Paper 3 Flashcards

1
Q

State the earth return path, external to the installation, for each of the following systems.

i) TN-C-S.
ii) TN-S.
iii) TT.

A

PEN conductor
Separate Metallic conductor
General mass of earth

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

3b State what happens to the value of insulation resistance when

i) a parallel conductor is provided
ii) the conductor length is decreased
iii) a distribution board is measured as a whole instead of the individual circuits.
iv) the cross sectional area of conductors is increased

A

i. Decrease
ii. Increases
iii. Decrease
iv. Stays the same

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

when undertaking insulation resistance testing as part of a periodic inspection what does GN3 identify as normal practice

A

For most installations a test between live conductors connected together and earth is satisfactory
OR; testing between live conductors is not generally required

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

3d State, from the formula Zs = Ze + (R1+R2), what is represented by

i) Zs
ii) Ze
iii) R1+R2.

A

i. System or total EFLZ
ii. External EFLZ
iii. Resistance of line and cpc conductors

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

State the

i) purpose of the IP coding system
ii) level of protection provided by IPXXB
iii) level of protection provided by IP4X.

A

i. Level of protection against solids and moisture.
ii. BS finger to a depth of80 mm
iii. 1 mm wire

How well did you know this?
1
Not at all
2
3
4
5
Perfectly