Chapter 5: Hot Water Heating System Equipment & Operation Flashcards

1
Q

Special diverter fittings are required in __________ to ensure an adequate flow of water though each convector.
A) One-pipe hot water system
B) Loop system
C) Two-pipe reverse return systems
D) Multi-zone systems

A

A) One-pipe hot water system

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

With the pump running in a hot water heating system, the normal differential pressure between the suction and discharge is ___________.
A) 25kPa (4psi)
B) 55kPa (8psi)
C) 75kPa (12psi)
D) 10kPa (1.5psi)

A

B) 55kPa (8psi)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

Which of the following should be included in the routine operation of a hot water heating system?
A) Testing the controls and safety relief valve on a regular basis
B) Keeping the boiler room and boiler clean and tidy
C) Refer periodically to the boiler manufacturer’s operation instructions
D) All of the above

A

D) All of the above

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

If there is an air lock after repairs have been made on the piping system, the operator should:
A) Increase speed of the pump to force out the air
B) Add chemicals to absorb the trapped air
C) Open the system vent valves, or check operation of the automatic air venting system
D) Increase the temperature of the system to boil the trapped air out

A

C) Open the system vent valves, or check operation of the automatic air venting system

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

An air pocket in a hot water heating system will cause:
A) Total or partial blockage of water flow to some parts of the system
B) Noise in the system
C) Insufficient water circulation
D) Insufficient heat in parts of the system
E) All of the above

A

E) All of the above

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

Firing a hot water boiler after refilling with water will result in:
A) Scaling
B) Release of air into the system
C) Change of state
D) Overheating
E) Chemical destabilization

A

B) Release of air into the system

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

The expansion tank in a hot water heating system is normally attached to the:
A) Highest point in the system directly above the boiler
B) Boiler or the hot water supply line near the boiler
C) Return line directly before the boiler
D) Supply line above the lowest convector
E) Supply line after the circulating pump

A

B) Boiler or the hot water supply line near the boiler

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

To prevent hot water heating system damage:
A) The vents should be opened wisely frequently
B) A drain valve should be temporarily installed before the boiler
C) The boiler should be blown down frequently after start up
D) A temporary strainer should be installed before the circulating water pump
E) The expansion valve should be drained several times

A

D) A temporary strainer should be installed before the circulating water pump

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

Typical construction contaminants sometimes encountered in a new hot water system are:
A) Welding slag, soldering flux
B) Thread cuttings, thread cutting oils
C) Pipe dope
D) Dirt
E) All of the above

A

E) All of the above

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

After a steam heating system has been operating for some time, you notice that some sections of the system are still cold. Which one of the following could be the cause of this?
A) Boiler water temperature too low
B) Steam does not contain enough heat
C) Boiler water pressure too low
D) Air is trapped in the affected sections
E) Condensate temperature too low

A

D) Air is trapped in the affected sections

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

Diverter fittings are used in one pipe system in the supply lines to heating units when:
A) A higher heating output is required from the heating unit
B) To compensate for a low heating load
C) The distance from the boiler to heating unit is short
D) There are no balancing valves installed in the supply line
E) A hydraulic balance must be corrected

A

A) A higher heating output is required from the heating unit

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

The highest point of a heating system above the boiler is 19.8m. The pressure on the boiler should indicate at least:
A) 255kPa
B) 25psi
C) 206kPa
D) 46psi
E) 216kPa

A

C) 206kPa (19.8x21m=206kPa)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

A new hot water system must be cleaned before start up to:
A) Prevent air infiltration
B) Keep the boiler inspector happy
C) Prevent the water from becoming acidic and corrosive
D) Keep the water clean
E) Fulfill the contractor’s obligation

A

C) Prevent the water from becoming acidic and corrosive

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

To regulate the flow of hot water to a zone circuit a:
A) Diverter fitting is used
B) Flow control valve is used
C) Pressure reducing valve is used
D) Gate valve is used
E) Balancing valve is used

A

E) Balancing valve is used

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

The correct quantity for each chemical used to clean a heating boiler includes:
1. 1kg/420L of trisodiumphosphate
2. 2L/340L of 18% muriatic acid
3. 1kg/420L of caustic soda
4. 1kg/250L of soda ash

A) 1,2,3,4
B) 1,3,4
C) 2,3,4
D) 1,2,4
E) 1,2,3

A

B) 1,3,4

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

An air separator should always be installed in a/an:
A) Horizontal pipe
B) Cross tee
C) Expansion tank
D) Converter
E) Vertical pipe

A

A) Horizontal pipe

17
Q

What type of air vent uses discs that readily absorb water and expand?
A) Hygroscopic
B) Handwheel
C) Airtrol
D) Manual Petcock
E) Float operated

A

A) Hygroscopic

18
Q

One of the chemicals used for the alkaline boil out solution is:
A) Sodium sulphate (NaSO4)
B) Sodium carbonate (soda ash)
C) Sodium chloride (salt)
D) Calcium carbonate (CaCO2)
E) Sodium sulphite (NaSO3)

A

B) Sodium carbonate (soda ash)

19
Q

To avoid cavitation in the pump the pressure at the highest point of the system should be at least equivalent to a head of water of:
A) 0.9m (3ft)
B) 2.2m (7.2ft)
C) 2m (6.6ft)
D) 1.2m (4ft)
E) 1.5m (4.9ft)

A

D) 1.2m (4ft)

20
Q

The closed expansion tank in hot water heating system has a gauge glass showing the level of water and air in the tank and would normally be from ________ the capacity of the tank.
A) 1/2 to 2/3
B) 1/4 to 1/2
C) 1/2 to 3/4
D) 3/4 to 7/8
E) 1/8 to 1/3

A

A) 1/2 to 2/3

21
Q

Air in hot water heating systems forms air pockets which __________.
A) Increase the flow of steam
B) Increase the flow of water
C) Restrict or even block the flow of steam
D) Restrict the flow of heat
E) Restrict or even block the flow of water

A

E) Restrict or even block the flow of water

22
Q

Zone circuits in multi-zone hot water heating system require a/an _______ to provide the same flow resistance in each circuit.
A) Zone valve
B) Air separator
C) Air vent
D) Zone pump
E) Balancing valve

A

E) Balancing valve

23
Q

The use of the ope expansion tank in hot water heating system is normally limited to a maximum water temperature of:
A) 80ºC (176ºF)
B) 100ºC (212ºF)
C) 90ºC (194ºF)
D) 60ºC (140ºF)
E) 70ºC (158ºF)

A

A) 80ºC (176ºF)

24
Q

Air separators used in hot water heating systems trap the air and direct it to the:
A) Hot water heater
B) Radiator
C) Expansion tank
D) Boiler
E) Convector

A

C) Expansion tank

25
Q

Air in hot water heating systems collects in the _______ of piping and heating units.
A) Down corners
B) High spots
C) Horizontal mains
D) Vertical risers
E) Return lines

A

B) High spots

26
Q

If there is an air lock after repairs have been made on the piping system, the operator should:
A) Increase the temperature of the system to boil the trapped air out
B) Install a more powerful pump
C) Add chemicals to absorb the trapped air
D) Open the systems vent valves or check operation of the automatic air venting system
E) Increase speed of the pump to force out the air

A

D) Open the systems vent valves or check operation of the automatic air venting system

27
Q

To prevent larger particles from reaching the circulating pump, it is common practice to install a temporary _________ in the suction line.
A) Filter
B) Screen
C) Strainer
D) Blank
E) Disc

A

C) Strainer