Distance Relaying Flashcards
(71 cards)
Impedance in regards to distance relaying
▪︎Used to tell between faults and normal system conditions or between faults in a specific area and those elsewhere on the system
▪︎Done by limiting relay operation to a certain range of impedance
How is impedance on a transmission line determined
▪︎Type of conductor
▪︎Size of conductor
▪︎Spacing between conductors
▪︎Length of the line
Basic distance relaying principles
▪︎In a Phase to phase fault current would be virtually limitless without the impedance of the line
▪︎The further the distance between the fault location and the source of fault current the greater the impedance will be
▪︎Faults reduce power system voltage, based on severity and location
• During a fault voltage is highest at generation but drops to near 0 at the fault
▪︎These characteristics allow distance relays to measure the distance to the fault
Ohm’s law: V/I = Z
during a fault: Z of a transmission line is =V/I
If the Z/km of the line is known we can calculate the distance to the fault
What are zones of protection in regards to distance relays
▪︎Protection of a line uses multiple zones of protection.
▪︎These cover different lengths of the line and use different times for tripping
▪︎Typically 3 Zones
• Zone 1: under-reaching 80-90% of the line, instantaneous
• Zone 2: overreaching 120-150% of the line, time delayed
• Zone 3: overreaching 150-200% of the line, time-delayed. Can also look reverse
Zone 1
▪︎Generally 80-90% of the line
▪︎Instantaneous
▪︎Direct under-reaching
▪︎Cannot be set to 100% because it may trip for a fault beyond the line
▪︎80-90% used to account for possible relay inaccuracies and voltage and current transformer errors
Zone 2
▪︎Reaches beyond the next substation ▪︎120-150% ▪︎Permissive over-reach ▪︎Time delayed to prevent mis-operation ▪︎Protects remaining portion of the line
Zone 3
150-200%
3 terminal line relay settings
Zone 1 set to 80% of the nearest terminal
Zone 2 set to 150% of the furthest terminal
Rx diagram
▪︎Used to visually show a relays characteristics and how impedance is seen by a distance relay
▪︎Impedance consists of both resistance(R, shown on the x axis) and reactance(X, shown on the y axis)
• Is represented by a phasor plotted on the Rx diagram
The circle represents the “reach” or characteristic of a zone
Rx Diagrams: reach
Distance in ohms along a line defined by the relay angle in the forward direction at which the relay begins to develop contact closing torque
Rx diagram; relay angle
Angle defined by the line through the origin and the center of the relay characteristics
▪︎Normally factory set at 80%
Rx diagram: off set
▪︎Distance in ohms of the reverse reach
▪︎Typically not seen in zone 1 or 2 relays
▪︎Zone 3 relays can provide time delayed bus protection
Sources
Because distance delays function via Ohm’s Law current and potential sources are needed
▪︎Current input is from bidding CTs on the associated PCB and determine the direction of the relay
▪︎Voltage inputs deter mines the point from which the impedance is measured
• On a Main/Aux bus it’s from the M/B PTs
• On breaker and a half or ring bus it’s from the line CVTs
Types of distance relays
▪︎Impedance
▪︎Reactance
▪︎Admittance
▪︎Compensator
Impedance (balance beam) relay
▪︎There first style of distance relay used by BPA (Westinghouse HZ)
▪︎Two opposing coils affect the balance beam
• Voltage coil energized by bus voltage
• Current coil energized by line current
▪︎Normally the strength of the voltage coil is greater then that of the current coil =>the contacts are restrained open
▪︎When a fault occurs, voltage goes down and current goes up, overcoming the restraint voltage and closing the contacts
▪︎The ratio of voltage to current that will trip the balance beam is the “trip impedance”
▪︎This type of relay is non-directional
• A separate high speed directional unit is added
Reactance relay
▪︎Developed to counter that impedance relays may fail if there is high fault resistance
▪︎Ignores resistance and only looks at transmission line reactance to determine if a fault occurred
▪︎Most common was the GE GCX relay
▪︎Required directional supervision
▪︎Functioned on the induction cup principle
Admittance relay
▪︎Admittance (MHO) is the opposite of impedance (OHM)
• Impedance measures the opposition to current flow
• Admittance is a measure of how permissive a conductor is to current flow
• Mathematically, admittance is the inverse of impedance
▪︎Early MHO relay was the GE GCY
• MHO element 4-pole induction disk
• No added directional unit needed
• Each case contained 3 elements for 3 zone
• Storage timing relays needed for zone 2 and 3
Compensator relays
▪︎Most common electro mechanical relay on the system
▪︎KD - 3 phase single zone relay
• Voltage operated relay, operating voltage is a combo of voltages from three PTs and current is from the line CTs
• Contains 2 3-phase units, one for phase-place faults and the other for 3- phase faults
• 3 phase currents and voltages are supplied to the “compensators” for each unit
• Compensators are air- gap transformers
•Primary is supplied by current from CTs
•Secondary is supplied by voltage from PT
Timing relays for distance relays
▪︎Directional distance relays operate instantaneously for phase- phase and 3 phase faults that occur in the correct direction and with in the zone of protection therefore a time delay relay is needed for zones 2&3
Loss of potential
▪︎It’s a relay trap for pilot and distance delays
▪︎KD relays are especially sensitive
▪︎During normal operations
• The KD relay is retained by potential
• Loss of potential will cause the relay to lose restraining torque and trip contracts will close
▪︎KC over current fault detectors are used to ensure there is a fault but need to be set very low, so high current might be seen as a fault
• Can not be depended on for preventing a trip during all LOP situations
Standard line protection relay package with electromechanical relays
▪︎Directional ground relays (phase to ground protection)
•Instantaneous: set to under-reach, keys a pilot relay direct trip
•Time delayed: lightly set to over-reach, let’s a pilot relay permissive trip
▪︎Distance relays (phase- phase protection)
•Zone 1: under-reach ~80% of the line, keys direct trip
•Zone 2,3,4: time delayed over-reach, keys permissive trip
▪︎Pilot relaying: MWTT, mirror bit, CC etc.
▪︎Reclosing relay
▪︎Optional:
•KC fault detectors - verifies fault for LOP
•Multi-phase fault detectors for reclose blocking
•Switch on to fault relays
•JM annunciator
SEL-121G
▪︎Early SEL relay
▪︎Contains:
• O/C fault detectors
• Directional ground relays
• Distance relays with impedance measuring
• Reclosing
▪︎Is the equivalent to 3 KD relays, an IRD-9, a KRD, reclosing relay, and a KC fault detector
▪︎A computer is needed to access fault event info
SEL-121G inputs
▪︎Current from PCB bushing CTs
▪︎Relay potential is usually from bus PTs
▪︎Polarizing potential and current from the usual sources
• Can also develop its own negative sequence polarizing
SEL-121G reports
▪︎Long reports
• Gives a cook plate list of voltages and currents with a sample every 1/4 cycle for 11 cycles
• Indicates when relay inputs and outputs are asserted as well as the operation of various relay elements
• Instantaneous trips take only one event report
• Trip with a time delay >12 cycles takes 2 event reports
▪︎Short reports
• Do not list quarterly samples
▪︎Both reports
• Event 1 is the most recent event and 12 is the oldest
• All event history is lost when the relay is powered down