Chapter 1 Article 100 A Flashcards
(94 cards)
The authority having jurisdiction has the responsibility of
1- Making interpretations of rules
2- for deciding upon the approval of equipment and materials
3- waiving specific requirements in the code, permitting alternate methods if safety is maintained
90.3 C. 90.4
The words “Shall” and “Shall Not”, in the NEC means?
A mandatory requirement.
90.5 A
The word
“Shall be Permitted” means
the identification of actions that are allowed but it is nat required in NEC.
90.5 B
The code specify that one equipment shall be “in sight from”, within sight from” or “within sight of” and so forth, another equipment, the specified equipment is to be visible and not more than ___________
50 Ft distant from the other
Article 100 Definition
On a 4-wire, delta-connected system where the mid point of one phase winding’s grounded, only the conductor or busbar having the higher voltage to ground shall be durably and permanently marked by an outer finish that is ___________ in color or by other effective means.
Such identification Shall be placed at each point on the system where a connection is made if the grounded conductor is also present.
Orange Color
The required working space for access to live parts operating at 300volts to ground, where there are exposed live parts on one side and grounded parts on the other side is
3 1/2 ft =42 inches
110.26 table condition # 2
The dimensions of working space for access to live parts operating 300 volts nominal to ground, where there are exposed live parts on both sides of the workspace is
4 ft
110.26 conduction #3
The working space for 150 volts or less, in any the condition named in table 110.26 will be
3 ft all condition
Table 110.26
Article 300
Wiring Methods
Wiring Methods
Cover all wiring Installations, Raceways,Wiring, Voltages up to 600 nominal volts
Armored Cable, Type AC. A fabricated assembly of insulated conductors in a flexible metallic enclosure. See 320.100 for construction
The Trade Name is _________
BX. trade name
which cable have an armor
of flexible metal tape and shall have an INTERNAL BONDING
STRIP of COPPER OR ALUMINUM in intimate contact with the
armor for its entire length.
AC cable is construction
The AC cable is use permitted
(1) For feeders and branch circuits in both exposed and
concealed work
(2) In cable trays
(3) In dry locations
(4) Embedded in plaster finish on brick or other masonry,
except in DAMP OR WET LOCATIONS
(5) To be run or fished in the air voids of masonry block or
tile walls where such walls are not exposed or subject
to excessive moisture or dampness
Uses NOT Permitted for Type AC Cable
320.12 Uses Not Permitted. Type AC cable shall not be
used as follows:
(1) Where subject to physical damage
(2) In damp or wet locations
(3) In air voids of masonry block or tile walls where such
walls are exposed or subject to excessive moisture or
dampness
(4) Where exposed to corrosive fumes or vapors
(5) Embedded in plaster finish on brick or other masonry
in damp or wet locations
Bending Radius. Bends in Type AC cable shall be
five times the diameter of the Type AC cable.
Supporting the AC Cable shall not be more than ____
(41⁄2 ft).
320.30 Supporting.
AC Cable shall be supported with
320.30 Securing and Supporting.
(A) General. Type AC cable shall be supported and secured by staples, cable ties, straps, hangers, or similar fittings, designed and installed so as not to damage the cable.
320.30 Securing
AC cable shall be secure with ….
Type AC cable
shall be secured within 12 in. of every outlet box, junction box, cabinet, or fitting and at intervals not
exceeding 41⁄2 ft. where installed on or across framing members.
Where we can install or what is the designed for the
Flat Conductor Cable: ( Type FCC Cable)
Type FCC ( flat conductor cable )
is designed to use it under carpet
squares
FCC Cable used permitted
Branch Circuits
Only in Commercial applications
(A) Branch Circuits, for general-purpose and appliance branch circuits
and for individual branch circuits.
FCC Cable Branch Circuits Ratings
(2) Current. General-purpose and appliance branch circuits shall have ratings not exceeding 20 amperes.
INDIVIDUALS branch circuits shall have ratings not exceeding 30. amperes.
324.12 Uses Not Permitted. FCC systems shall not be
used in the following locations:
(4) In residential, school, and hospital buildings
1) Outdoors or in wet locations
(2) Where subject to corrosive vapors
(3) In any hazardous (classified) location
(4) In residential, school, and hospital buildings
Type AC Cable
Armored Cable
Type FCC
Flat Conductor Cable