STATE the functions of the Containment Air Handling (CAH) system

A

• The primary function of the containment air handling (CAH) system is to remove the heat generated by equipment within the containment structure.
The CAH secondary functions are:
• Recirculate containment structure air following a loss-of-coolant accident (LOCA) ,
• Filter containment structure air prior to personnel entry.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

Briefly DESCRIBE the flowpath from suction to discharge for the following subsystems of the CAH system: containment structure cooling

A

Filter->Cooling Coils->Fan->Backdraft Damper -> Distribution

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

Briefly DESCRIBE the flowpath from suction to discharge for the following subsystems of the CAH system control rod drive mechanism cooling

A

Shroud Inlets-> Nozzles-> CRDM’s -> Fan’s -> Backdraft Dampers

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

Briefly DESCRIBE the flowpath from suction to discharge for the following subsystems of the CAH system recirculating filter unit (recirc mode)

A

Containment Dome -> Damper -> Fan -> Below 25ft Containment Floor

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

Briefly DESCRIBE the flowpath from suction to discharge for the following subsystems of the CAH system recirculating filter unit (filter mode)

A

Containment 25 ft. to the Filter -> Damper -> Fan -> Below 25 ft. Containment Floor

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

STATE the functions of the Combustible Gas Control (CGC) System

A

– Monitor the concentration of H2 gas within the Containment structure.
– Reduce the concentration of H2 gas in the Containment atmosphere to prevent fires / explosions. (Containment Integrity => fission barrier)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

STATE the functions of the Containment Air Purge (CAP) system

A

• Provides Containment ventilation during refueling operations for personnel comfort
– Note: air is conditioned (heated or cooled via PAH system)
• Provides filtration of Containment exhaust air during refueling operations to ensure potential radioactive releases are within Federal Guidelines
• Provides ventilation for the radiological control access (RCA) walkways (tunnel).
• Provides filtration of RCA exhaust air to ensure any potential radioactive release is within Federal Guidelines

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

Briefly DESCRIBE the flowpaths of the CAP system from the fresh air suction to the discharge to the plant vent in the following mode: RCA Walkway

A

– CAP-MM-726 (CAP-FN-179) RCA air supply heating and ventilation unit supplies 4000 cfm of outside air to the RCA
– CAP-FN-10 discharges air to the Plant vent
– Damper 1013 opened to provide »11,000 CFM back to fan suction via filter for flow balancing

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

Briefly DESCRIBE the flowpaths of the CAP system from the fresh air suction to the discharge to the plant vent in the following mode: Pre-Entry Purge

A

– The Pre-entry Supply Fan (CAP-FN-9) draws 11,000 cfm of air from the PAB supply fan bay
– CAP-FN-9 discharges into a supply header through CAP-V-1&2 (flange removed)
– The supplied air is distributed within the Containment via CAP ductwork
– CAP exhaust air is drawn across the refueling cavity by CAP exhaust fan (CAP-FN-10).
– The exhaust air exits Containment through CAP-V-3 and V-4 (flange removed)
– The exhaust air then passes through a HEPA filter unit (CAP-F-310)
– Air then routed to HEPA/Charcoal filter unit (CAP-F-40) “CAP air cleaning unit” for removal of radioactive gaseous Iodine and radioactive particulate matter
– CAP-FN-10 (Pre-entry Purge exhaust fan) discharges to Plant vent.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

Briefly DESCRIBE the flowpaths of the CAP system from the fresh air suction to the discharge to the plant vent in the following mode: Refueling

A

– The Refueling Purge Supply Fan (CAP-FN-34) draws 31,000 cfm of air from the PAB supply fan bay (same flow path as Pre-Entry)
– Refueling Purge Exhaust Fan (CAP-FN-35) draws 31,000 cfm of air across the refueling cavity (same flow path as Pre-Entry)
– Air routed through F-310
– CAP-FN-35 discharges to Plant Vent

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

STATE the functions of the Containment On-line Purge (COP) system

A

• Purge the containment atmosphere periodically during normal plant operation and to
– Reduce containment pressure
– Reduce containment airborne radiation levels

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

Briefly DESCRIBE the flowpath of the COP system from the fresh air suction to the discharge to the plant vent.

A
  • The COP Supply Fan (COP-FN-73) draws 1,000 cfm of air from the PAB supply fan bay
  • COP-FN-73 discharges air to Containment via COP-V-1 and V-2
  • The “COP” air is mixed by the running CAH Structure Cooling Fans
  • PAH filter exhaust fan PAH-FN-8-A or B draws COP exhaust air from Containment via COP-V-3 and V-4
  • Exhaust air discharged to Plant Vent