Ch 5 - Water Heaters Flashcards
True or False
A permit is required to install, remove, or replace any water heater.
TRUE
It shall be unlawful for a person to install, remove, or replace or cause to be installed, removed, or replaced a water heater without first obtaining a permit from the Authority Having Jurisdiction to do so.
2024 UPC- 502.0 Permits. 2024 UPC- 502.1 General.
Fill in the blank
Water heaters installations in bedrooms and bathrooms shall be of the _____ type.
Direct-vent
(1) Water heater shall be of the direct vent type [NFPA 54:10.27.1(2)] (NFPA 54: National Fuel Gas Code)
2024 UPC- 504.0 Water Heater Requirements. 2024 UPC- 504.1 Location.
Fill in the blank
Fuel-burning water heaters are permitted to be installed in a closet located in the _____.
Bedroom or bathroom
(2) Fuel-burning water heaters shall be permitted to be installed in a closet located in the bedroom or bathroom provided the closet is equipped with a listed, gasketed door assembly and a listed self-closing device. The self-closing door assembly shall meet the requirements of Section 504.1.1. The door assembly shall be installed with a threshold and bottom door seal and shall meet the requirements of Section 504.1.2. Combustion air for such installations shall be obtained from the outdoors in accordance with Section 506.4. The closet shall be for the exclusive use of the water heater.
2024 UPC- 504.0 Water Heater Requirements. 2024 UPC- 504.1 Location.
Fill in the blank
Gasketing on gasketed doors or frames must be furnished according to the published listings of the _____.
Door, frame, or gasketing material manufacturer
Gasketing on gasketed doors or frames shall be furnished in accordance with the published listings of the door, frame, or gasketing material manufacturer.
2024 UPC- 504.1.2 Gasketing
Fill in the blank
Unlisted water heaters must be installed with a clearance of _____ on all sides and the rear.
12 inches
Except as otherwise permitted in this code, unlisted water heaters shall be approved by the Authority Having Jurisdiction prior to being installed. Clearance for unlisted water heaters shall be not less than 12 inches (305 mm) on all sides. Combustible floors under unlisted water heaters shall be protected in an approved manner. {NFPA 54-2018:10.27.2.2} (NFPA 54: National Fuel Gas Code)
2024 UPC- 504.3.2 Unlisted Water Heaters.
Fill in the blank
Gas appliances of other than natural draft design and other than Category I vented appliances shall be provided with _____, ventilation, and dilution air in accordance with the appliance manufacturer’s instructions.
Combustion
Appliances of other than natural draft design appliances not designated as Category I vented appliances, and appliances equipped with power burners shall be provided with combustion, ventilation, and dilution air in accordance with the appliance manufacturer’s instructions. [NFPA 54:9.3.1.2] (NFPA 54: National Fuel Gas Code)
2024 UPC- 506.1.1 Other Types of Appliances.
True or False
True or False: Where exhaust fans, clothes dryers and kitchen ventilation systems interfere with the operation of appliances, makeup air must be provided.
TRUE
Where exhaust fans, clothes dryers, and kitchen ventilation systems interfere with the operation of appliances, makeup air shall be provided. [NFPA 54:9.3.1.5] (NFPA 54: National Fuel Gas Code)
2024 UPC- 506.1.3 Makeup Air.
Fill in the blank
The minimum required combustion air volume shall be _____ cubic feet per 1000 BTU/hour.
50 cu. Ft.
The required volume shall be not less than 50 cubic feet per 1000 British thermal units per hour (Btu/hr) (4.83 m3/kW). [NFPA 54:9.3.2.1] (NFPA 54: National Fuel Gas Code)
2024 UPC- 506.2.1 Standard Method
Fill in the blank
Required combustion air ducts shall not be less than _____ inches in the least dimension.
3 inches
(1) Combining spaces on the same story. Each opening shall have a minimum free area of 1 square inch per 1000 Btu/h (0.002 m2/kW) of the total input rating of all appliances in the space but not less than 100 square inches (0.065 m2). One permanent opening shall commence within 12 inches (305 mm) of the top of the enclosure and one permanent opening shall commence within 12 inches (305 mm) of the bottom of the enclosure (see Figure 506.3). The minimum dimension of air openings shall not be less than 3 inches (76 mm).
2024 UPC- 506.3 Indoor Opening Size and Location.
Fill in the blank
Openings shall be located so that one combustion air opening extends within the upper _____ inches of the appliance enclosure.
12 inches
Two permanent openings, one commencing within 12 inches (305 mm) of the top of the enclosure and one commencing within 12 inches (305 mm) of the bottom of the enclosure, shall be provided.
2024 UPC- 506.4.1 Two Permanent Opening Method
Fill in the blank
Openings shall be located so that one combustion air opening extends within the lower _____ inches of the appliance enclosure.
12 inches
Two permanent openings, one commencing within 12 inches (305 mm) of the top of the enclosure and one commencing within 12 inches (305 mm) of the bottom of the enclosure, shall be provided.
2024 UPC- 506.4.1 Two Permanent Opening Method
Which of the following should supply outdoor combustion air?
One or two permanent openings.
Two permanent openings, one commencing within 12 inches (305 mm) of the top of the enclosure and one commencing within 12 inches (305 mm) of the bottom of the enclosure, shall be provided.
2024 UPC- 506.4.1 Two Permanent Openings Method.
Fill in the blank
Where the design and free area are not known, it shall be assumed that wood louvers will have _____ percent free area.
25 percent
The required size of openings for combustion, ventilation, and dilution air shall be based on the net free area of each opening. Where the free area through a design of louver, grille, or screen is known, it shall be used in calculating the size opening required to provide the free area specified. Where the louver and grille design and free area are not known, it shall be assumed that wood louvers have 25 percent free area and metal louvers and grilles have 75 percent free area. Nonmotorized louvers and grilles shall be fixed in the open position. [NFPA 54:9.3.7.1] (NFPA 54: National Fuel Gas Code)
2024 UPC- 506.8 Louvers, Grilles, and Screens.
Fill in the blank
Where the design and free area are not known, it shall be assumed that metal louvers and grilles will have _____ percent free area.
75 percent
The required size of openings for combustion, ventilation, and dilution air shall be based on the net free area of each opening. Where the free area through a design of louver, grille, or screen is known, it shall be used in calculating the size opening required to provide the free area specified. Where the louver and grille design and free area are not known, it shall be assumed that wood louvers have 25 percent free area and metal louvers and grilles have 75 percent free area. Nonmotorized louvers and grilles shall be fixed in the open position. [NFPA 54:9.3.7.1] (NFPA 54: National Fuel Gas Code)
2024 UPC- 506.8 Louvers, Grilles, and Screens.
Fill in the blank
Water heaters may be installed in a garage, provided all burners and burner-ignition devices are at least _____ inches above the floor.
18 inches
Appliances in residential garages and in adjacent spaces that open to the garage and are not part of the living space of a dwelling unit shall be installed so that all heating elements, switches, burners, and burner-ignition devices are located not less than 18 inches (457 mm) above the floor.
2024 UPC- 507.13 Installation in Residential Garages.