Containment Building Flashcards
LCO 3.3.3 “ESF Instrumentation” requirement
4 ESF bistables and associated instrument channels for CHP (3.7-4.3 psig) and CHR (<= 20 R/hr) shall be operable.
LCO 3.3.3 “ESF Instrumentation” applicability for CHP/CHR
Modes 1-4
LCO 3.3.4 “ESF Logic and Manual Initiation” requirement
2 ESF manual and 2 ESF actuation logic channels and associated bypass removal channels shall be operable for CHP and CHR.
LCO 3.3.4 “ESF Logic and Manual Initiation” applicability for CHP/CHR
Modes 1-4
LCO 3.3.6 “Refueling CHR Instrumentation” requirement
2 refueling CHR auto actuation function channels and 2 CHR manual actuation function channels shall be operable.
LCO 3.3.6 “Refueling CHR Instrumentation” applicability
During core alterations and during movement of irradiated fuel assemblies within containment
LCO 3.3.6 “Refueling CHR Instrumentation” required actions if 1 or more functions with 2 channels inoperable
IMMEDIATELY suspend core alterations and movement of irradiated fuel assemblies within containment
LCO 3.3.7 “PAM Instrumentation” requirement
The PAM Instrumentation for Containment Pressure (Wide Range, 2 channels req’d), Containment Isolation Valve Position (1 per valve), and Containment Area Radiation Monitor (High Range) shall be operable
LCO 3.3.7 “PAM Instrumentation” applicability
Modes 1-3
LCO 3.6.1 “Containment” requirement
Containment shall be operable
LCO 3.6.1 “Containment” applicability
Modes 1-4
LCO 3.6.1 “Containment” required actions if containment is inoperable
WITHIN 1 HOUR, restore containment to operable status.
LCO 3.6.2 “Containment Air Locks” requirement
2 containment air locks shall be operable
LCO 3.6.2 “Containment Air Locks” applicability
Modes 1-4
LCO 3.6.2 “Containment Air Locks” notes/exceptions
- Entry/exit is permissible through a “locked” air lock door to perform repairs on the affected air lock components
- Separate condition entry is allowed for each air lock
- Enter applicable conditions and required actions of LCO 3.6.1 “Containment” when leakage results in exceeding the overall containment leakage rate acceptance criteria
LCO 3.6.2 “Containment Air Locks” required actions if 1 or more air locks with 1 or more air lock door inoperable
WITHIN 1 HOUR verify the operable door is closed in the affected air lock
LCO 3.6.2 “Containment Air Locks” required actions if 1 or more air locks with interlock mechanism inoperable
WITHIN 1 HOUR verify an operable door is closed in the affected air lock
LCO 3.6.2 “Containment Air Locks” required actions if 1 or more air locks inoperable for reasons other than a door or interlock mechanism inoperable
IMMEDIATELY initiate action to evaluate overall containment leakage rate per LCO 3.6.1
AND
WITHIN 1 HOUR verify a door is closed in the affected air lock.
LCO 3.6.3 “Containment Isolation Valves” requirement
Each containment isolation valve shall be operable
LCO 3.6.3 “Containment Isolation Valves” applicability
Modes 1-4
LCO 3.6.3 “Containment Isolation Valve” notes/exceptions
- penetration flow paths, except for 8” purge exhaust valves and 12” air room supply valves penetration flow paths, may be unisolated intermittently under admin controls
- separate condition entry is allowed for each penetration flow path
- enter applicable conditions and required actions for system(s) made inoperable by containment isolation valves
- enter applicable conditions and required actions of LCO 3.6.1 “Containment” when leakage results in exceeding overall containment leakage rate acceptance criteria
LCO 3.6.3 “Containment Isolation Valves” required actions if 1 or more penetration flow paths with 2 isolation valves inoperable (except for purge exhaust valve or air room supply valve not locked closed)
WITHIN 1 HOUR isolate the affected penetration flow path by use of at least 1 closed and de-activated automatic valve, closed manual valve, or blind flange
LCO 3.6.3 “Containment Isolation Valves” required actions if 1 or more purge exhaust or air room supply valves not locked closed
WITHIN 1 HOUR lock closed the affected valves
LCO 3.6.4 “Containment Pressure” requirement
Containment pressure shall be <= 1 psig in Modes 1-2, and <= 1.5 psig in Modes 3-4