Systems Final Review Flashcards
(163 cards)
How does a Deluge System work and what systems/rooms use this type of Fire Protection?
a) Deluge System (Aux boiler, H2 Seal Oil Units, RFPT rooms, RFP oil cond, U2 EHC room, all filter trains)
* *i) A deluge system is used in areas where SEVERE, fast spreading fire might occur**
(1) Employs open sprinkler heads attached to piping connected to a water supply through a valve that is opened upon actuation of a fire detection system in the same area as the sprinklers (or manually)
(2) When valve opens, water flows into associated piping and discharges from all open sprinklers instantly
(3) Deluge valve is differential type valve that depends upon water pressure in diaphragm chamber to hold clapper closed against water supply pressure
(a) Loss of pressure in diaphragm chamber results in clapper opening permitting flow to piping and spray heads
(i) Any leakage past clapper valve is detected by flow from ball drip valve
1. Functions as leak detection device when system in standby
2. If clapper valve opens, spring plug in ball drip valve closes
(4) All filter train deluge systems are not connected to source of water
(a) To use deluge system on filter trains, connect 1 ½” Fire Hose to hose connection on exterior of filter, pressurize hose, and open deluge system manual isolation valve
How does a Fixed Water Spray System work and what systems/rooms use this type of Fire Protection?
b) Fixed Water Spray System (switchyard transformers, shunt reactors, Intake Structure)
i) Network of piping that provides water to DIRECTIONAL SPRAY NOZZLES actuated automatically or manually
ii) Identical to Deluge System except it has open directional nozzles in spray header not open sprinkler heads
(1) Intake structure has closed head fixed water spray system
How does a Wet Pipe Sprinkler System work and what systems/rooms use this type of Fire Protection?
c) Wet Pipe Sprinkler System (FP pump house, HPCI/RCIC rooms, cableways, U1 EHC room, Warehouse 6)
i) Auto closed head sprinklers containing water and connected to water supply so water discharges onto fire
(1) Wet pipe sprinkler system piping is pressurized to fire main pressure
(2) Heat activated sprinkler heads open if ambient temperature reaches specified temperature indicating fire
(3) Sprinkler heads are non-reusable and must be replaced after actuation
(4) Uses component called retard chamber to help prevent nuisance fire alarms
(a) Retard chamber designed to accumulate excess flow generated by pressure surges in system
How does a Dry Pipe Sprinkler System work and what systems/rooms use this type of Fire Protection?
d) Dry Pipe Sprinkler System (Warehouse 1-5, LLRW, Dry Waste storage)
i) Auto closed head sprinklers attached to piping containing air under pressure, release of which through open sprinkler permits water to open dry pipe valve releasing water into piping and out open sprinkler
(1) Consists of riser pressurized with water up to clapper valve
(a) Air pressure between clapper valve and closed sprinkler heads holds clapper closed
(2) Heat activated sprinkler heads open if ambient temperature reaches specific temperature
(3) When sprinkler head opens, air bleeds off downstream side of clapper valve thru sprinkler head allowing clapper valve to open, spraying water on affected area
ii) Dry pipe system used to PREVENT FREEZING of pipes during cold weather
How does a Preaction Sprinkler System work and what systems/rooms use this type of Fire Protection?
e) Preaction Sprinkler System
i) Auto closed head sprinklers containing air that may or may not be under pressure with fire detection system installed in same area as sprinklers
(1) Fire detection system actuation opens valve permitting water flow into piping discharge thru all open sprinklers
(2) Unlike deluge or fixed spray system, loss of air pressure does not activate clapper valve
(3) Requires combination of TWO SIGNALS TO INITIATE
(a) Fire detector used to actuate clapper valve
(b) Sprinkler heads melt on high temperature directing spray on affected area
(4) Used where accidental water spray would cause excessive damage in area sprayed
What actions are prevented when an EDG is placed in TEST?
a) Placing a EDG to TEST results in the following
i) Locks out associated EDG automatic start
ii) Prevents AUTO close of associated EDG output breaker
iii) Allows paralleling of associated EDG with either its normal or alternate power supply
iv) TEST NO MANUAL for station service buses
(1) Cannot manually transfer SS buses from normal to alt (fast transfer still works)
(2) Can manually transfer SS buses from alt to normal
v) TEST NO AUTO for emergency buses
(1) Emergency bus (associated) will not auto transfer to alternate on UV
(2) Arms additional EDG trips
What situations cause an EDG to be knocked out of TEST?
1) Loss of power to the ALTERNATE SAT for the associated 4160 Emergency Bus
2) LOCA Signal
What are the normal EDG trip signals? What if the EDG is in TEST?
Anytime: SOLD Start Failue - <250 rpm or <6 psig oil pressure 7s after start Over speed - 1000+/- 10 rpm Low Lube Oil Pressure - 21 (18) psig Differential Lockout
TEST: PORCH Pushbutton - with EDG output bkr open Oil (lube) Temp Hi - 230 F Reverse Power Crankcase Pressure Hi - .5" H2O Hi Temp or Low Pressure (Jacket Water) - 205 F or 9 (10) psig
For the Vital AC system, what does the Static Bypass Switch (Static Transfer Switch) do?
Used to auto transfer Vital AC bus to its alternate AC power supply
i) Transfer happens within a fraction of a cycle (no loss of power should occur)
For the Vital AC system, what does the Return Mode Switch (U2) do?
Controls the auto swap function for the inverter during a power loss from the inverter
i) If left in the “AUTO” position, Vital AC auto transfers back to inverter when power is restored to the inverter
ii) If placed in the “MANUAL” position, Vital AC system will remain aligned to the Alternate power source until manually transferred back to the inverter in the event a power loss occurs form the inverter pathway.
For the Vital AC system, what does the Sync Monitor Light being illuminated mean?
ii) Sync Monitor light is ON when the Inverter output voltage is OUT OF PHASE w/ Bypass AC Voltage
iii) Do NOT operate Test Switch to ALT LINE position if Sync Monitor light is ILLUMINATED
What major functions and instruments are lost if the 125/250 VDC Switchgear “A”
(R22-S016) is de-energized?
- Generator PCBs will not auto open on Turbine Trip (4 mins allowed for opening the PCBs, unless the exciter field breaker is open or exhaust hood spray is not functioning properly)
- Once PCBs are opened, SS 4160 buses will de-energize b/c no control power (will not swap)
- RCIC not available and all indication for DC power loads are lost
- Station Service 4160V will not fast transfer.
- C32-R606B – “B” GEMAC RWL Indicator lost
- C32-R605B – “B” GEMAC Pressure Indicator lost
- C32-R603B – “B” Steam Flow Indicator lost
- C32-R604A – “A” Feed Flow Indicator lost
• Unit 2
o RFPT 2A and 2B will not trip manually or automatically due to loss of power to their trip circuits. Local trip is required
o 2E, 2F, and 2G will not fast transfer from norm to alternate
• Unit 1
o 1B Recirc pump will not trip manually or automatically due to loss of input breaker control power. Local trip is required.
o RFPT 1A will not trip manually or automatically due to loss of power to its trip circuit. Local trip is required.
What major functions and instruments are lost if the 125/250 VDC Switchgear “B”
(R22-S017) is de-energized?
- HPCI is not available and all indication for DC power loads are lost
- C32-R606C – “C” GEMAC RWL Indicator lost
- C32-R605C – “C” GEMAC Pressure Indicator lost
- C32-R603C – “C” Steam Flow Indicator lost
- C32-R604B – “B” Feed Flow Indicator lost
• Unit 2
o Control power is lost to BOTH ASD bkrs (neither pump can be tripped from the MCR, shutdown button still functions)
• Unit 1
o 1A Recirc pump will not trip manually or automatically due to loss of input breaker control power. Local trip is required.
o RFPT 1B will not trip manually or automatically due to loss of power to its trip circuit. Local trip is required.
What major functions and instruments are lost if the 125 VDC Cabinet “A”
(R25-S001) is de-energized?
- Generator PCBs will not auto open on Turbine Trip (4 mins allowed for opening the PCBs, unless the exciter field breaker is open or exhaust hood spray is not functioning properly)
- RCIC not available
- Rx Instruments similar to R22-S016
- Loss of control power to 4160 ‘A’ and ‘B’ supply breakers. They will not fast transfer to startup supply on loss of norm
- Loss of control power to 600 ‘C’
• Unit 2
o RFPT 2A will not trip manually or automatically due to loss of power to their trip circuits. Local trip is required
o 2E, 2F, and 2G will not fast transfer from norm to alternate
• Unit 1
o RFPT 1A will not rip manually or automatically due to loss of power to its trip circuit. Local trip is required.
What major functions and instruments are lost if the 125 VDC Cabinet “B”
(R25-S002) is de-energized?
• HPCI not available
- Rx Instruments similar to R22-S017
- Loss of control power to 4160 ‘A’, ‘B’, ‘C’, and ‘D’ feeder breakers
- Loss of control power to 600 ‘D’
• Unit 2
o 2A and 2B Recirc Pumps will not trip manually or automatically due to loss of input breaker control power. Local trip is required
• Unit 1
o 1A Recirc pump will not trip manually or automatically due to loss of input breaker control power. Local trip is required.
o RFPT 1B will not trip manually or automatically due to loss of power to its trip circuit. Local trip is required.
What major functions and instruments are lost if the 125 VDC Cabinet “C”
(R25-S003) is de-energized?
- Control power is lost to the Exciter Field Breaker, however, the breaker remains closed
- Rx Instruments similar to R22-S016
- Loss of control power to 4160 ‘C’ and ‘D’ supply breakers. No transfer available manually or automatically.
- Loss of control power to 600 ‘A’, ‘B’, ‘AA’, and ‘BB’
• Unit 2
o RFPT 2B will not trip manually or automatically due to loss of power to their trip circuits. Local trip is required
• Unit 1
o 1B Recirc pump will not trip manually or automatically due to loss of input breaker control power. Local trip is required.
What major functions and instruments are lost if the 125 VDC Cabinet “D”
(R25-S004) is de-energized?
- ‘A’ EDG will not auto or manual start
- ‘A’ EDG output breaker will not tie
- ARI will not initiate (S005 on U1)
- RHR ‘A’ and ‘D’ cannot be started from the MCR
- CS ‘A’ will not auto start
- Loss of control power to 4160 ‘E’
What are the Unit 2 Undervoltage and Degraded voltage setpoints for the 4160V emergency buses? How do theses voltages cause the 86 lockout relay to trip on bus undervoltage?
Bus undervoltage will cause EDG to start and tie. Without a LOCA signal, there is not a signal to initiate timers for auto start of Core Spray or LPCI.
Undervoltage : 3255V
Undervoltage for >1s causes 86 lockout relay to trip
Degraded Voltage:
1) 4160V Bus 2E: 3983V
2) 4160V Bus 2F: 3924V
3) 4160V Bus 2G: 3924V
Degraded voltage for 9 seconds, causes the normal supply breaker to trip, the associated Diesel Generator to start AND alternate supply breaker to close.
If the degraded voltage condition remains for one (1) additional second, the 86 lockout relay will trip the alternate supply breaker and allow the associated Diesel Generator to tie and pick up the emergency bus loads.
What are the Unit 1 Undervoltage and Degraded voltage setpoints for the 4160V emergency buses? How do theses voltages cause the 86 lockout relay to trip on bus undervoltage?
Bus undervoltage will cause EDG to start and tie. Without a LOCA signal, there is not a signal to initiate timers for auto start of Core Spray or LPCI.
Undervoltage : 3255V
Undervoltage for >1s causes 86 lockout relay to trip
Degraded Voltage:
1) 4160V Bus 1E: 4021.5V V
2) 4160V Bus 1F: 3892V
3) 4160V Bus 1G: 3916.5V
Degraded voltage for 9 seconds, causes the normal supply breaker to trip, the associated Diesel Generator to start AND alternate supply breaker to close.
If the degraded voltage condition remains for one (1) additional second, the 86 lockout relay will trip the alternate supply breaker and allow the associated Diesel Generator to tie and pick up the emergency bus loads.
What are the pressures for the automatic start of the Fire Pumps? What is the power supply for the Electric Fire pump?
1X43-C001 Electric FP - Starts @ 110 psig.
1X43-C002A Diesel FP #1- Starts @ 100 psig.
1X43-C002B Diesel FP #2 - Starts @ 90 psig.
1X43-C003 Jockey Pump - Starts @ 125 psig - Stops @ 157 psig.
Power Supply: Electric Fire Pump - 4160V Bus 1E
How does Vital AC respond on a LOSP?
a) Normal – Vital AC auto swaps to backup batteries. With no operator actions, voltage will reduce to <208V (~2 hours) causing Vital AC to swap to Alternate supply (600V C)
How are the station service battery chargers restored following a LOSP?
a) To restore battery chargers – Manual actions must be performed including reset of non-essential load lockout and pressing push buttons in MCR (for Station Service Battery Chargers
b) 600V Bus 2C Loads Locked Out
i) 2R42-S026, 2R42-S027, 2R42-S028 Station Battery Chargers 2A, 2B, and 2C
c) 600V Bus 2D Loads Locked Out
i) 2R44-S001 Vital AC Battery Charger
ii) 2R42-S029, 2R42-S030, 2R42-S031 Station Battery Chargers 2D, 2E, and 2F
d) Recovery of Loads off 600V 2C/2D
i) RESET the 600V 2C / 600V 2D Non-Essential Load Lockout
ii) Restore Division I Station Service Battery Chargers per the following:
(1) Depress 2R42-S026, Battery Charger 2A/2B/2C pushbutton, located on 2H11-P664
(2) If previous steps did not energize Battery chargers, proceed to 34SO-R42-001-2 (locally)
iii) Restore Division II Station Service Battery Chargers per the following:
(1) Depress 2R42-S029, Battery Charger 2D/2E/2F pushbutton, located on 2H11-P664
(2) If previous steps did not energize Battery chargers, proceed to 34SO-R42-001-2 (locally)
How does the B EDG decide which unit to align to?
In General, the unit that is worse off will be the one to get the B EDG.
If one unit is experiencing a LOSP, and the other unit has a LOCA, the B EDG will go to the unit with the LOSP (it needs the power)
The only times the EDG will not tie to one bus or the other is when BOTH units have a LOCA/LOSP, or when there is just a LOCA signal on a single unit (power not needed since normal power supplies available)
What happens with Station Service Buses when there is a fault on a UAT?
a) UAT fault will cause a SIMULTANEOUS trip of the Main Generator and Main Turbine, both PCBs (U1 - 500/510, U2- 740/750) to open, and the Station Service buses to fast transfer to their respective SAT supply.