LOOP/LOFC Flashcards
What are the two safety functions assumed in LOOP/LOFC and how are they maintained?
Reactivity control is maintained in mode 3 hot standby. SDM is assured by CEAs inserted. Tc is held as constant as possible.
Core Heat Removal is maintained by feeding and steaming with ADVs and thru the use of AFA.
Identify the concern with RCP coastdown used throughout the safety analysis.
Safety analysis assumes that the RCPs remain energized for at least 3 seconds during a MT trip and LOOP. This additional time along with the coasdown features of the RCPs provides flow for the removal of maximum generated decay heat in the seconds following a trip.
Identify the accidents or AOOs that assume a LOOP.
SGTR
ESD
LOCA
LOAF
RCP shaft shear.
State the entry criteria that is not obvious for LOOP/LOFC.
A station blackout has occured, at least one 4.16kv bus has been restored from:
EDG, other unit EDG, offsite power.
Subcooled natural circulation is to be used for RCS heat removal although at least one non vital 13.8kv AC bus is energized.
What ORP is appropriate when a LOOP/LOFC exists in conjunction with a LOCA, ESD SGTR or LOAF?
LOOP/LOFC is appropriate only when no other major events are in progress.
The specific ORPs covering those events are designed to mitigate them in the face of a loss of nonvital power.
Identify the major mitigation strategies for a LOOP/LOFC.
Perform SFSCs to confirm it is the only event occurring.
Place plant in a stable condition.
Either maintain Hotstandby or cooldown to SDC conditions.
Attempt to restore power
IF power restored, restore major plant equipment and restart RCPs.
If power not restored, EOP provides cooldown guidance to place SDC inservice and then transition to GOPs. SDC transition covered by GOP procedures.
Why is seal inj. isolated prior to restoring a CHP to operation?
Seal inj. must be isolated to prevent a rapid cooldown of the RCP seals and thus damage. Once a CHP is running, seal inj should be restored.
Why is the always running CHP handswitch taken to stop following a LOOP?
With no SIAS or CIAS actuations, the always running CHP will be antipumped. It will subsequently have to be manually started by clearing the antipump. This is done by taking the handswitch to stop.
Why is an MSIS initiated on receipt of a LOOP?
Initiating an MSIS prevents overpressurizing the main condenser in the event of a loss of vacuum due to a loss of CW from the loss of offsite power.
SG blowdown is isolated as well by the MSIS to minimize the amount of secondary inventory that is lost.
What parameters are checked to ensure natural circulation is occurring and is adequate?
Loop dT is < 65F
Thot and Tcold are constant or lowering
RCS is > 24F subcooled using CET subcooling.
< 30F dT between Thot RTDs and Max quadrant CET temperature.
Why is SApp 53 - align deenergized buse performed during a LOOP.
SA 53 opens breakers on the deenergized buses to allow for proper laoding when the buses are reenergized. This sets up the electrical distribution system to be reenergized, it DOES NOT brink power back.
Per SA 53 - Aligning deenergized buses, why are the buses checked for tripped relays and when does this have to be performed?
The direction to check deenergized buses for tripped relays and reset if necessary. This SA is at the discretion of the CRS. If the reason is known and there is no possibility of damage to the buses, then there is not need to wait until the inspection is completed before reenergizing buses.
State the time limitation associated with energizing NAN-S07 from the SBOG and its basis.
SBOG design assumes that offsite power or the SBOG is available to supply power to the local bus. In the case of a LOOP where DGs start and load, there is no power to the SBOG local bus and therefore no power to the battery chargers. Since those batteries are rated for 1 hour, an SBOG is started within 1 hour so as to maintain the SBOG available to cope with a SBO or interruption of power.
WHy is it necessary to energize switchyard loads from the SBOGs?
SWYD loads are supplied from the SBOGs to supplement SWYD batteries and supply power to the arc suppressor air compressors, ensuring SWYD bkr operation.
Why would SWYD loads NOT be energized from the SBOGs if they are deenergized?
IF the SWYD is deenergized and BOTH:
- power restoration is not expected in 2 hours.
- thunderstorm activity is not present near PVGS
Then perform SA 54 - Energize SWYD loads from the SBOGs.
If lightning is IN the vicinity of PVGS, SA 54 will NOT BE PERFORMED.