1
Q

A 240 volt boat hoist receptacle has to be?

A

GFCI protected

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

Non-dwelling unit receptacles installed in/on the_____ shall be gfci protected.

A

Roof tops, outdoors, and sinks

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

What is the minimum rating for a laundry circuit in a single family dwelling?

A

20 amps and 1,500 watts

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

A receptacle on a individual branch circuit can be rated for what percent?

A

100%

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

What size branch circuit shall apply only non-lighting loads?

A

50 amps

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

What type of [lamp holder] shall be connected to a load in excess of [20 amps?]

A

Heavy duty

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

The laundry outlet shall be installed within how many feet of the designated location?

A

6 feet

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

Receptacle outlet in the floor shall not be counted as part of the required number of wall receptacles unless located within how many inches of the wall?

A

18 inches

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

What is the minimum number of small appliances for a single family dwelling?

A

2 circuits

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

Other than counter top appliances, what type of device is allowed to utilize the small appliance circuit in a single family dwelling?

A

Refrigerator, clocks, and cooking equipment

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

Receptacles shall be installed so that no point along the wall line of a kitchen countertop is no more than ____ inches measured horizontally from a receptacle in that space?

A

24 inches

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

What is the minimum length of countertop in a kitchen that required the installation of a receptacle?

A

12 inches

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

Island counter tops, with a minimum dimension of 12”W x 24”D, must have at least ____ receptacle outlet.

A

1

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

18 feet of show window requires how many receptacles above window?

A

2

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

What is the maximum distance from a roof unit that the rooftop gfci service receptacle shall be located?

A

25 feet

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

A conference room is 250 sq ft and has a 12.5 ft wall. How many floor receptacles are needed?

A

1

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
17
Q

Does a vehicle garage door require illumination under the illuminated entryway rule?

18
Q

General branch circuit lighting load for a hospital shall be calculated at ___ watts per sq feet?

19
Q

In dwelling units, new additions to the lighting branch circuit shall be calculated in accordance with 220.12 when over ____ square feet.

20
Q

Where SE cable enters the building, the conduit has to be?

21
Q

The conductors for festoon lighting shall be supported by messenger wire in all spans exceeding?

22
Q

What is the minimum service rating for a single family dwelling with 6 or more 2 wire branch circuits?

23
Q

Circuit breakers used as switches in 120V flourecent lighting shall be marked as?

24
Q

What is the minimum height of a SE conductor rated 600 volts going above a pedestrian sidewalk?

25
The minimum number of disconnects at the main service?
6
26
What is the minimum service disconnect of a commercial building?
60 amps
27
Serve as overcurrent protection, I’ll just connecting me and Shelby supplied on the line side of all fused circuits that exceed 150 V if the fuses are accessible to who?
Other than qualified personnel
28
Edison based fuses shall not operate at over then?
30 amps
29
A type S fuse installed in an edison base fuse holder for what primary reason?
Non-interchangeable
30
Conductor may be spliced together by____?
Exothermic welding
31
What size grounded conductor you can run in parallel?
1/0
32
Main panel enclosure serves as what?
Main bonding jumper
33
High impedance ground systems operate at a minimum of what voltage?
480 volts
34
A concrete encased electrode with electrically, conductive coated, steel, reinforcing bar shall be at least ______in diameter, and a minimum of 20 feet and continuous length?
1/2”
35
Minimum size wire for ground ring?
#2 copper
36
How many feet of a rod electrode, be in contact with the Earth?
8 feet
37
A ground rod shall be at least how many inches in diameter?
5/8”
38
Minimum space between ground rods?
6 feet
39
What size grounding electrode conductor must always be protected from physical damage?
#6 or bigger
40
When a metal enclosure is required to protect the grounding electrode conductor, the enclosure has to be bonded to what at both ends?
Grounding electrode conductor
41
What is the minimum Size main bonding jumper for 800 kcmil service entrance conductor?
2/0
42
What is the minimum Size copper clad grounding, electrode, conductor, needed for 200 amp single phase dwelling, copper feeder?
2 awg 200 x 83% 166 amps