Windows 1

A

Turbine Bearing High Temp

2 RTD - 70C
TBB11 - 85
C
Foxboro - 55C
Foxboro - 55
C - Oil return

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

Window 2

A

Turbine Bearing Oil Level Alarm

Foxboro - 1/8 Low 7/8 High

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

Window 3

A

DC Oil Pump Run

Motor Starter Contact 6QDC1

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

Windows 4

A

Turbine Bearing Low Oil Flow or Pressue

Teleflow Indicator @ 0 Flow
63Q1 - Mercoid - 5 PSI

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

Window 5

A

Gen. Upper Guide Brg. High Temp

2 RTD - 70C
TBB11 - 105
C
Mercoid- 75C
Foxboro - 70
C

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

Window 6

A

Gen. Upper Guide Brg. Oil Level

Magnetrol - High/Low

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

Window 7

A

Gen. Lower Guide Brg. High Temp.

2 RTD - 70C
TBB11 - 105
C
Mercoid- 75C
Foxboro - 70
C

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

Window 8

A

Gen. Bearing High Temp

4 RTD - 70C
TBB11 - 105
C
Mercoid- 75C
Foxboro - 70
C

2 RTD - 70C Oil
Foxboro - 55
C Oil

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

Window 9

A

Gen. Thrust Brg. Oil Level Alarm

Magnetrol - High/Low

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

Window 10

A

Generator Brakes Applied

Pressure Switch off 20A1B @ 80 PSI

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

Window 11

A

Overspeed

Overspeed switch 12G1 @ 97.5 RPM, Resets 78.75 RPM

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

Window 12

A

Governor Oil Low Pressure

63Q1L - Pressure Switch @ 255 PSI

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

Window 13

A

Gov. Oil Pump Excessive Run Time

62QT Timer @ 3 mins

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

Window 14

A

95U Trouble

R6 output of the 95U, Self Check

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

Window 15

A

Head Cover Sump High Water

63S1B Mercoid/Float - High Level
DC Pump Run

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

Window 16

A

Kaplan Head Oil Level Alarm

Magnetrol/Float - High Level

17
Q

Window 17

A

Kaplan Head High Temp.

3 - RTD - 70C
3- TBB11 - 105
C
1 for each bushing

18
Q

Window 18

A

Generator Air Coolers High Temp.

Foxboro - 45*C x 8

19
Q

Window 19

A

Generator Air Coolers Low Water Flow

Toshiba Electromagnetic Flow Meter - 200 GPM or 25%

20
Q

Window 20

A

Thrust Bearing Coolers Low Water Flow

Toshiba Electromagnetic Flow Meter - 30 GPM or 21.4%

21
Q

Window 21

A

Stuffing Box Low Water Flow

Toshiba Electromagnetic Flow Meter - 4.3 or 43%

22
Q

Window 22

A

Generator Stator High Temp

6 RTD - 100*C

23
Q

Window 23

A

Gen. Field High Temp

Not Used

24
Q

Window 24

A

Generator Diff. Relay Operation

87G1X (MG6) @ Operation of 95U R3

25
Window 25
Generator Ground Relay Operation 87G1X (MG6) @ Operation of 95U R3
26
Window 26
95U Alarm R5 Output - 95U Operation
27
Window 27
Generator Overvoltage Relay Operation 59G1X (MG6) @ Operation of 59G1 (SV) @ 15.2 KV, reset at 14.8 KV
28
Window 28
440V Unit Bus No-Volt Undervoltage Relay @ 0V
29
Window 29
Partial Shutdown Relay Operation 5P (WL) @ Operation of 51G1X or 87T1X
30
Window 30
Complete Shutdown Relay Operation 5C (WL) @ Operation of 5A1, 1G11, 1G12, 64G1, 87G1X2, 63Q1CX, CO2 Pressure Switch 1PS2
31
Window 31
Generator C02 Release 87G1X initiated by R3 on 95U
32
Window 32
Unit Available For Operation Fisherman Warning System Timeout After Condensing