildings on the same lot may have a combined connection to the public sewer.
True
Fill in the blank:
When work is performed ______ feet above lower levels, fall protection is required.
6
When a draft vent serves multiple appliances, what is the maximum horizontal length for a vent connector that is 8 inches in diameter?
12”
What is the gas pipe size for a pipe system having the following conditions:
Semi-Rigid Copper Tubing Type K
Undiluted Propane
Inlet Pressure 11 in. w.c.
Pressure Drop 0.5 in. w.c.
Specific Gravity 1.50
Longest Length: 50 feet
BTU per Hour: 150
3/4”
What are the maximum drainage fixture units that can be served by a 3” vent pipe?
84
What is the minimum distance from a trap to the vent if the diameter of the trap arm pipe is 2”?
4”
Find the grade of a pipe if the drop is 21” and the run is 84 feet.
1/4” per foot
Which of the following is not an approved method for providing overflow protection for indirect condensate waste?
a. water level detecting device that will shut off the equipment
b. watertight pan with separate drain line
c. additional drain line pipe with connection higher than the primary drain
line
d. water overflow detecting alarm device
d. water overflow detecting alarm device
What is the minimum air gap required for an effective opening that is 1/2” in diameter where not affected by side walls?
1”
For appliances listed for use with Type B gas vents, what is the minimum required distance from combustible material for a single-wall metal pipe connector?
6”
Fill in the blank:
An abandoned building sewer shall be plugged or capped within ______ feet of the property line.
5
What is the drainage fixture unit value for an intermittent flow of 20 GPM?
4 DFU