A320 Systems Flashcards
ATA 21
At what cabin altitude is ECAM EXCESS CAB ALT triggered
9,550 ft
ATA 21
Automatic pressurization law
• CPC uses:
- Landing elevation and QNH from FMGC
- Pressure altitude from ADIRS
• Pressurization schedule:
- Ground (before takeoff and 55 s after landing)
Outflow valve opens fully to ensure that there is no residual cabin pressure
- Take Off, CPC pressurizes at ΔP 0.1 PSI to avoid a pressure surge at rotation.
- Climb, Cabin altitude varies according to a fixed pre-programmed law that takes into account the aircraft’s actual rate of climb.
- Cruise, Cabin altitude is kept at level off value, or at landing field elevation, whichever is higher.
- Descent:
. Cabin rate of descent computed in order to get cabin pressure equal to landing field pressure +0.1 PSI shortly before landing
. Maximum descent rate is 750 ft/min
ATA 21
Cabin Pressure Controllers
- 2 identical, independent, digital controllers automatically control the system, by maintaining proper cabin pressure
- They receive signals from:
- ADIRS
- FMGC
- EIU
- LGCIU
- When the system is in automatic or semi-automatic mode, 1 controller is active, the other is on standby
- The controllers communicate with each other via a cross-channel link
ATA 21
Components of the Pressurization system
- 2 Cabin Pressure Controllers (CPC)
- 1 Residual Pressure Control Unit (RPCU)
- 1 Outflow valve, with an actuator that incorporates 3 motors (2 for automatic and 1 for manual operation)
- 1 Control panel
- 2 Safety valves
ATA 21
Components of the Avionics ventilation system
- 1 Avionics Equipment Ventilation Controller (AEVC)
- 2 electric fans
- Skin air inlet and extract valve
- Air conditioning inlet valve
- Skin exchange isolation valve
ATA 21
Conditions for an automatic transfer of CPC
An automatic transfer occurs:
- 70 s after each landing
- If the operating system fails
ATA 21
Describe the Packs operation
- 2 packs operate automatically and independently of each other
- Warm pre-conditioned bleed air enters via the pack flow control valve, and goes through:
- The primary heat exchanger
- The compressor section of the air-cycle machine where air is Compressed to a higher pressure and temperature
- The main heat exchanger where air is cooled again
- A water separator system where air is dried
- The turbine section, where air expands and generates power to drive the compressor and the cooling air fan.
The removal of energy during this process reduces air temperature, resulting in very low air temperature at turbine discharge.
ATA 21
ECAM BLEED Page, Packs indications
From top to bottom: • Outlet temp • Bypass Valve position • Compressor Outlet temp • Flow
ATA 21
Amber HOT AIR Fault light
• Fault light comes ON when:
- Duct reaches 88 °C
- HOT AIR pressure regulating valve disagrees with selected position
- Hot air pressure regulating valve and trim air valves close automatically
- When temperature drops below 70 °C and Hot Air is switched OFF, light goes OFF
ATA 21
Amber Pack Fault light
- Pack flow control valve disagrees with selected position
- Compressor outlet overheat
- Pack outlet overheat
ATA 21
Pressurization operation
• Automatic Operation:
- FMGS sends an external pressurization Schedule to the CPC
- When FMGS data is not available, select manually the landing field elevation for the CPC to use an internal pressurization Schedule
• Manual Operation, Cabin altitude is controlled via the manual motor of the outflow valve by operating a switch on the pressurization control panel
ATA 21
Pressurization Safety Valves
- 2 independent pneumatic safety valves prevent cabin pressure from going too high (8.6 PSI above ambient) or too low (1 PSI below ambient)
- They are located on the rear pressure bulkhead, above the flotation line
ATA 21
RAM AIR inlet flap logic
- Takeoff, the ram air inlet flap closes when takeoff power is set and the main landing gear struts are compressed
- During landing, it closes as soon as the main landing gear struts are compressed, as longas speed is at or above 70 kt,It opens 20 s after the speed drops below 70 kt
ATA 21
RAM AIR operation
- Used to ventilate the cockpit and cabin to remove smoke, or if both packs fail
- If ΔP is less than 1 PSI and ditching not selected, RAM AIR P/B ON:
- RAM AIR valve opens
- Outflow valve opens about 50 %, provided that it is under automatic control
ATA 21
Residual cabin pressure
Red light flashes close to door window when:
Both engines are stopped and Slides are disarmed
ATA 21
Residual Pressure Control Unit
Residual Pressure Control Unit (RPCU) automatically opens the outflow valve on ground in case of abnormal residual pressure when:
• Both CPCs are failed, or manual mode is selected and• The aircraft is on ground and
• All engines are shutdown or all ADIRS indicate an airspeed below 100 kt.
ATA 21
Under which condition, Hot air pressure regulating valve close automatically
- Duct overheats
- 1 Cockpit trim air valve fails
- Both cabin trim air valves fail
ATA 21
Under which condition, Pack Flow Control Valve close automatically
- Pack Overheating
- Engine Starting
- Operation of Fire or Ditching P/b
ATA 21
Amber Ventilation Blower Fault light
- Blowing pressure low
- Duct overheat
- Computer power supply fails
- Smoke warning activated
ATA 21
Amber Ventilation Extract Fault light
- Extract pressure low
- Computer power supply fails
- Smoke warning activated
ATA 21
Ventilation operation
• On ground:
- Before application of TO power, ventilation system is in open circuit configuration (closed configuration when skin temperature is low)
- After application of TO power, ventilation system is in closed circuit configuration
• In Flight, ventilation system is in closed circuit configuration
ATA 21
Ventilation, Blower/Extract on OVRD
• Either pushbutton on OVRD:
‐ System goes to closed circuit configuration
‐ Air conditioning air is added to ventilation air (blower fan stops if BLOWER P/B is OVRD)
• Both pushbuttons on OVRD:
‐ Air flows from air conditioning system and then overboard
‐ Extract fan continues to run
ATA 21
Air Conditioning System Controler Fault
• 1 Lane fails: no effect
• 2 Lanes fail:
- Pack is lost
- Hot air pressure regulated and trim air valve close
ATA 21
Air Conditioning System Controller / Pack Controller operation
• Each Air Conditioning System Controller / Pack Controller regulate the temperature by:
- Modulating the bypass valve and the ram air inlet flap of its associated pack for basic regulation
- Modulating Trim air valves in each zone duct for optimized regulation