Ch 6 - Water Supply Flashcards
Fill in the blank
Flushometer valves may be substituted for _____.
Flush tanks
Each plumbing fixture shall be provided with an adequate supply of potable running water piped thereto in an approved manner, so arranged as to flush and keep it in a clean and sanitary condition without danger of backflow or cross-connection. Water closets and urinals shall be flushed using an approved flush tank or flushometer valve.
2024 UPC- 601.2 Water Supply and Flushing.
Fill in the blank
Water closets and urinals shall be flushed by means of an approved flush tank or _____ valve.
Flushometer
Each plumbing fixture shall be provided with an adequate supply of potable running water piped thereto in an approved manner, so arranged as to flush and keep it in a clean and sanitary condition without danger of backflow or cross-connection. Water closets and urinals shall be flushed using an approved flush tank or flushometer valve.
2024 UPC- 601.2 Water Supply and Flushing.
True or False
True or False: Each plumbing fixture shall be provided with an adequate supply of potable running water arrange as to flush and keep it clean and sanitary without danger of backflow or cross-connection.
TRUE
Each plumbing fixture shall be provided with an adequate supply of potable running water piped thereto in an approved manner, so arranged as to flush and keep it in a clean and sanitary condition without danger of backflow or cross-connection. Water closets and urinals shall be flushed using an approved flush tank or flushometer valve.
2024 UPC- 601.2 Water Supply and Flushing.
What colors are used to identify potable water, when a building has both potable and nonpotable water?
Green background with white lettering
Green background with white lettering.
2024 UPC- 601.3.1 Potable Water.
What colors are used to identify nonpotable water, when a building has both potable and nonpotable water?
Yellow background with black lettering.
Except as required by Section 601.3.3, nonpotable water systems shall have a yellow background with black uppercase lettering, with the words “CAUTION: NONPOTABLE WATER, DO NOT DRINK.” Each nonpotable system shall be identified to designate the liquid being conveyed, and the direction of normal flow shall be clearly shown. The minimum size of the letters and length of the color field shall comply with Table 601.3.2.
2024 UPC- 601.3.2 Color and Information.
Fill in the blank
An Atmospheric Vacuum Breaker (AVB) consists of a body, a checking member and an _____ opening.
Atmospheric
An atmospheric vacuum breaker consists of a body, a checking member, and an atmospheric port.
2024 UPC- 603.3.2 Atmospheric Vacuum Breaker (AVB).
Fill in the blank
Where potable water is discharged to the drainage system it shall be by means of an approved airgap of _____ pipe diameters of the inlet.
2 pipe diameters
Direct connections between potable water piping and sewer-connected wastes shall not be permitted to exist under any condition with or without backflow protection. Where potable water is discharged to the drainage system, it shall be by means of an approved air gap of two pipe diameters of the supply inlet, but in no case shall the gap be less than 1 inch (25.4 mm). Connection shall be permitted to be made to the inlet side of a trap provided that an approved vacuum breaker is installed not less than 6 inches (152 mm), or the distance according to the device’s listing, above the flood-level rim of such trapped fixture, so that at no time will such device be subjected to backpressure.
2024 UPC- 603.4.4 Connections.
Fill in the blank
Direct connections between potable water piping and sewer connected wastes shall not exist under any condition with or without _____ protection.
Backflow
Direct connections between potable water piping and sewer-connected wastes shall not be permitted to exist under any condition with or without backflow protection. Where potable water is discharged to the drainage system, it shall be by means of an approved air gap of two pipe diameters of the supply inlet, but in no case shall the gap be less than 1 inch (25.4 mm). Connection shall be permitted to be made to the inlet side of a trap provided that an approved vacuum breaker is installed not less than 6 inches (152 mm), or the distance according to the device’s listing, above the flood-level rim of such trapped fixture, so that at no time will such device be subjected to backpressure.
2024 UPC- 603.4.4 Connections.
Fill in the blank
In cold climate areas, backflow assemblies and devices shall be protected from _____ by a method acceptable to the Authority Having Jurisdiction.
Freezing
In cold climate areas, backflow assemblies and devices shall be protected from freezing with an outdoor enclosure that complies with ASSE 1060 or by a method acceptable to the Authority Having Jurisdiction.
2024 UPC- 603.4.7 Freeze Protection.
Fill in the blank
Water Closet and Urinal Flushometer Valves shall be equipped with a listed _____.
Atmospheric vacuum breaker (AVB)
Water closet and urinal flushometer valves shall be protected against backflow by an approved backflow prevention assembly, device, or method. Where the valves are equipped with an atmospheric vacuum breaker, the vacuum breaker shall be installed on the discharge side of the flushometer valve with the critical level not less than 6 inches (152 mm), or the distance according to its listing, above the overflow rim of a water closet bowl or the highest part of a urinal.
2024 UPC- 603.5.1 Atmospheric Vacuum Breaker.
Fill in the blank
Water Closet and Urinal Tanks shall be equipped with a listed _____.
Ballcock
Water closet and urinal tanks shall be equipped with a ballcock. The ballcock shall be installed with the critical level not less than 1 inch (25.4 mm) above the full opening of the overflow pipe. In cases where the ballcock has no hush tube, the bottom of the water supply inlet shall be installed 1 inch (25.4 mm) above the full opening of the overflow pipe.
2024 UPC- 603.5.2 Ballcock.
Fill in the blank
Heat exchangers used for heat transfer, heat recovery, or solar heating shall protect the potable water system from being _____ by the heat transfer medium.
Contaminated
Heat exchangers used for heat transfer, heat recovery, or solar heating shall protect the potable water system from being contaminated by the heat-transfer medium. Single-wall heat exchangers used in indirect-fired water heaters shall meet the requirements of Section 505.4.1. Double-wall heat exchangers shall separate the potable water from the heat-transfer medium by providing a space between the two walls that are vented to the atmosphere.
2024 UPC- 603.5.4 Heat Exchangers.
Fill in the blank
Hose connections in health care or laboratory areas shall not be less than _____ feet above the floor.
6 feet
Vacuum breakers for washer-hose bedpans shall be located not less than 5 feet (1524 mm) above the floor. Hose connections in health care or laboratory areas shall be not less than 6 feet (1829 mm) above the floor.
2024 UPC- 603.5.15 Health Care or Laboratory Areas.
Fill in the blank
Combination stop-and-waste valves or cocks shall not be installed _____.
Underground
Potable water outlets, freeze-proof yard hydrants, combination stop-and-waste valves, or other fixtures that incorporate a stop and waste feature that drains into the ground shall not be installed underground.
2024 UPC- 603.5.17 Potable Water Outlets and Valves.
True or False
True or False: Water distribution pipe and building supply water pipe and fittings can be made of copper alloy.
TRUE
Pipe, tube, fittings, solvent cement, thread sealants, solders, and flux used in potable water systems intended to supply drinking water shall comply with NSF/ANSI/CAN 61. Where pipe fittings and valves are made from copper alloys containing more than 15 percent zinc by weight and are used in plastic piping systems, they shall be resistant to dezincification and stress corrosion cracking in compliance with NSF/ANSI 14. Materials used in the water supply system, except valves and similar devices, shall be of a like material, except where otherwise approved by the Authority Having Jurisdiction. Materials for building water piping and building supply piping shall comply with the applicable standards referenced in Table 604.1.
2024 UPC- 604.1 Pipe, Tube, and Fittings. 2024 UPC- Table 604.1 Materials for Building Supply and Water Distribution Piping and Fittings (page 103)