Chows Unit 8 Flashcards
(60 cards)
True or false After repairing a system that has had an electrical motor failure (compressor burnout), it is good field practice to re-use the recovered refrigerant in that system.
False
Air entering a refrigerant system can eventually lead to compressor failure
True
The maximum recommended pressure for leak testing is 150 psig on the low-pressure side of the system.
True
While under a deep vacuum, any liquid water under the oil in the motor compressor assembly can be removed by operating the compressor motor for several seconds without any adverse effects on the system
False
True or false clearance tolerances are such that the ordinary, clean refrigerant oil can be used satisfactorily in a vacuum pump
False
True or false The oil in a vacuum pump should be changed after each time it is used
True
When using a standing pressure test for leak checking, _______ should never be used since an explosive mixture can be created
Oxygen
Only two substances should be in the refrigeration system for proper operation. They are _________ and oil.
Refrigerant
____________ microns is equal to 1 mm Hg.
1000
The electronic vacuum gauge is attached to the system so it can measure the pressure ________ the system
Inside
A vacuum involves reducing the pressure in a refrigeration system to a micron gauge reading of _______ or below
300
There are _________ microns in 1 mm Hg.
1000
Sludge is produced when moisture acid and _________ are present in the system
Oil
A __________ pressure could also mean refrigerant vapor is still seeping from the refrigeration system.
Rise in
Explain why, triple evacuations are not normally performed on large systems.
It takes too much time and it would take a lot of nitrogen to pressurize a large system correctly.
A pressure of 100 µm has been reached with the vacuum pump operating. The pump is turned off and the gauge reading rises to 5000 microns and stays there. What does this indicate?
This indicates that there is still moisture within the system that still needs to boil off
A pressure of 100 µm has been reached with the vacuum pump operating. The pump is turned off and the gauge reading rises to 500 µm and stays there. What does this indicate?
500 µm would indicate that the system has little to no moisture and that no leaks are present. This is an acceptable number of microns as long as it holds for 10 minutes.
Why is refrigerant not used for a system standing pressure test?
Because the pressure/temperature relationship with refrigerant vary, the pressure readings will not be accurate. If the leak is big, the refrigerant will be released into the atmosphere against EPA rules. Using nitrogen is cheaper and OK to be released into the atmosphere.
Why is nitrogen considered a noncondensible gas?
Unlike refrigerant, nitrogen cannot change states
A pressure of 100 µm has been reached with the vacuum pump operating. The pump is turned off in the gauge reading rides is above 5000 µm and keeps rising. What does this indicate?
More than likely, there is still a leak within the system, and at this point, the system is sucking in atmospheric pressure
Why must all valves be opened when an evacuation is performed?
All valves should be opened to ensure that the entire system is being dehydrated/degassed
Why is it a good idea to remove schrader stems from service valve ports prior to evacuation?
Schrader stems restrict flow by 90%. This makes pulling a deep vacuum, more time-consuming then it has to be.
A micron gauge is used to measure…….
Absolute pressure below 1 mm Hg.
To insure accurate testing, the best materials to use for connecting lines to the vacuum pump and gauge set is…….
Copper tubing