1
Q
Describe how DFWCS feeds in RTO (5 points).
A
- RTO signal is generated by the UV relays (1&2 or 3&4)
- Controller will feed based on Tavg (564F) instead of level
- Will stop feeding at 51.9% NR
- Master controller is tracking
- MFPs receive speed signals from their own DFWCS
2
Q
Describe the inputs to digital feed in single element control (<14%).
A
- SG level error drives the master controller demand
- TLI (RRS) and SBCS master demand signal are used as an anticipatory input for better transient response
3
Q
What conditions will automatically shift the DFWCS master controller from 3E to 1E?
A
- 8% deviation; in FW flow
- 50% deviation is steam flow
- 13.5% and lowering reactor power
4
Q
Describe the ATUN lockout.
A
Deviation in either FW temperature or Control channel power will cause the controller to throw out the failed transmitter and use a canned value.
- ALARM = 4% temperature difference
- CANNED = 8% temperature difference…inserts 425F canned value
- ALARM = 4% reactor power difference
- CANNED = 8% reactor power difference…inserts 5% if below 16.5% inserts 60% if above 16.5%