1
Q

What is a second method of compensating for movement within a stack (other than expansion joint)?

A

Horizontal offset in piping that is a minimum of 1.5m (5’)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

Average speed of sewage in sanitary building sewer?

A

2ft/sec

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

Max change of direction on sanitary building sewer?

A

45 degrees

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

Why must you use a normally open back water valve on the sanitary building drain/sewer?

A

Permits air flow within the plumbing system

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

Table for sizing sanitary building drain

A

2.4.10.6. C

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

Max change of direction on a sanitary building drain?

A

Max 135 degrees between cleanouts

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

The sanitary building drain ends at the . . .

A

last connected soil stack connection.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

Table for size and spacing of cleanouts?

A

2.4.7.2. (2)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

Table for sizing individual and continuous vents?

A

2.5.7.1.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

Table for sizing wet vents?

A

2.5.8.1.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

Minimum size wet vent serving a water closet?

A

2”

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

Minimum size continuous vent serving a water closet?

A

1 1/2”

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

A stack vent must be a minimum of _____ the size of the stack at its base.

A

1/2

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

A wet vent that is 2” or less may have a max horizontal offset of _____. Larger than 2” may have a max horizontal offset of _____.

A

1.2m , 2.5m

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

Minimum size roof penetration?

A

3” or one pipe size

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

Minimum size EFD?

A

2” if vented

17
Q

Maximum change of direction on water closet trap arm?

A

225 degrees

18
Q

Table for sizing branch vents, vent headers, circuit vents and continuous vents?

A

2.5.8.3.

19
Q

Table for sizing waste branch?

A

2.4.10.6. B

20
Q

Maximum length of continuous waste?

A

1200mm

21
Q

Is a normally open backwater valve required in residential drainage?

A

No. Only when you have fixtures that are below the adjoining street level.

22
Q

Code for water pressure testing a residential drainage system?

A

Fill system with water to a minimum height of 3 metres (10 feet) for 15 minutes with no leaks