Air & Water Testing Flashcards
(26 cards)
What is a general description of air and water testing?
Field testing of installed exterior windows, skylights, doors, and curtain walls.
What standards cover field air and water testing?
ASTM E1105 (2015): standard method for field determination of water penetration of installed exterior windows, skylights, doors, and curtain walls, by uniform or cyclic static air pressure difference
ASTM E783 (2010): Standard test method for field measurement of air leakage through installed exterior windows and doors
AAMA 501.2 (2015): Quality assurance and diagnostic water leakage field check of installed storefronts, curtain walls and sloped glazing systems
ASTM E1186 (2009): Standard practices for air leakage site detection in building envelope and air barrier systems
What standards cover laboratory air and water testing?
ASTM E331 (2009): Standard test method for water penetration of exterior windows, skylights, doors, and curtain walls by uniform static air pressure difference.
ASTM E283 (2010): Standard test method for determining rate of air leakage through exterior windows, curtain walls, and doors under specified pressure differences across the specimen
How do you determine which test to apply?
- Field testing parameters can be specified in the project construction documents or derived from specification for lab test requirements.
- test parameters can also be found through the manufacturer as product data or through sample specifications.
Which tests are water tests?
- AMAA 501.2 (nozzle)
- ASTM E1105 (spray rack)
What is the purpose of the AAMA 501.2 test?
To “provide quality assurance and diagnostic field water check method for installed storefronts, curtain walls, and sloped glazing systems”
What does the AMAA 501.2 test procedure encompass?
- Test area is divided into ~5-feet sections of the framing and perimeter sealant joint using a water pressure range between 30 and 35 psi.
- Hold the nozzle perpendicular to the plane of the wall at a distance of 1 foot from the test specimen
- Evaluate each 5-foot section of test area for a period of 5 minutes (1 min per foot) by slowly moving the nozzle back and forth over the test section while maintaining the nozzle perpendicular to the wall. - Working from the exterior, test each wall section by wetting each area progressing from the lowest horizontal framing member, then the adjacent framing intersectinos, then the adjacent vertical framing members, etc.
- Another member will observe the interior side of the test area using a flashlight during the test to identify any water leakage and will note where it comes from.
- Utilize hydrion water detection paper in areas that cannot be visually inspected as a secondary means to verify the presence of moisture.
What are pass/fail criteria for AMAA 501.2?
A passing test occurs if water leakage is not observed at the specimen. Water leakage is defined in AMAA 501.2 as “any uncontrolled water that appears on any normally exposed interior finishes, that is not contained or drained back to the exterior, or that can cause damage to adjacent materials or finishes. Water contained within the drained flashings, gutter, and sills is not considered water leakage.” Test failure occurs if water leakage is observed.
What should be included in the AMAA 501.2 test report?
- Project and Client name
- Test Date
- Window/specimen Information
- Water Pressure photos
- Diagnostics
- Recommendations
What does ASTM E1105 test for?
ASTM E1105 test standard is “intended primarily for determining the resistance to water penetration through such assemblies for compliance with specified performance criteria, but it may also be used to determine the resistance to penetration through joints between the assemblies and the adjacent construction.”
What testing components makeup the ASTM E1105 test?
- spray rack with water pressure measurement and setup 20 inches from specimen face
- negative pressure chamber installed on test specimen interior
- air exhaust controls
- air pressure measurement
- water supply
What are the two types of test procedures for ASTM E1105?
- Uniform Static Pressure
- Cyclic Pressure
What is the procedure for ASTM E1105 uniform static pressure?
Uniform static pressure consists of inducing a uniform static pressure difference across the specimen for 15 min. straight while introducing water at the specimen exterior by means of calibrated spray rack
- test pressure is derived from the project specifications, manufactures’ published literature, and/or agreed to by the project team prior to testing. NOTE: the field differential pressure is 2/3 of the specified lab pressure
- virtually inspect the specimen from the interior during the 15 min. test for signs of water intrusion
- removed the chamber from the test area and visually inspect the area for signs of water intrusion.
- use the hydrion water detection paper in areas that cannot be visually inspected as a secondary means to verify the presence of moisture.
Approximately how many pounds is a gallon of water?
8.34 lbs
What is the procedure for ASTM E1105 cyclic pressure?
Consist of inducing a cyclic pressure difference across the specimen for 5 min. increments while introducing water at the specimen exterior by means of calibrated spray rack.
- introduce water at the pre-calibrated rate
- induce negative pressure: test pressure is derived from the project specifications, manufactures’ published literature, and/or agreed to by the project team prior to testing
- while maintaining the water spray, reduce the air pressure difference to zero for a period of not less than 1 min.
- repeat the preceding two steps to accomplish 3 cycles for a total test duration of 17 min.
- visually inspect the specimen from the interior during the test for signs of water intrusion
- remove the chamber from the test area and visually inspect the area for signs of water intrusion
- utilize hydrion water detection paper in areas that cannot be visually inspected as a secondary means to verify the presence of moisture
What are ASTM E1105 pass/fail criteria?
Water penetration is defined in ASTM E1105 as penetration of water beyond a plane parallel to the glazing (the vertical plane) intersection the innermost projection of the test specimen, not including interior trim and hardware, under the specified conditions of air pressure difference across the specimen.”
What should ASTM E1105 test documentation consist of?
- Test location
- window information
- assembly materials
- test parameters
- photographs
- leak locations
- test notes
- witnesses
What should the ASTM E1105 test report consist of?
- Project and client name
- test date
- window information
- equipment photos
- pressure photos
- diagnostics
- recommendations
What test standards cover air testing?
ASTM E783
ASTM E1186
What is ASTM E783?
The ASTM E783 test standard is “intended to measure only such leakage associated with the assembly and not the leakage through the openings between the assemblies and adjacent construction. The test method can be adapted for the latter purpose provided the potential paths of air movement and the sources of infiltration and exfiltration can be identified, controlled, or eliminated”
What is the ASTM E783 Test Procedure?
ASTM E783 consists of inducing a uniform static pressure difference across the specimen and measuring the air flow required to maintain this pressure. Masking is then applied to the exterior of the specimen and the same uniform static pressure difference is induced across the specimen. The air flow rate is measured again and the difference between the two air flow rates is the air leakage through the test specimen.
What are the procedural steps for ASTM E783?
1) induce a negative pressure of XX pounds per square foot (psf). The test pressure is derived from the project specifications, manufactures’ published literature, and/or agreed to by the project team prior to testing.
2) Measure the air flow required to induce the negative test pressure across the specimen. Take fifteen pressure and airflow measurements at 30 second intervals. This measurement is designated Q(e)
3) Remove the masking from the exterior of the test specimen
4) Repeat measurement of the air flow required to induce the negative test pressure across the specimen. Take fifteen pressure and airflow measurements at 30 second intervals. This measurement is designated Q(t).
5) Identify all calculated airflow values cited above in the report after testing is complete.
What are the pass/fail criteria for E783?
A passing test occurs when the measured airflow is less than the allowable airflow value of XX cfm/ft^2 at a differential pressure of XX psf. The allowable airflow and differential pressure values are provided in the project specifications/identified in the product technical data/derived from AAMA/WDMA, CSA 101/I.S.2/A440-11 NAFS and AAMA 502/503. Test failure occurs if the measured airflow exceeds the allowable value.
What information is needed for the ASTM E783 report?
- Test location
- Window information
- Test Parameters
- Flow Photographers
- Test Notes
- Witnesses