2100 bms Flashcards

(19 cards)

1
Q

List 9 examples the 2100 can be used for?

A
  1. Line heater 2. Dehydrator 3. Combustor 4. Tank Heater 5. Separator 6. Treater 7. GPU 8. Amine Reboiler 9. Thermal Oxidizer
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

What requirements and approvals does the 2100 have?

A

CSA B149, NFPA 87 and UL approved

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

What is the maximum size burner the 2100 is recommended for?

A

12.5 MMBtuh

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

What power levels can operate the 2100?

A

12vdc or 24vdc

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

What is the maximum current the 2100 can handle without tripping?

A

5 Amps

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

What is the total draw for the 2100?

A

100mA

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

What is the total draw for the system?

A

4 Amps

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

What is the purpose of the low fire?

A

To create a draft in burners which exceed 5 MMBtuh prior to high fire/main opening

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

Where does the dual head thermocouple connect to in the 2100?

A

Process and High temp thermocouple inputs

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

List the 6 dry contact inputs in the 2100

A
  1. Start 2. ESD 3. Proof of closure 4. High pressure 5. low pressure 6. Level
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

What is the start dry contact used for?

A

Remote start/stop typically connected to an independent PLC

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

What is the ESD dry contact used for?

A

Attached to an external emergency shutdown switch such as mushroom switch or PLC dry contact

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

What is the proof of closure dry contact used for?

A

To receive signal from a main valve with proof of closure output capabilities

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

What is the high pressure dry contact used for?

A

Placed after main valve as safety feature to shutdown when high pressure exists

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

What is the low pressure dry contact used for?

A

Connected to a low pressure switch installed in the fuel train

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

What and where is the low pressure setting in the menus?

A

Menu 4 System setup. Pressure/level delay

17
Q

What is the level dry contact used for?

A

Connected to a level switch installed above the fire tube

18
Q

What 2 things can the 4-20 mA contact be used for?

A
  1. temperature output 2. control a proportional valve (modulating)
19
Q

What are the 3 main features of the Modbus expansion card?

A
  1. Remote monitoring 2. remote start/stop 3. remote setpoint adjustment