Manual J Flashcards

1
Q

What is the summer infiltration air quantity of an 1800ft² residential structure with 8ft ceilings of average construction in Greensboro, North Carolina?

A
48cfm
Volume x Air Changes Per Hour(ACH) = CFH
CFH ÷ 60 = CFM
1800 x 8 = 14,400ft³
14,400ft³ x .2(ACH) = 2880CFH
2880CFH ÷ 60 = 48CFM
Pg. 389 Manual J
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

A block wall in a residential building has a stucco outside finish, metal studs with R-11 insulation, hollow cells, medium color and an interior finish. If 500ft² of this wall faces west in Raleigh, NC, what is the heat gain from this wall in the summer at design load conditions?

A
692btuh
Cooling HTM = U-value x Table 4B  CLTD Value
Design temp = 92⁰ 
Daily range = M
Group number = H
Default indoor = 75⁰
HTM = .109 x 12.7
HTM = 1.3843
BTUH = 1.3843 x Area
BTUH = 1.3843 x 500ft²
BTUH = 692
Pg. 273, 345, 349, 383
Manual J
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

What is the winter infiltration rate in cfm for a 4000ft², two story single family home of average construction that has one fireplace, 5 bedrooms and contains 36,000 cubic feet of air?

A
242cfm
CFM = Air Changes an Hour x Volume ÷ 60
CFM = .37 x 36,000ft³ ÷ 60
CFM = 13,320 ÷ 60
CFM = 222
Add 20 cfm for the fireplace
CFM = 222 + 20
CFM= 242
Pg. 389, 42 Manual J
How well did you know this?
1
Not at all
2
3
4
5
Perfectly