Air Conditioning Flashcards
(40 cards)
What are the objectives ofair conditioningon ships ?
1.To extract excess heat
2.To raise air temperature when required
3.To add moisture as required
4.To reduce moisture content as required
5.To maintain sufficient oxygen and air flow
6.To remove dust
How is the correct temperature on a ship achieved
Comfortable temperature range is about 22°C and relative humidity (RH) about 60% (usually 40 ~ 70%)
1.Controlled by compressor suction pressure, via solenoid valve as step controlling.
2.Thermostat, placed at some accommodation space actuates the Master Solenoid Valve of theplant, which will stop the Compressor, when pre-set temperature is reached
3.Capacity unloader of compressor units, does last step controlling, as required
4.Local cabin temperature can be adjusted by volume control at delivery point of air duct controller.
What is ventilation ?
It is the circulation and refreshing of the air in the space without necessarily a change oftemperature.
What isair conditioning?
It is the control of temperature and humidity in a space together with the circulation, filtering andrefreshing of the air.
What is comfort zone ?
It is between the 40 to 70 % relative humidity at the temperature of 20 to 29 °Cdry bulb temperature andair motion is 100mm per sec.
What is defrosting ?
A method of removal of frost, built-up on evaporator coils. Defrosting should be done beforesnow thickness exceeds ¼”.
What are the reasons for defrosting ?
Affecting heat transfer properties
Affecting air flow and circulation
Liquid back to compressor
what are some defrosting methods
By stopping the system
By washing with warm water
By means of electric heater coil fitted at the evaporator
By hot gas defrosting method
How would u defrostbrine system?
Hot brine thawing
Best and fastest method, used powerful brine heater with separatethawing system. Watertight trays under the pipes, collect the dripping water.
Hot air from atmosphere
It is important that isolating doors in air trunks are perfectly tight, soas to prevent hot air going into cargo spaces.
By shutting off brine
Allow the snows to be melted by the heat of the air incirculation .Very slow operation and tends to throw back great deal of moisture into cargo space.
What is the purpose of ventilation for cargo hold ?
1.To remove surplus heat and humidity
2.To prevent the condensing of moisture on cargo or hull
3.To remove gases produced in ripening process of some fruits and vegetables cargos.
What is relative humidity ?
Ratio of amount of water vapour in given volume of air, to maximum amount of water vapourthat can be present before precipitation occurs.
It is the mass of water vapour per unit volume of air compared to the mass of water vapour perunit volume of saturated air at the same temperature.
What is saturated air ?
The air contains maximum weight of water vapour at the particular temperature.
What is super heating ?
Keeping refrigerant at a temperature above the saturated temperature.
what is the Cause of expansion valve chocking ?
When a valve is functioning correctly frost forms on the outlet side of the valve, and if the inletside does show frosting then this is a sign of blockage.
It is caused by dirt or freeze up by water present in the system.
Starving of evaporator and rapid consider pressure rise cause compressorshort cycling.
Remedy
Clean the expansion valve filter
Renew the drying agent of dehydrator or drier. (activated alumina or silica gel )
What are the indications of leaky suction and discharge valves in refrigeration system ?
Leaky Suction valve
1.Continuous running of compressor
2.Insufficient cooling effects
3.Noisy operation
4.High suction pressure
Leaky Discharge valve
1.Continuous running of compressor
2.Insufficient cooling effects
3.Noisy operation
4.High suction pressure during running
5.Low discharge pressure during running
6.Suction pressure increase faster after compressor is shut down
7.Warm cylinder head
What is High pressure (HP) cut out and low pressure (LP) cut out in refrigeration system on ships ?
HP cut out
Occurs due to condenser coolant failure, low coolant pressure and malfunction of considercooler valve operation.
Also can cause dirty or chocked condenser tubes.
The refrigerant can not liquefy rapidly .The discharge pressure will abnormally raise and highpressure cut out will take in action.
LP cut out
Operate the solenoid valve is closed when the cool room temperature reach its desired temperature(setting temperature)
Can cause when expansion valve is chocked by dirt or freeze up by water present in thesystem.
Starving of evaporator and rapid condenser pressure rise.
Compressor may stop by low pressure cut out.
pressure and temperature variations in a refrigeration circuit canprovide information about the operating condition of the refrigeration plant.In particular, suction and condenser pressures as well as the temperatures of suctionand discharge gases may provide important information as to the operating conditions ofthe plant. It often takes only very slight modifications of variable pressures and temperatures toproduce considerable changes in operating conditions
list 4 reason why a compressor is failing to start and how to remedy situation
Causes
1.Control current circuit open
2.High-pressure cut-out
3.Low-pressure cut-out
4.Oil-pressure cut-out
Remedy
1.Pinpoint open switch and remedycause of interruption.
2.Reset pressure cut-out andinvestigate cause of highcondenser pressure.
3.Compressor cannot start beforesuction pressure has risen aboveset point for pressure cut-outrestarting.
4.Compressor starts at reset.Check oil level.
Compressor starts and stops too often what are possible reasons and how to remedy situation
Causes
1.High-pressure cut-out cutsat high pressure
2.Low-pressure cut-out cuts attoo low suction pressure
3.Low-pressure cut-outdifferential is too smallbetween stopping andstarting
4.Compressor capacity toohigh
5.Filter in suction line clogged
6.Solenoid valve in liquid linedoes not close tight
7.Discharge valves oncompressor are leaky
Remedy
1.Check condenser cooling andadjust pressure cut-out to correctbreaking pressure.Replace defective pressure cut-out.
- If low-pressure cut-out is set toohigh, adjust pressure cut-out.
3.Increase differential pressure.
4.Check operating conditions and, ifnecessary, reduce capacity.
5.Check suction filters incompressor.
6.Check direction of flow.Replace any leaky valves.
7.At compressor stop,
pressureequalizes relatively quicklybetween suction and dischargeside.Clean or change discharge valves.
Compressor starts, but stops again immediately. what are possible reasons and how to remedy situation
Causes
1.Motor protection cuts
2.Low-pressure cut-out hascut
3.Defective oil-pressure cutout
4.Oil charge insufficient
5.Oil pressure failing owing toformation of foam in oil.
Remedy
1.Look for cause of overloading.If star-delta start, set starting timeat minimum.
2.Open any suction stop valve whichis closed.
3.Replace cut-out.
4.Top up with oil and investigatecause of oil shortage.
5.Reduce capacity.
Compressor operates continuously. what are possible reasons and how to remedy situation
Causes
1.Thermostat or low-pressurecut-out does not cut at toolow temperature/pressure
2.Restricted supply ofrefrigerant to evaporator.Compressor working at toolow suction pressure.
3.Refrigerant chargeinsufficient.
Remedy
1.Adjust operating points.
2.Remove dirt in filters and checkfunction of expansion device asper special instructions.
3.Top up with refrigerant of correcttype.
there is Abnormal noise from compressor what are possible reasons and how to remedy situation
Causes
1.Compressor capacity toohigh during start-up
2.Oil pressure too low
3.Liquid refrigerant in suctionline
4.Incorrect alignment of motorand compressor.Loose bolts in coupling
5.Worn or defective bearings
6.Too much oil circulatingthrough the plant, resultingin toolow oil level incompressor
7.Capacity regulationoscillating owing to failing oilpressure
Remedy
1.Reduce capacity.
2.See section below
3.Slugging.Adjust expansion or float valves.
4.Check alignment as per specialinstructions.Tighten with torque wrench.
5.Overhaul or replace
6.Check oil level.Solenoid valve, filter or jets in oilreturn system may be clogged.Leaky suction valve ring plates,piston rings and worn-out cylindermay also produce such oilconsumption.
7.Low oil pressure
there is Too little capacity for compressor what are possible reasons and how to remedy situation
Causes
1.Insufficient oil charge
2.Iced-up evaporator
3.Defective oil pump andhence failing oil pressure
4.Defective capacityregulating system
Remedy
1.Top up with fresh oil of same typeand make.
2.Defrost evaporator; adjustdefrosting time if required.
3.Repair or replace oil pump.
4.Cause is most often failure in oilpressure or refrigerant in oil.
explain what is meant by slugging in a compressor
Slugging occurs when liquid refrigerant — or liquid refrigerant and oil — enters the compressor’s cylinder during an on-cycle or run-cycle. can cause rupture of the valve ring plates and damage thebuilt-in relief devices. Furthermore, it can result in damage to theconnecting rod bearings and cylinders if the coolant degreasesthe faces and impairs the lubricating capacity of the oil.
Slugging in compressor during start-up
Causes
1.Sudden reduction inpressure across the oilsump (suction pressure)produces foaming
2.Refrigerant has condensedin suction line or crankcase.Suction line has free falltowards compressor
Remedy
1.Reduce compressor capacity orstart throttling suction stop valve.
2.Heating element in crankcaseshould be connected for 6-8 hoursbefore starting, so that refrigerantdissolved in oil can be separatedbefore starting compressor up.Start throttling suction stop valve –stop when hammering is heard.Liquid separator should bemounted in suction pipe.
Slugging in compressor during operation
Causes
1.Refrigerant gas in liquid line
2.Superheating of expansionvalve is set too low
Remedy
1.Expansion valve is oscillating.
2.Adjust superheating, which shouldnormally be 5-8°C
Too low condenser pressure, what are possible reasons and how to remedy situation
Causes
1.Excessive condenser cooling
2.Defective piston rings or worncylinders
3.Discharge valves are defectiveor leaky
4.By-pass between high pressureside and suction sideof compressor
5.Compressor lacks capacity
Remedy
1.Regulate condenser cooling
2.Replace worn parts.
3.Check valve ring plates andpiston rings
4.Check compressor for internalleakage by performingpressure-drop test.
5.Check whether compressorcapacity corresponds to load onplant. Reduce condensercooling.