A final practice Flashcards
(127 cards)
A 3.0” schedule 40 gas line is 875 feet long (fittings included) and operates at a static
pressure of 10 psig. What is the maximum load on the piping system with a maximum
allowable pressure drop is 3 psi?
Actual inside diameter of 3.068: 20,489 ft3,
Nominal pipe size: 19,320 ft3 from answers
What is the size of a TOE nipple for the purge point at each end of a 6″ gas pipe?
3/4 inch
The actual pipe size for the nipple is 3/4 inch.
Calculate the theoretical draft in the venting system based on the following information:
a. Stack temperature 473 degrees F.
b. Ambient temperature 72 degrees F.
c. Stack height 38 ft.
Options:
a) 0.18 in. w.c.
b) 0.23 in. w.c.
c) 0.30 in. w.c.
d) 0.35 in. w.c.
Answer:
b) 0.23 in. w.c.
D=7.6×0.0008088×38
D≈0.2335in.w.c.
You are called on to commission an installation of a 3,275,000 Btu natural gas boiler.
Excess air set at 22%
Stack diameter 14 inch
Combustion chamber and heat exchanger pass volume 165 ft³
Gross stack temperature 405 deg. F
Ambient temperature 75 deg. F
The programming control requires a purge card. The gas inspector has asked for your calculations for the pre-purge period for the boiler, select the correct card?
Options:
a) 30 seconds
b) 60 seconds
c) 90 seconds
d) 120 seconds
Total Volume to be Purged:
Combustion chamber and heat exchanger pass volume = 165 ft³
Assuming 4 air changes for pre-purge:
Total Volume = 165 ft³ × 4 changes = 660 ft³
Volumetric Flow Rate of Combustion Air:
Boiler Input: 3,275,000 Btu/h
Heating Value of Natural Gas: Approximately 1,020 Btu/scf (standard cubic foot).
Stoichiometric Air Requirement: For natural gas (primarily methane), approximately 9.52 scf of air is required per scf of natural gas for complete combustion.
Natural Gas Flow Rate:
Gas Flow = 3,275,000 Btu/h / 1,020 Btu/scf ≈ 3210.78 scf/h
Stoichiometric Air Flow:
Stoich Air Flow = 3210.78 scf/h × 9.52 scf air/scf gas ≈ 30560 scf/h
Total Air Flow with Excess Air: (22% excess air)
Total Air Flow = 30560 scf/h × (1 + 0.22) = 30560 scf/h × 1.22 ≈ 37283.2 scf/h (at standard conditions, 60°F)
Actual Volumetric Air Flow at Ambient Temperature:
Ambient Temperature (T a ) = 75°F = 75 + 459.67 = 534.67 °R
Standard Temperature = 60°F = 60 + 459.67 = 519.67 °R
Actual Volumetric Air Flow = 37283.2 scf/h × (534.67 °R / 519.67 °R) ≈ 37283.2 scf/h × 1.0288 ≈ 38363.3 ft³/h
Calculate Pre-Purge Time:
Pre-Purge Time (hours) = Total Volume / Actual Volumetric Air Flow
Pre-Purge Time = 660 ft³ / 38363.3 ft³/h ≈ 0.0172 hours
Convert to seconds:
0.0172 hours × 60 minutes/hour × 60 seconds/minute ≈ 61.92 seconds
What is the required minimum relief valve capacity of a 150 PSIG steam boiler rated at 500 BHP?
17,250 lbs/hr (500 x 34.5)
What is the maximum allowable operating Pressuretrol set point of a high pressure steam boiler equipped with 125 PSIG pressure relief valves?
Options:
a) 100 PSIG
b) 112.5 PSIG
c) 125 PSIG
d) 137.5 PSIG
Answer:
100 PSIG 125x.80
A DFMA on a building has a capacity of 18,000 CFM and requires a natural gas supply. What is the maximum load on the gas supply line to the unit?
Options:
a) 1,632,960 Btu/h
b) 1,800,000 Btu/h
c) 2,160,000 Btu/h
d) 2,400,000 Btu/h
a) 1,632,960 Btu/h
Mechanical means is used to provide combustion air to a mechanical room. The appliances in the room are over 400 mbh and have their excess air set at 25%. None of
the appliances have draft control. What volume of air is required for every 1000 btu’s?
Options:
a) 10 ft³ for every 1,000 Btus
b) 20 ft³ for every 1,000 Btus
c) 30 ft³ for every 1,000 Btus
d) 40 ft³ for every 1,000 Btus
c) 30 ft³ for every 1,000 Btus
A mechanical room contains the following natural gas appliances:
2 atmospherically fired hot water tanks 500 MBH
One hot water boiler with a barometric damper input rating 2,895 MBH
One steam boiler at 18,500 MBH without draft control
Grills with a K factor of .75
a. What is the free area of the combustion air opening?
b. What is the free area of the ventilation air opening?
c. What are the opening sizes required for each grill?
a. 966.31 in²
b. 96.6 in²
c. 1288.41 in² / 128.8 in²
Gross Area = Free Area (Combustion) ÷ K-factor
Gross Area = 966.31in
2 ÷0.75=1288.413in
What is the cross sectional area of a duct that will pass 170,000 cubic feet/hour of combustion air at a velocity of 550 feet/minute?
Options:
a) 3.5 ft² / 504 in²
b) 4.2 ft² / 605 in²
c) 5.15 ft² / 742 in²
d) 6.8 ft² / 979 in²
c) 5.15 ft² / 742 in²
Convert Volume from ft³/hour to ft³/minute:Volume
fpm =170,000ft
3 /hour÷60minutes/hourVolume
fpm =2833.33ft 3 /minute
Calculate Area in square feet (ft²):
Area ft 2= Velocity fpm
Volume
fpm Area ft 2= 550ft/minute
2833.33ft3/minute
Area ft 2=5.1515ft 2
Convert Area from square feet (ft²) to square inches (in²):
Since 1 ft² = 144 in²,
Area in2=5.1515ft2 ×144in2 /ft 2
Area in 2=741.816in 2
- What is the maximum allowable time for the pilot to light the main burner when
adjusted to its minimum flame when conducting a pilot turn down test?
Options:
a) 40 seconds
b) 1 second
c) 4 seconds
d) 10 seconds
1 second
A valve train on a 5 psi system must have the high and low pressure gas switch replaced. What pressure do you set the High pressure switch?
Options:
a) 5.0 psig
b) 6.0 psig
c) 6.25 psig
d) 7.5 psig
c) 6.25 psig
5x%125
A valve train on a 5 psi system must have the high and low pressure gas switch replaced. What pressure do you set the Low pressure switch?
Options:
a) 1.0 psig
b) 2.0 psig
c) 2.5 psig
d) 3.0 psig
c) 2.5 psig
5x%50
What is the minimum operating pressure of a valve train requiring low and high gas pressure switches?
Options:
a) 0.1 psig
b) 0.25 psig
c) 0.5 psig
d) 1.0 psig
c) 0.5 psig
no high max
A motor is rated 115/60/1 at 5 amps: How many watts would this motor be rated at?
Options:
a) 115 Watts
b) 230 Watts
c) 575 Watts
d) 690 Watts
Power(Watts)=Voltage(Volts)×Current(Amps)
Power=115V×5A
Power=575Watts
What would 6 ounces be in water column?
Options:
a) 8.5 “w.c.
b) 9.2 “w.c.
c) 10.5 “w.c.
d) 11.2 “w.c.
c) 10.5 “w.c.
A DFMA on a building has a capacity of 13,000 cfm. Design temperatures are 0 deg F to 70 deg F.
a. What is the expected amount of CO2 for a DFMA firing natural gas operating at an outdoor air temp of 55°F and a discharge set point of 72°F?
b. On Propane
a. 0.034%
b. 0.0408%
- A 15,500 MBH boiler is operating on natural gas with 22% excess air.
a. What percentage of O2 would you expect to find in an analysis of the flue
gasses?
b. What percentage of CO2 would you expect to find in an analysis of the flue
gasses?
a. 8.9%
b. 3.9%
A natural gas appliance is operating under the following conditions atmospheric
burner:
* input 3,820 mbh
* manifold pressure 7.2” wc.
* Orifice K factor 0.83
* calorific value of the natural gas is 1024 Btu/ft3
* standby fuel 52% propane 48% air mix
Calculate the diameter of the orifice required when operating on natural gas
1.009”
What is the input of an 82% efficient boiler required to raise the temperature of 673
imperial gallons of water from 39 °F to 139 °F in 23 minutes.
2,141,039 btu/hr
A mechanical room contains a natural gas steam boiler rated at 1 453 MBH. The boiler is
required to run 24 hrs. a day to supply steam requirements. The room is supplied with
gas from a 15 psig meter with a 10 ft3 test dial. A new hot water heater rated at 93 Kw
is installed. The meter was clocked with just the boiler operating and the test dial took
50 seconds for one revolution. On start-up of the hot water heater the meter was
clocked with both appliances fired at 41 seconds. Local atmosphere is 14.69 PSIG.
a. What is the clocked input of the boiler?
b. What is the clocked input of the water heater?
c. Are both appliances firing correctly
a. 1451.232 MBH
b. 318.563 MBH (93.36 kW)
c. Boiler Yes / Water heater No
By what percentage would the input of an appliance increase if the manifold pressure of
6 “ w.c. was increased to 9.5” w.c.
25.83%
At a pressure of 3.5” w.c. a 3/8” diameter orifice will pass 677 ft3/hr of natural gas.
What would the resulting flow be if the pressure was increased to 11” w.c.
1,200.193 ft3
What would be the new input be if a 26,375 MBH boiler was switched from Nat gas
toits standby fuel of 55% Prop 45% Air mix?
24 771 381 btus