General Flashcards

1
Q

Purpose?

A
  • Provides the emergency busses (E1 and E2) with power in the event of a loss of offsite power to these busses.
  • In the event of an automatic safeguards actuation the EDG’s will startup.
  • EDG’s are essential for the safe shutdown of the plant
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

Design Basis:

A
  • The emergency power supply system consists of two Emergency Diesel Generators.
  • The systems are kept in standby status at all times, with the exception of when maintenance is being performed on the units.
  • Designed to reach rated speed of (900rpm) and voltage (480V) within 10 seconds of the start signal.
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

EDG Description: (load Rating) (with Deepwell)

A
  • Generator load rating is:
    - 2500KW (continuous)
    - Between no more than 2 hours in 24hrs
    - 2750KW Not to be exceeded
    - No more than 4,000 Amps (Output breaker rating)
  • 1500Kw
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

EDG can be manually started from:

1 pre-lube
3 not

A

-The RTGB (preform a 4.5 min pre-lube when started from the RTGB.)

  • Locally at the following (Will not pre-lube)
    - Engine Control Panel (must be in local control)
    - Generator control Panel
    - Hand-Start Valves
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

EDG Auto-starts

A

-SI Signal
(EDG starts but output breaker to E bus will not close unless UV is present)
-UV on respective E-Bus
(430volts for 10 seconds, trips input breaker to respective bus, DV, degraded voltage, causes UV)
(328 volts is under voltage set point)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

E1/E2 UV
and
Degraded Grid Voltage

A
  • Setpoints: 328V (1/2 UV relays)
    - Isolates E-Bus
    - Sheds loads except MCC-5/16, MCC-6/18
    - Starts EDG
    - Starts Blackout Sequencer
  • Setpoint 430V for greater than or equal to 10seconds, causes UV because:
    - Opens normal bus supply breakers
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

SI/UV auto start defeated by?

A

-Local/Remote control switch is in the Local position

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

EDG DC Control power by:

supplies power to (6)

A

-Powered by DP-A(MCC-A) and DP-B(MCC-B)

Supplies:

  • Air start solenoids
  • Voltage Regulator
  • Generator field flash circuitry for the exciter
  • Low speed relay
  • Pressure switches
  • temperature switches