LOT 201.29 Fire Protection Flashcards

1
Q
  • LOT 201.29 Fire Protection*
    • *

Which fire hydrants are required for tech specs?

A
  • ECW Intake Structure:*
  • *Fire Hydrant #13**
  • Restore OR Route hose within 1 hr*
  • AFWST:*
  • *Fire Hydrant #7 (Unit 1)**
  • Restore OR Route hose within 1 hr*
  • *Fire Hydrant #20 (Unit 2)**
  • Restore OR Route hose within 1 hr*
  • Fire Pump Hose House:***
  • *Fire Hydrant #10**
  • Restore OR Route hose within 1 hr*

Note:
Only required by 0PGP03-ZR-0018.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q
  • LOT 201.29 Fire Protection*
    • *

What auto starts the fire protection pumps?

A

Pump 1:
Header Pressure 130 psig [5 sec TD]
Loss of Power to Panel

Pump 2:
Header Pressure 120 psig [10 sec TD]
Loss of Power to Panel

Pump 3:
Header Pressure 110 psig [15 sec TD]
Loss of Power to Panel

Jockey pump maintains system pressure > 130 psig (35 gpm)

Note:
Jockey pump operated locally in “Hand” position. Auto position non-functional.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q
  • LOT 201.29 Fire Protection*
    • *

What rooms are protected by Halon?

A

Computer Room

Computer Battery Room

Relay Room

TSC Computer Room

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q
  • LOT 201.29 Fire Protection*
    • *

What is required to be FUNCTIONAL in the Fire Protection System?

A

2 Tanks (300,000 gal each)

2 Pumps (2500 gpm each)

  • 1 Pump FUNCTIONAL (Restore in 7 days)
  • Total Volume ≥ 300,000 gal but < 600,000 gals (Restore in 7 days)
  • Pumps AND Volume NOT FUNCTIONAL (Restore in 24 hours)
  • Underground Piping NOT FUNCTIONAL (Restore in 24 hours)

Note:
Only Safety Related portion of the system is the CIVs

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q
  • LOT 201.29 Fire Protection*
    • *

What provides makeup to the FWSTs?

A

Freshwater

Well Water

  • Each FWST contains 300,000 gals
  • Auto Makeup
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q
  • LOT 201.29 Fire Protection*
    • *

If the fire protection pump auto starts, what is the only thing that will trip the pump?

A

Mechanical Overspeed

Applies if pumps start on Low Header Pressure, Loss of power, or remote start from either control room. (CP018)

Note:
Cannot be stopped from control room.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q
  • LOT 201.29 Fire Protection*
    • *

What will trip the fire protection pumps?

A
  • *Overspeed**
  • Electrical / Mechanical*

Low Oil Pressure

High Engine Water Temperature

  • *Low Battery Voltage**
  • Battery A / B*

Low Fuel Level

How well did you know this?
1
Not at all
2
3
4
5
Perfectly