Chapter 9 Fire Protection and Life Safety Systems Flashcards
(47 cards)
An Automatic sprinkler is required in Group A-1 if…
- fire area exceed 12,000 square feet
- fire area occupant load 300 or more
3.The fire area is located on a floor other than level of exit - fire area contains multi theater complex.
An Automatic sprinkler is required in A-2 if…
- fire area exceed 5,000 square feet
- fire area occupant load 100 or more
3.The fire area is located on a floor other than level of exit
An Automatic sprinkler is required in A-3
- fire area exceed 12,000 square feet
- fire area occupant load 300 or more
3.The fire area is located on a floor other than level of exit
An Automatic sprinkler is required in A-4 if..
- fire area exceed 12,000 square feet
- fire area occupant load 300 or more
3.The fire area is located on a floor other than level of exit
An Automatic sprinkler is required in A-5 if…
Accessory use is over 1000 square feet
Where a roof has an occupied assembly all floors between floor and level of exit needs…
an automatic sprinkler system
An Automatic sprinkler is required in Group E if…
- fire area exceed 12,000 square feet in entire Group E
2.The fire area is located on a floor other than level of exit
An Automatic sprinkler is required in F-1…
- fire area exceed 12,000 square feet
- all fire areas in total shall not exceed 24,000 square feet
3.The fire area is located on a floor other than level of exit
Woodworking operations ins F-1 exceeding 2,500 square feet shall be equipped with
Automatic sprinkler system
Is An Automatic sprinkler is required in all Group I
Yes
An Automatic sprinkler is required in M if…
- fire area exceed 12,000 square feet
- all fire areas in total shall not exceed 24,000 square feet
3.The fire area is located more than 3 floors of level of exit
High Piled storage in group M needs an..
automatic sprinkler system
Is An Automatic sprinkler is required in all Group R
Yes
Is An Automatic sprinkler is required in all Group R
Yes
An Automatic sprinkler is required in S-1 if…
- fire area exceed 12,000 square feet
- all fire areas in total shall not exceed 24,000 square feet
3.The fire area is located more than 3 floors of level of exit - storage of commercial vehicles exceed 5000 square feet
Bulk storage of tires exceeding
20,000 square feet need automatic sprinkler system
An Automatic sprinkler is required in S-2 Parking garages if.
- fire area of enclosed parking garage exceeds 12,000 square feet.
2.Parking garage underneath other occupancies.
Stories without openings shall need an automatic sprinkler system if exceeds…
1,500 square feet..
Exterior openings shall be no less than..
30 inches
One side only openings with opposite wall more than 75 feet away needs..
automatic sprinkler system
Any portion of basement further than..
75feet need automatic sprinkler system
Any building with one or more floors with 30 occ. load or 55 feet in height need.
automatic sprinkler system
Automatic sprinkler can be installed in or under equipment than exceeds
4 feet
how many feet between automatic sprinklers and the top of piles of combustible fibers
3 foot clearance