codes Flashcards

1
Q

UL 1741

A

product safety requirements for inverters and other equipment used in both interconnected and stand alone systems

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

table 310

A

open air/race way, conduit codes

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

706.21(E)

A

a disconnect means is required to isolate the fuse from all sources for servicing

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

table 690.7

A

determining the max number of modules depending on max source Voltage

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

706

A

energy storage systems

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

NEC 250.52(A)(3)(1)

A

dealing with rebar and concrete encasements ?

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

90.4

A

The AHJ has
the responsibility for making interpretations of the rules, for deciding on the approval of
equipment and materials, and for granting the special permissions covered by the NEC

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

705.12 (B)

A

load side connections must comply with the following six requirements

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

706.30 (A)

A

Concealed lithium-ion battery compartments that do not require maintenance can operate at voltages
above 100V in dwellings

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

Article 300

A

Wiring Methods

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

250.97

A

For circuits over 250 volts where oversized concentric or eccentric knockouts are encounter the raceway needs to be bonded by one of the means listed in 250.92(B) except for (B)(1)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

706

A

energy storage systems (ESS), listed to UL 9540 is NOT subject to field inspection except for field termination

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

706.23 (B)

A

Interactive systems must also have a second
independent charge controller to prevent battery overcharge when the grid or loads are not
available to divert excess power

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

NEC 334.30

A

USE-2 wire be secured 12” from the junction box

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

Article 230

A

services

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

110.27

A

all live parts shall be guarded

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
17
Q

Article 240

A

overcurrent devices

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
18
Q

710

A

stand-alone systems

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
19
Q

NEC 310.15(B)(16)

A

At 75⁰C THW, XHHW, THWN should be used

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
20
Q

NEC 338.10(B)(4). Article 334.30

A

Installation methods for exterior USE-2 conductors; USE-2 wire must be strapped and secured between modules at
intervals no more than 4.5”

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
21
Q

110.26

A

Working spaces must be allowed for installers and maintenance personnel to safely work on electrical equipment

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
22
Q

Article 691

A

Large-Scale PV Power

Production Facility

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
23
Q

90.1 (purpose)

A

“is the practical safeguarding of persons and property from hazards
arising from the use of electricity and is not intended as a design specification
or an instruction manual for untrained persons”

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
24
Q

250.110

A

Any conductive battery racks, cases or trays must also have proper equipment grounding

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
25
Article 712
DC Microgrids
26
110.3 (B)
A key element of a safe and code-compliant electrical installation is adherence to product installation and use instructions included with listed and labeled products
27
NEC Table 310.15(B)(16)
75 or 90 degree column is good for #8 wire good for 50 Amp breaker
28
690.41 (B)
most PV systems, residential, and commercial must have ground fault
29
[NEC 706.23(B)]
Whenever a diversionary charge controller is used, a second independent charge controller is required to prevent battery overcharge in the event the diversion loads are unavailable or the diversion charge controller fails
30
250.12
aluminum either has an anodized coating to reduce corrosion or a thick layer of oxidation as in the case of non-anodized aluminum. In either case, simple bolting of modules to structures, or lugs to modules or structures, will not necessarily provide the necessary bonding and grounding. The NEC generally requires that the installer remove non-conductive coatings prior to making electrical connections
31
706.23
A charge controller is required in most PV systems that use battery storage, to prevent damage to the batteries or hazardous conditions resulting from overcharging
32
IEEE 1547
establishes the technical requirements for interconnecting all types of distributed generation equipment, including PV, fuel cells, wind generators, reciprocating engines, microturbines, and larger combustion turbines with the electrical power system. It also establishes requirements for testing, performance, maintenance and safety of the interconnection, as well as response to abnormal events, anti-islanding protection and power quality
33
690.34
Junction boxes do not have to be readily accessible, but must permit ready access by temporarily removing modules connected by flexible wiring methods
34
Article 690.45(A) refers to Table 250.122
Where no overcurrent protection is provided for the PV dc circuit, an assumed overcurrent device rated at the PV circuit Isc is used to size the equipment grounding conductor
35
Article 705
Interconnected Electric | Power Production Sources
36
IEEE 1547
testing procedures required to ensure that grid-direct inverters conform with safety requirements related to voltage, frequency, synchronization, disturbances, faults, and reconnect time. "islanding"
37
690.8 (A) (3)
conductor should be sized according to the max continuous current output of the inverter
38
Article 250.52 (A) (4)
1/0 ground wire = ground ring
39
Article 690.14 (C)(1)
Requirements and location for Disconnecting Means
40
90.7, 110.3
Equipment is generally | approved when it is listed, labeled, or evaluated for safety by an approved testing laboratory
41
[NEC 690.4(B), 705.6].
Certain PV products are also identified for specific applications and conditions of use, such as inverters intended for utility interconnection
42
710.15 (C)
special warning sign is required on | the panel to prohibit the connection of multiwire branch circuits
43
690.72
self regulating PV charge controller
44
480.10(C), 110.26
Sufficient working spaces and clearances must be | provided for any battery installations
45
690.2
installer should be able to clearly identify the different circuits ( DC or AC )
46
UL 2579
fuses for photovoltaic systems
47
690.42
The dc system grounding connection must be made at a single point on the PV output circuit
48
690.72
Active means of charge control is required by the NEC unless the maximum array charge current for 1 hour is less than 3% of the rated battery capacity measured in amp/hours.
49
Article 706
Energy Storage Systems
50
NEC 240.4(D) (7)
copper #10 wire limited to 30 Amp overcurrent device
51
480.9, 480.10
To prevent battery installations from being classified as hazardous locations, ventilation of explosive battery gasses is required. However, the NEC does not provide specific ventilation requirements. Vented battery cells must incorporate a flame arrestor to help prevent cell explosions from external ignition sources, and cells for sealed batteries must have pressure relief vents
52
690.49
Where the removal of the utility-interactive inverter or other equipment disconnects the bonding connection between the grounding electrode conductor and the photovoltaic source and/or the photovoltaic output circuit grounded conductor, a BONDING JUMPER shall be installed to maintain the system grounding while the inverter or other equipment is removed.
53
710.15 (A)
the inverter should be large enough to power the total connected load, but is only required to be as large as the single largest load
54
110.26
requirements for working spaces | around live electrical equipment
55
Article 710
Stand-Alone Systems
56
Article 480
Storage Batteries
57
Article 250.53 (F)
30" of burial depth for ground ring
58
UL 1741
standard for inverters, converters, charge controllers and combiner boxes
59
PV racking systems are UL standard 2703, meaning?
module clamps, when mechanically attached, have a means to bond the frames of the mods to the rails for equipment grounding purpose
60
Article 690.14 (D) (1-4)
) Utility-interactive inverters mounted in not-readily – | accessible-locations.
61
705
AC microgrids
62
NEC 690.17
The DC and AC disconnects should be on either side of the inverter AKA 'readily accessible requirement'
63
Article 310
Conductors for | General Wiring
64
250, 690.43
The installation of an equipment grounding conductor (EGC) is required for all metal framed PV module systems and any PV array that has exposed conductors in contact with metal support structures, regardless of system voltage ; The EGC can be a conductor, busbar, metallic raceway, or structural component.
65
UL 2703
standard for racking systems
66
Article 250
Grounding and Bonding
67
300.9
conductors in conduit installed outdoors/ rooftops must be water tight; labeled W
68
Article 240
Overcurrent Protection
69
UL 4703
standard for PV wire
70
690.4 (C), 705.6
any PV system equipment, including any electrical power production sources operating in parallel with a primary source of electricity be installed only by qualified persons
71
690.53
The maximum rated output current of the charge controller must be posted on a sign at the dc disconnect
72
690.72
max charge rates from PV array multiplied by 1 hour = 3% of battery nominal Ah capacity or greater a charge controller is required
73
712
DC microgrids
74
300.5
conductors in conduit installed underground must be water tight; labeled W
75
NEC 338.10(B) (4).
USE-2 wires should be lifted off of roof ad strapped at 3' (wire management)
76
OSHA requirements for battery installations
-Unsealed batteries must be installed in ventilated enclosures to prevent fumes, gases, or electrolyte spray entering other areas, and to prevent the accumulation of an explosive mixture. • Battery racks, trays and floors must be of sufficient strength and resistant to electrolyte. • Face shields, aprons, and rubber gloves must be provided for workers handling acids or batteries, and facilities for quick drenching of the eyes and body must be provided within 25 feet of battery handling areas. • Facilities must be provided for flushing and neutralizing spilled electrolyte and for fire protection. • Battery charging installations are to be located in designated areas and protected from damage by trucks. • Vent caps must be in place during battery charging and maintained in a functioning condition.
77
480.8
Metal racks must be painted or otherwise treated to resist degradation from electrolyte and provide insulation between conducting members and the battery cells
78
690.45
EGC (equip. grounding conductor) size for DC side
79
706.30 (B)
If batteries are connected in series to produce more than 240 V (nominal), then the batteries must be connected in a manner that allows the series strings of batteries to be separated into strings of 240 V or less for maintenance by qualified persons
80
690.8
code-approved method to determine conductor/wiring
81
480.10
proper ventilation for vented and sealed battery systems
82
690.7
``` The charge controller rated continuous current (sometimes specified as input current, sometimes as output current) must be at least 125% of the PV array short-circuit output current, and the charge controller maximum input voltage must be higher than the maximum system voltage ```
83
Article 110
Requirements for | Electrical Installations
84
UL 1703
standard for PV mods
85
Article 705.10
Permanent plaque or directory
86
706.30 (A) exception
First, if routine maintenance is required, which would not be the case for lithium-ion or valve-regulated lead-acid (VRLA) batteries, then the terminals must be guarded to prevent contact during that maintenance. Second, a ground-fault detector-indicator is also required for any ESS operating over 100 volts.
87
690.31
Spacing between cable management devices for PV wire
88
Commissioning protocol standards
NFPA 70 (National Fire Protection Association) National Electrical Code and in particular those Articles relevant to the solar industry: 690, 691, 705, 706, 710, and, in some projects, 712. • NFPA 70E Standard for Electrical Safety in the Workplace. • IEC 62446-1 Grid connected photovoltaic systems – Minimum requirements for system documentation, commissioning tests and inspection. This standard provides a framework for system commissioning that is widely accepted in the solar industry.
89
IEC 62446-1
Grid connected photovoltaic systems – Minimum requirements for system documentation, commissioning tests and inspection
90
ANSI/ NETA ATS 2017
Standard for Acceptance Testing Specifications for Electrical Power Equipment and Systems
91
110.26
requirements for working spaces around live electrical equipment
92
Table 250.122
Where no overcurrent protection is provided for the PV dc circuit, an assumed overcurrent device rated at the PV circuit Isc is used to size the equipment grounding conductor
93
690.31 (G)
metallic conduit, raceways, and enclosures for PV source and output circuits (DC) that run inside a building/structure
94
ANSI Z87.1
standard for safety glasses
95
250.119 and 200.6 (A)
color coding requirements