T7 RIPCI Flashcards

1
Q

RD 513/2017 COMPOSICIÓN

A

1 ARTICULO
1 DISP ADICIONAL
1 DISP DEROGATORIA
5 DISP FINALES

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

RIPCI COMPOSICIÓN

A
23 ARTICULOS
6 CAPITULOS
5 DISP ADICIONALES
4 DISP TRANSITORIAS
4 ANEXOS
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

ENTRADA EN VIGOR DEL RIPCI

A

A LOS 6 MESES TRAS PUBLICACIÓN EN EL BOE (12 DICIEMBRE DE 2017)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

OPCIONES ACREDITACIÓN CUMPLIMIENTO DE REQUISITOS

A
  • MARCADO CE (UNE-EN)
  • MARCA DE CONFORMIDAD A NORMA (UNE)
  • EVALUACIÓN TÉCNICA
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

EXCEPCIONES EMPRESAS INSTALADORAS RESPECTO A EXTINTORES PORTÁTILES Y MANTAS IGNÍFUGAS

A

<100 M2 O VIVIENDA UNIFAMILIAR: USUARIO

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

SEGURO RESPONSABILIDAD CIVIL EMPRESAS INSTALADORAS Y MANTENEDORAS

A

800.000€ O MÁS, SI SE CONSIDERA OPORTUNO

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

CERTIFICADO DE CALIDAD EMPRESAS INSTALADORAS Y MANTENEDORAS

A

SE CONSIDERA CUMPLIDO POR MÁX 1 AÑO SI LO TIENES EN MARCHA

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

TIEMPO QUE TARDA LA COMUNIDAD AUTÓNOMA EN RESOLVER EN CASO DE DESACUERDO ENTRE EMPRESA INSTALADORA Y TITULAR

A

2 MESES MÁXIMO

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

TIEMPO IMPOSIBILIDAD PRESENTAR NUEVA DECLARACIÓN RESPONSABLE EN CASO DE FALSIFICACIÓN, NO PRESENTACIÓN DE LA DECLARACIÓN RESPONSABLE, … EMPRESAS INSTALADORAS Y MANTENEDORAS

A

1 AÑO

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

TIEMPO PARA COMUNICAR A LA C.A. EN CASO DE MODIFICACIÓN DE DATOS, CESE DE ACT, … EMPRESAS INSTALADORAS Y MANTENEDORAS

A

1 MES MÁXIMO

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

TIEMPO QUE DEBEN CONSERVAR LAS EMPRESAS MANTENEDORAS LA DOCUMENTACIÓN JUSTIFICATIVA DE LAS OPERACIONES REALIZADAS

A

5 AÑOS

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

CUANDO SOLICITAR INSPECCIONES PERIÓDICAS NO REGULADAS POR REGLAMENTACIÓN ESPECÍFICA Y EXCEPCIONES (USO RESIDENCIAL VIVIENDA, USO ADMIN, USO DOCENTE, USO COMERCIAL, USO PÚBLICA CONCURRENCIA Y USO APARCAMIENTO)

A

SOLICITAR, AL MENOS, CADA 10 AÑOS. HAY EXCEPCIONES:

  • USO RESIDENCIAL VIVIENDA
  • USO ADMIN < 2000 M2
  • USO DOCENTE <2000 M2
  • USO COMERCIAL <5OO M2
  • USO PÚBLICA CONCURRENCIA <500 M2
  • USO APARCAMIENTO <500 M2

???

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

TIEMPO ADAPTACIÓN SISTEMAS DEL RIPCI VIEJO QUE AHORA DEBEN LLEVAR MARCA DE CONFORMIDAD O SUJETOS A NORMA

A

2 AÑOS MÁX.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

TIEMPO DE ADAPTACIÓN SISTEMAS DEL RIPCI VIEJO QUE AHORA DEBEN PASAR MANTENIMIENTO

A

1 AÑO MÁX.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

TIEMPO ADAPTACIÓN EMPRESAS INSTALADORAS/MANTENEDORAS RIPCI VIEJO

A

1 AÑO MÁX.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

1ª INSPECCIÓN SISTEMAS YA EXISTENTES EN RIPCI VIEJO Y EXCEPCIONES

A

10 AÑOS MÁX. EXCEPCIONES SI TIENEN +10 AÑOS:

  • 10-14 AÑOS: 3 AÑOS
  • 15-19 AÑOS: 2 AÑOS
  • 20 O MÁS AÑOS: 1 AÑO
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
17
Q

DISTANCIA PULSADORES

A

25 METROS DESDE CUALQUIER PUNTO ORIGEN DE EVACUACIÓN

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
18
Q

DISTANCIA PULSADOR-SUELO

A

PARTE SUPERIOR-SUELO 80-120 CM

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
19
Q

DISPOSITIVOS ACÚSTICOS Y VISUALES DE DETECCIÓN Y ALARMA CUANDO SON NECESARIOS

A

RUIDO AMBIENTE >60 dB

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
20
Q

TIPOS HIDRANTE COLUMNA

A

B- HÚMEDA

C- SECA

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
21
Q

HIDRANTES DE COLUMNA ADMITIDOS

A

PAR 2

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
22
Q

MST (PAR MINIMO DE RESISTENCIA DEL SIST DE ROTURA) HIDRANTES COLUMNA SECA

A

250 N*M

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
23
Q

PFA (PRESIÓN DE SERVICIO) HIDRANTES ARQUETA

A

1600 KPA, 16 BAR, 16 KG/CM2

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
24
Q

TABLA KV MÍNIMO (PRESIÓN Y CAUDAL) HIDRANTES EN FUNCIÓN DE SALIDAS

A

SALIDAS COLUMNA ARQUETA
1 DE 45 33 33
2 DE 45 66 66
1 DE 70 80 80
2 DE 70 150 150
1 DE 90/100 180 150

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
25
Q

REQUISITOS ZONA PROTEGIDA POR HIDRANTES

A
  • RECORRIDO HORIZONTAL EN ZONA URBANA <100M
  • RECORRIDO HORIZONTAL EN RESTO DE ZONAS <40M

AL MENOS 1 HIDRANTE A LA ENTRADA DEL EDIFICIO, CON SALIDA DE 100 MM Y DE ESPALDAS A FACHADA
-DISTANCIA HIDRANTE-EDIFICIO DE 5-15 M

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
26
Q

OBLIGACIONES HIDRANTES. CAUDAL Y PRESIÓN.

A
  • CAUDAL MÍNIMO POR BOCA: 500 L/MIN
  • PRESIÓN MIN POR BOCA EN CIUDAD: 100 KPA, 1 BAR, 1KG/CM2
  • PRESIÓN MIN POR BOCA EN RESTO DE ZONAS: 500 KPA, 5 BAR, 5 KG/CM2
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
27
Q

TIPOS EXTINTORES

A
  • PORTÁTILES: HASTA 20 KG

- MÓVILES: > 20 KG

28
Q

DISTANCIA EXTINTOR-SUELO

A

SOPORTES A 80-120 CM

29
Q

RECORRIDO HORIZONTAL HASTA EXTINTORES

A

15 METROS MÁX.

30
Q

TIPOS FUEGO

A
A-SOLIDOS
B-LIQUIDOS/SOLIDOS LICUABLES
C-GASES
D-METALES
F-ACEITES Y GRASAS DE COCINA
31
Q

TIPOS BIES

A

MANGUERA PLANA 45 MM

MANGUERA SEMIRRIGIDA 25 MM

32
Q

FACTOR K MÍNIMO BIES (DETERMINA DIAMENTRO DE BOQUILLA Y PRESIONES)

A

SEMIRRIGIDA: 42 (10 MM)
PLANA: 85 (13 MM)

33
Q

DIÁMETRO BIE ALTA PRESIÓN

A

MÁX 12 MM (SE PUEDEN ADMITIR SUPERIORES)

34
Q

DISTANCIA BIE-SUELO

A

MÁX 1,5 M DEL SUELO

35
Q

DISTANCIA BIE-SALIDA SECTOR

A

MÁX 5 METROS

36
Q

RADIO ACCIÓN BIE PLANA/SEMIRRIGIDA

A

LONGITUD MANGUERA +5 METROS

37
Q

SEPARACIÓN BIE PLANA/SEMIRRIGIDA

A

MÁX 50 METROS

38
Q

LONGITUD MÁXIMA BIE PLANA

A

20 METROS

39
Q

LONGITUD MÁXIMA BIE SEMIRRIGIDA

A

30 METROS

40
Q

PRUEBAS BIES PLANAS/SEMIRR. TIEMPO DE FUNCIONAMIENTO Y PRESIÓN.

A
  • AL MENOS 1 HORA FUNCIONANDO LAS 2 MÁS DESFAVORABLES A UNA PRESIÓN DE ENTRADA DE 300 KPA, 3KG/CM2, 3 BAR - 600 KPA, 6 KG/CM2, 6 BAR.
  • PRUEBA PRESIÓN ESTÁTICA = PRESIÓN MÁX DE SERVICIO. MÍNIMO 980 KPA, 10 KG/CM2, 10 BAR DURANTE 2 H
41
Q

SEPARACIÓN BIES ALTA PRESIÓN

A

RADIO DE ACCIÓN MANGUERAS X2 COMO MAXIMO

42
Q

LONGITUD MAXIMA BIE ALTA PRESIÓN

A

30 METROS

43
Q

PRUEBAS BIES ALTA PRESIÓN. TIEMPO DE FUNCIONAMIENTO Y PRESIÓN.

A
  • AL MENOS 1 HORA FUNCIONANDO LAS 2 MÁS DESFAVORABLES A UNA PRESIÓN DE SALIDA DE 3450 KPA, 35 KG/CM2,35 BAR
  • PRUEBA PRESIÓN 1,5 VECES LA PRESIÓN DE TRABAJO MÁXIMA DURANTE AL MENOS 2 HORAS
44
Q

IPF-41

A

COLUMNA SECA FACHADA
RACORES DE 70MM
LLAVE DE PURGA DE 25MM

45
Q

IPF-39

A

BOCA SALIDA EN PLANTA COLUMNA SECA

46
Q

IPF-40

A

BOCA SALIDA EN PLANTA + VALVULA DE SECCIONAMIENTO

47
Q

ESQUEMA COLUMNA SECA ASCENDENTE

A
  • SALIDAS EN PLANTAS PARES HASTA LA 8ª Y EN TODAS A PARTIR DE ESTA
  • RACORES DE 45MM
  • VALVULAS DE SECCIONAMIENTO CADA 4 PLANTAS. POR ENCIMA DE SALIDA
48
Q

ESQUEMA COLUMNA SECA DESCENDENTE

A
  • SALIDA Y VALVULA DE SECCIONAMIENTO EN CADA PLANTA. POR DEBAJO DE SALIDA
  • RACORES DE 45MM
49
Q

DISTANCIA BOCAS COLUMNA SECA-SUELO

A

CENTRO DE LA BOCA A 0,90 M DEL SUELO

50
Q

DISTANCIA MÁXIMA COLUMNAS SECAS

A

60 METROS

51
Q

PRUEBA COLUMNA SECA. TIEMPO DE FUNCIONAMIENTO Y PRESIÓN.

A

PRESIÓN ESTATICA = PRESIÓN MÁX DE SERVICIO

  • MINIMO 1470 KPA, 15 KG/CM2, 15 BAR EN COLUMNA DE MAX 30 METROS, DURANTE 2 HORAS MINIMO
  • MINIMO 2450 KPA, 25 KG/CM2, 25 BAR EN COLUMNA DE MÁS DE 30 METROS, DURANTE 2 HORAS MINIMO
52
Q

CADUCIDAD MANTAS IGNÍFUGAS

A

MÁX 20 AÑOS

53
Q

VIDA ÚTIL DETECTORES

A

MÁX 10 AÑOS

54
Q

VIDA UTIL MANGUERAS BIES

A

MÁX 20 AÑOS

55
Q

VIDA UTIL SEÑALES FOTOLUMINISCENTES Y EXCEPCIÓN.

A

10 AÑOS. SALVO QUE EN LA REVISIÓN DEN VALORES >80% DEL RENDIMIENTO. DESPUÉS, REVISIONES CADA 5 AÑOS.

56
Q

QUIÉNES PODRAN SOLICITAR CERTIFICACIÓN ACREDICATIVA DE CUALIFICACIÓN COMO OPERARIOS CUALIFICADOS PARA LA INSTALACIÓN/MANTENIMIENTO DE INSTALACIONES CONTRA INCENDIOS FRENTE AL NUEVO RIPCI

A

AQUELLOS TRABAJADORES QUE PRESTEN O HAYAN PRESTADO SERVICIOS DURANTE MINIMO 12 MESES ANTERIORES A LA ENTRADA EN VIGOR DEL ACTUAL RIPCI

57
Q

ANEXO I RIPCI

A

EQUIPOS Y SISTEMAS

58
Q

ANEXO II RIPCI

A

MANTENIMIENTO MÍNIMO (TABLAS)

59
Q

ANEXO III RIPCI

A

MEDIOS HUMANOS MINIMOS

60
Q

ANEXO IV

A

CONOCIMIENTOS MINIMOS NECESARIOS PARA LOS OPERARIOS CUALIFICADOS

61
Q

TABLAS ANEXO II

A

I - PROGRAMA TRIMESTRAL Y SEMESTRAL (FAB, MANT, US)

II - PROGRAMA ANUAL Y QUINQUENAL (FAB Y MANT)

III - PROGRAMA SEÑALIZACIÓN LUMINISCENTE ANUAL (FAB, MANT, US)

62
Q

MANTENIMIENTO EXTINTORES

A
  • TRIMESTRAL: LO BÁSICO (INSP VISUAL). UNE 23120
  • ANUAL: UNE 23120 Y EXTINTORES MÓVILES BUEN ESTADO DE TRASLADO
  • QUINQUENAL: PRUEBA NIVEL C (TIMBRADO) Y RETIMBRADO POSTERIOR
63
Q

MANTENIMIENTO BIES

A
  • TRIMESTRAL: SEÑALIZACIÓN
  • ANUAL: UNE-EN 671-3
  • QUINQUENAL: UNE 671-3
64
Q

MANTENIMIENTO HIDRANTES

A
  • TRIMESTRAL: SEÑALIZACIÓN, INSP VISUAL, ACCESIBILIDAD, QUITAR TAPAS Y ENGRASAR ROSCAS
  • SEMESTRAL: ENGRASAR TUERCA ACCIONAMIENTO O RELLENAR CÁMARA DE ACEITE. ABRIR Y CERRAR HIDRANTE
  • ANUAL: ESTANQUEIDAD TAPONES
  • QUINQUENAL: CAMBIO JUNTAS RACORES
65
Q

MANTENIMIENTO COLUMNAS SECAS

A
  • SEMESTRAL: LO BÁSICO (INSP VISUAL, ACCESIBILIDAD, SEÑALIZACIÓN, …)
  • QUINQUENAL: PRUEBA DE LA INSTALACIÓN