ECE Flashcards

(426 cards)

1
Q

Tactical and Safety Considerations

Due to limited access to entrance, lobbies, and courtyards, the engine may need to park _______
_______________ from the location.

A

well removed.

pg. 11

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

In tight complexes it may be necassry to park outside, leaving the closest acces for the ___________ ____________.

A

rescue unit

pg. 11

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

Multi-story Structure

Engine placement is the same as single-story structures, but the engine should be placed to leave the building _____________ __________.

A

corners open

pg. 13

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

Leaving the building corners open permits the ladder company to place the turntable in a position to reach ________ ________ of the structure

A

two sides

pg. 13

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

Tactical and Safety Considerations

Do not park under power lines.

true or false?

A

True.

pg. 13

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

Tactical and Safety Considerations

Do not park too close to involved structures.

true or false?

A

true

pg. 13

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

Leave the rear of ____ ________________ unobstructed to facilitate ground ladder and tool access.

A

all apparatus

pg. 13

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

Tactical and Safety Considerations

Newer engines need ___________ of space on the officer’s side to lower the ladder rack

A

5 feet

pg. 13

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

Tactical and Safety Considerations

contact ________ prior to attempting removal of any engine that has become stuck.

A

TSF

pg. 13

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

Tactical and Safety Considerations

Do not drive on private driveways or on private bridges except during emergency response.

true or false?

A

true

pg. 13

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

When backing, use a spotter on the engineer’s side, _________ feet from the tailboard.

A

5-10

pg. 14

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

The engineer and the spotter must maintain

_______ ______________ and the apparatus stopped when the spotter is no longer in view.

A

eye contact

pg. 14

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

The main sizes range from _____ to ______ in diameter and average _________ static pressure.

A

6” to 36”, 70 PSI

pg. 15

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

The communities _____________, ______________, and _____________ operate their own water utilities in the system parameters may differ somewhat from the majority of Jacksonville served by JEA

A

Atlantic Beach, Neptune Beach, Baldwin

pg. 15

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

Static sources include:

A

lakes, rivers, swimming pools, storage tanks, and retention ponds.

pg. 15

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

Portable tanker basins are also static sources.

true or false?

A

true

pg. 15

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
17
Q

All City hydrants are equipped with a ____ inlet and are supplied by the water main system

A

6”

pg. 15

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
18
Q

Dead end mains or loops, partially closed street valves, sediment build-up, and damaged mains can interfere with hydrant flow.

true or false?

A

true

pg. 15

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
19
Q

City fire hydrants

Color ___________, Steamer ________,
Side outlets _______, Static Pressure _______,
Residential ___________, Commercial _________

A
Yellow
4 1/2
2 1/2
70 PSI
6" to 10"
8" to 36"

pg. 16

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
20
Q

There are some older hydrants that do not have steamers connections. This may appear to be a handicap in terms of flow but a 2 1/2” discharge into 5” hose can still flow a ________ ________.

A

significant volume

pg. 16

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
21
Q

If the steamer connection is damaged or not accessible one 2 1/2” connection can be utilized, or to maximize flow use ______ 2 1/2”discharge connections

A

both

pg. 16

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
22
Q

Roadway Incidents

What is the primary consideration for engine placement.

A

Safety of the patient and responders

pg. 12

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
23
Q

Roadway Incidents

Spills and leaks may require spotting __________ and ______________.

A

uphill, upwind

pg. 12

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
24
Q

Roadway Incidents

If extrication is required, consider placement needs of the _________________ or ______________.

A

ladder truck, extrication engine

pg. 12

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
25
Single Story Structure The first arriving engine ladder company should be spotted in front of the structure in __________ _____________.
most cases pg. 12
26
Single Story Structure Position the engine for placement of __________ ___________ while leaving room in front of the structure for the ladder company.
attack lines pg. 12.
27
Private Systems The diameter of the backflow preventer is the same as the water main. true or false?
true pg. 16
28
Private Systems High pressure systems may be located at high risk facilities (__________) that require immediate firefighting pressure but don't have fire engines on site to boost pressure.
chemical or petroleum pg. 16
29
Private Systems At high risk facilities all pressure for firefighting is supplied within the private pump and main system. true or false?
true pg. 16
30
Private Systems Commercial plants, schools, shopping centers, aircraft hangars, and apartment complexes may utilize a private water supply. true or false?
true pg. 16
31
Private Fire Hydrants (Industrial Facilities) What is the color, thread sizes, and static pressure?
Red, steamer - 4 1/2", side outlets - 2 1/2", up to 180 PSI.
32
Private Fire Hydrants (Apartments and Business Complexes) What is the color, thread sizes, static pressure, and supply mains?
Red, steamer - 4 1/2", side outlets - 2 1/2", 70 PSI, and 6" to 10" pg.17
33
Private Hydrants Private hydrants are typically red but may be yellow or another color. true or false?
true pg. 17
34
Private Hydrants Some may utilize NFPA color codes which indicate the GPM flow. What color indicates a flow of less than 500 GPM.
Red pg. 17
35
Private Hydrants Some may utilize NFPA color codes which indicate the GPM flow. What color indicates a flow of 500 to 1000 GPM.
Orange pg. 17
36
Private Hydrants Some may utilize NFPA color codes which indicate the GPM flow. What color indicates a flow of 1000 to 1500 GPM.
Green pg. 17
37
Private Hydrants Some may utilize NFPA color codes which indicate the GPM flow. What color indicates a flow of greater than 1500 GPM.
Blue pg. 17
38
Private Hydrants Purple hydrants may be found on ______________ water mains.
reclaimed pg. 18
39
Private Hydrants Purple hydrants are for irrigation but may be used for firefighting in emergencies. true or false?
false (not intended for firefighting use) pg. 18
40
Sound barrier walls long limited access highways may incorporate access holes. (__________) to reach hydrants on nearby streets.
about 12" pg. 18
41
Regardless of the number of hydrants on a private system the flow may not be _______________.
sufficient pg. 18
42
The presence of dead end mains or dead end loops within the complex may require secondary methods to supply large volumes to water. true or false?
true pg. 18
43
Static Water Supply If water from a __________ static source enters the booster tank and pump, both must be thoroughly flushed after use.
natural pg. 18
44
Static Water Supply Fire department pumps are equipped with a primer to reduce pressure inside the pump below _________________ pressure.
atmospheric pg. 18
45
Booster Tank The booster tank is also static supply and is located higher than the pump intake manifold to take advantage of ______________________.
head pressure pg. 19
46
Booster Tank Each JFRD engine has a __________ TANK-TO-PUMP valve.
3" pg. 19
47
Booster Tank Flow from the booster tank is limited to ________________ GPM on all JFRD engines.
700-800 pg. 19
48
Booster Tank The size of the TANK-TO-PUMP valve and __________________ determines the flow from the booster tank.
head pressure pg. 19
49
Booster Tank Booster tanks shall be refilled from city hydrants and always from the nearest supply point. true or false?
true pg. 19
50
Booster Tank Only refill booster tanks from private hydrants in emergencies. true or false?
false (Do not refill from private hydrants) pg. 19
51
Dry Hydrants A dry hydrant consists of a pipe with threaded 4 1/2" steamer connection attached to a _____________________ supply.
static water pg. 19
52
Dry Hydrants The pipe is commonly PVC but could be _________________ or __________________.
cast iron, stainless steel pg. 19
53
Dry Hydrants These will be found near commercial structures (__________________________) were city hydrants are not within reach.
usually at retention ponds pg. 19
54
Dry Hydrant Considerations before using a dry hydrant:
• Is the hydrant maintained by the property owner ▪ the strainer could be obstructed with sediment or vegetation ▪ PVC pipes are easily damaged by vehicles vandalism and prolong UV exposure ▪ if the cap is missing the pipe could contain trash pg. 19
55
Dry Hydrant - considerations The engineer should ensure the engine gain access to the hydrant often they are placed some distance from the road or parking lot. true or false?
true pg. 19
56
Dry Hydrant - considerations The engineer should ensure there is sufficient water available. The water level in a retention pond fluctuates with rainfall. true or false?
true pg. 19
57
Hydrant and Main Locations Hydrant inspections are recorded using the Safety File Maintenance database within __________, which list the hydrant location in inspection.
Fireweb pg. 20
58
Hydrant and Main Locations Hydrants are plotted on mapping software managed by __________, which displays hydrant and fire station locations
JEA (https://maps.coj.net/hydrantproximity) pg. 20
59
Hydrant and Main Locations Water main locations and size along with associated infrastructure can be viewed at:
https://jaxgis.coj.net (then select "Duval Maps") pg. 20
60
In simplest terms the modern fire pump has three primary sections:
* Intake manifold (lower half of pump body) * Discharge manifold (upper half of pump body) * Centrifugal pump assembly (including impeller(s)) pg. 21
61
JFRD engines are built by Pierce and are fitted with midship mounted __________________ centrifugal pumps.
Waterous pg. 21
62
JFRD engines are either single-stage or two- stage and rated at ________, ___________, or ___________ GPM capacity.
1500, 1750, 2000 pg. 21
63
JFRD engines are powered by six-cylinder turbo- charged diesel motors manufactured by Caterpillar (C12 or c-13) or Cummings (ISL series). true or false?
true pg. 21
64
_________ can cause loss of prime and inhibit the ability of the pump the build pressure.
Air pg. 22
65
A pressurized water supply to the pump can be distributed to the various discharges even with the pump disengaged. true or false?
true pg. 22
66
The Impeller has a ____________________design allowing water under pressure to pass through the impeller when the pump is not engaged in the impeller is stationary.
"flow-through" pg. 22
67
Centrifugal pumps cannot pump air due to their __________ design
open pg. 22
68
``` The impeller(s) will rotate continuously when the pump is engaged, even when hoselines are shut down. ``` true or false?
true pg. 22
69
If equipped with two impellers (two-stage), they are mounted on separate shafts and rotate at the same speed (RPM). true or false?
false. (they are mounted on a common shaft) | pg. 22
70
This _________________ prevents a continuous rise and discharge pressure but can create excessive heat within the pump.
"slippage" pg. 22
71
The engineer must begin circulating water immediately after engaging the pump. Running the pump dry for more than a few minutes may cause excessive heat and pump damage. true or false?
true pg. 22
72
The pump shift control is a ____________ switch located in the cab at the engineer position
pneumatic pg. 23
73
Pump Shift There are 3 positions - _________, ____________ and ___________.
ROAD, NEUTRAL, PUMP pg. 23
74
The pump shift controls a _________________ within the transfer case.
ring gear pg. 23
75
The transfer case cannot engage both PUMP and ROAD simultaneously. true or false?
true pg. 23
76
Pump Shift The ______________ position is used only in the event of a failure with the pump shift requiring the use of the manual shift control.
neutral pg. 23
77
When shifting between ROAD and PUMP stop in the NEUTRAL position then to PUMP. true or false?
false. (do not stop) | pg. 23
78
The impeller discharges water into the _______________, the chamber which directs the pressurized water into the discharge manifold.
volute pg. 23
79
As motor speed (RPM) increases, the ______________ of the impeller(s) increases.
velocity pg. 23
80
Pump Testing Centrifugal pumps are tested by_________________ in accordance with ______________.
Underwriters Laboratories (UL), NFPA 1911 pg. 24
81
Pump Testing The volume at 150 PSI is called the ____________ ____________.
rated capacity pg. 24
82
Pump Testing The pump measures ____________ at three pressures while drafting.
volume pg. 24
83
Pump Testing A data plate is affixed to the pump panel with the results of the initial pump test. true or false
true pg. 24
84
Pump Testing The data plate may also indicate the test _______ and __________________.
RPM, governed speed pg. 24
85
Pump Testing It is more important understand that centrifugal pumps have the ability to pump _______ than their rated capacity is supplied from a pressurized source.
more pg. 24
86
Pump Stages Centrifugal pumps can be single stage or two stage design. true or false?
true pg. 24
87
Pump Stages A single stage has a single impeller, and is the ________________to build and operate.
simplest pg. 24
88
Pump Stages The two-stage pump has two impellers mounted on a common shaft. true or false?
true pg. 24
89
Two-Stage Pumps A two-stage pump can operate in one of two settings -
pressure or volume pg. 24
90
Two-Stage Pumps In PRESSURE each impeller provides pressure in_____________.
series pg. 24
91
Two-Stage Pumps, In simplest terms where a single impeller can produce 60 PSI, two impellers operating in series can produce ____________ at the same RPM.
120 PSI pg. 24
92
Two-Stage Pumps Roughly 50% of the pressure is produced by each impeller. true or false?
true pg. 24
93
Two-Stage Pumps In __________________, the supply is divided and water is routed to both impellers at the same time.
VOLUME pg. 25
94
Two-Stage Pumps The VOLUME position is also called ____________ and ____________.
parallel, capacity pg. 25
95
The advantage of a two-stage design is the ability to operate in either setting - PRESSURE (series) for maximum pressure or VOLUME (parallel) for maximum volume. true or false?
true pg. 25
96
Two-Stage Pumps Attempting to pump high volume in PRESSURE will not be successful. true false?
true pg. 25
97
Two-Stage Pumps Attempting to pump high pressure and VOLUME will require excessive RPM. true false?
true pg. 25
98
Changing between the two settings is accomplished by the ________________ which must be fully engaged in either PRESSURE or VOLUME (there is no intermediate position).
transfer valve pg. 25
99
Transfer Valve Utilize a ______ socket and socket wrench to change settings if the electronic valve fails.
3/4" pg. 25
100
The transfer valve is ______________ driven but also has a manual override in case of electric switch failure.
electrically pg. 25
101
The normal position of the transfer valve is ______________ which will produce maximum pump performance for the majority of pumping scenarios.
VOLUME pg. 25
102
High pressure needs such as a high-rise fire would require changing to the ________________ setting.
PRESSURE pg. 25
103
Transfer Valve CAUTION: To minimize water hammer temporarily reduce RPMs to idle before operating the transfer valve. true false?
true pg. 25
104
If unable to lower pressure to idle, reduce ______________ pressure a safe amount and operate transfer valve slowly, allowing time for the governor to adjust.
discharge pg. 25
105
When operating the transfer valve, do not sacrifice handlines already in use. true or false?
true pg. 25
106
Single-Stage Pumps The main difference in operation from a two-stage pump is ___________ _____________.
motor speed pg. 25
107
In most pumping situations there will be minimal difference in pump performance between a single-stage and two-stage pump. true or false
true pg. 25
108
To pump high pressures the single-stage pump requires higher ________.
RPM pg. 25
109
A single-stage pump will operate much like a two-stage pump in VOLUME. true or false?
true pg. 25
110
The Engineer should anticipate the requirements of the fire operation and properly set the _________ ____________ as early as possible.
transfer valve pg. 25
111
The intake side of a centrifugal pump is an open manifold directing water to the impeller(s). True or false?
true pg. 26
112
All intake connections share this common manifold. Due to this design there is only one ______________ _____________.
intake gauge pg. 26
113
If the pump is being supplied by a hydrant at 70 PSI, the entire intake manifold is pressurized to ____________.
70 PSI pg. 26
114
JFRD engines have _________ or ___________ intakes.
four, five pg. 26
115
There are two ______ steamer intakes and two ______ auxillary intakes (often called "pony" intakes) on each engine.
6", 2 1/2" pg. 26
116
Some engines have an additional ______ intake on the front or rear with an electrically controlled valve.
5" pg. 26
117
Each steamer intake has installed a piston intake valve (PIV) or ball intake valve (BIV). True or false
true pg. 26
118
Both types of intake valves incorporate a water control valve, a spring operated _____________ ___________ ___________, a bleeder valve to bleed air from supply hose, and a 5" stortz adapter.
pressure relief valve pg. 26
119
The newer BIV is less restrictive (allowing higher GPM) and is rated for drafting. true or false?
true pg. 26
120
The pump is protected by an intake pressure relief valve built into the pump, protecting the pump from ____________ __________ ___________.
excess intake pressure pg. 26
121
The PIV/BIV also includes a pressure relief valve that can provide redundant pump protection but can also protect ___________ __________ from excess pressure when the intake valve is closed.
supply hose pg. 26
122
Both the internal pressure relief valve and PIV/BIV are preset to _____________.
150 PSI pg. 26
123
The diameter of the intake pipe is determined by the __________ ______________ of the pump.
rated capacity pg. 27
124
All JFRD engines have ______ steamer intakes which allow the pump the draw the rated capacity at draft through one steamer intake (1500 GPM) or both steamer intakes (1750 and 2000 GPM).
6" pg. 27
125
The front and rear intake pipes are 5" in diameter and because of the reduced diameter will flow less than the steamers (_________ GPM at draft, _________ GPM from a hydrant).
1000, 1500 pg. 27
126
The rear intake is not properly equipped for drafting but can be used to connect 5" hose where on-scene access precludes use of the steamer connections. true or false?
true pg. 27
127
Front intakes are capable of drafting and in some situations will be the _______________ intake for drafting.
preferred pg. 27
128
E-7 and E-21 have one additional intake inside the tailboard compartment. true or false?
true pg. 27
129
E-7 and E-21's additional intake is a DIRECT TANK FILL and is painted _________ to distinguish it from other connections.
red pg. 27
130
E-7 and E-21 are equipped with foam proportioners, where the water from the foam solution is metered through the _______ _________ into the booster tank for more accurate finished foam.
red intake pg. 27
131
On hazmat incidents the red intake may be the preferred connection for the hydrant or tanker supply line. true or false?
true pg. 27
132
Most intake and discharge valves are quarter-turn ball valves which can be operated directly or by remote control handle at the pump panel (commonly called "______ ____________").
pull handles pg. 27
133
These valves, when opened, can be turned _______________ to "lock" in position.
45 degrees pg. 27
134
The valves should NOT be placed 45 dgrees in the "locked" position closed. true or false?
true pg. 27
135
Large diameter intakes and discharge use | ____________________ valves controlled by a hand wheel or electronic control.
quarter-turn pg. 27
136
Large diameter intakes and discharges valves, due to the large volumes they must be of the "_________________________" type to prevent water hammer.
slow-operating pg. 27
137
The electric front and rear intake valve take ____________ seconds to fully open or fully close.
15-20 pg. 27
138
The electric front and rear intake valve may be held closed by hydrant pressure. Partially open the valve before charging supply line. true or false?
true pg. 27
139
The most commonly used valves are ___________________ and ___________________.
TANK TO PUMP, TANK FILL pg. 28
140
The ___________________ valve allows booster tank water to be drawn into the pump to be pressurized and discharged.
TANK TO PUMP pg. 28
141
If tank water is used and an ___________ __________ is later established, the engineer should refill the booster tank as soon as possible.
external supply pg. 28
142
Once hoselines are properly set and there is enough residual pressure, open the _____________________ valve just enough to supply water to the tank without reducing residual pressure.
TANK FILL pg. 28
143
When the water supply is from a source other than the booster tank the ____________________ valve must be closed.
TANK TO PUMP pg. 28
144
Bleeder valves are installed at each intake and discharge connection to bleed incoming air (intake) or bleed water pressure when __________ ____ __________ (discharge).
taking up lines pg. 28
145
Bleeding air from intake lines is critical to avoid loss of ______________.
prime pg. 28
146
JFRD engines have a wide range of discharge options ranging from 1" booster line to a 4" LDH discharge. true or false?
true pg. 28
147
Each discharge valve has a corresponding discharge gauge, allowing the engineer to monitor and ______________ pressure to each individual discharge.
adjust pg. 28
148
The _______________ ______________ gauge reads the discharge manifold pressure while the remote discharge gauges indicate pressure within that discharge piping and hose line only.
master discharge pg. 28
149
Be sure to view the discharge gauge for the line charged when setting PDP. true or false?
true pg. 28
150
Each gauge is of the ___________________ type.
compound pg. 28
151
Compound gauges have a pressure scale (_____) and a vacuum scale (___________________ or inHg).
PSI, inches of Mercury pg. 28
152
The pressure scales reads from ______________ PSI, and the vacuum scale reads ___________ inches.
0-600, 0 to -30 pg. 28
153
While the pressure scale is graduated and easy to read, the vacuum scale is not. true or false?
true pg. 28
154
You can accurately measure vacuum at the pump panel. true or false?
false (cannot) pg. 28
155
The threaded plugs between the intake and discharge gauges are only used for ________ ______________.
pump testing pg. 28
156
A _______________ is required for a centrifugal pump due to the inability of the pump to move air.
primer pg. 29
157
A small amount of air inside the pump can prevent a large volume of water from being pumped. true or false?
true pg. 29
158
Activating the primer will remove air from the pump and allow __________________ to increase.
pressure pg. 29
159
Once air is removed, the pump is "____________".
primed pg. 29
160
The electric primer is a ____________ ___________ | pump driven by a small electric motor, and activated by a pull handle on the pump panel.
rotary vane pg. 29
161
Electric Primer Unlike the centrifugal fire pump, the primer is a _____________ _____________________ pump which can pump air and water.
positive displacement pg. 29
162
When the primer is activated it creates a vacuum with the fire pump, removing air so water can enter the pump. true or false?
true pg. 29
163
Newer engines utilize a ____________________ primer activated by pressing a button on the pump panel.
pneumatic pg. 29
164
Pneumatic Primer When activated, you will hear air being discharged from the pump. true or false?
true pg. 29
165
The pneumatic primer will prime the pump in the same manner as the electric primer and within the same time period. true or false?
true pg. 29
166
Engines with front intakes have two primers which should be operated independantly when utilizing the front intake. true or false?
false. (simultaneously) | pg. 29
167
If your primer is inoperative there are three alternative methods for bleeding air from the pump. true or false?
false (two methods) * partially open deck gun discharge valve * partially opening TANK FILL valve pg. 29
168
When using either of the two alternate methods for bleeding air - these methods may prime the pump faster than using the primer alone. true or false?
true pg. 29
169
Small amounts of air can also be purged by partially opening the ________________ valve.
TANK FILL pg. 29
170
Both types of priming pumps draw current from the vehicle charging system. Although you can safely operate the primer at any prssure or RPM, for best performance set the RPM between ________.
1000-1200 pg. 30
171
There are four motor functions to be monitored while pumping:
* coolant temperature * oil pressure * transmission temperature * voltage pg. 30
172
Motor Function Gauges These gauges are located on the pump panel and are redundant of ______ ____________.
cab gauges pg. 30
173
Motor Function Gauges They are connected to autible and visual alarms which will activate when readings are outside of the ____________ _________________.
normal parameters pg. 30
174
Motor Function Gauges Some engines have analog gauges and some are built-in to the governor control box. true or false?
true pg. 30
175
If the alarm sounds immediately check all gauges for the one displaying the abnormal reading. If all appear normal, compare the indications with the gauges in the _______.
cab pg. 30
176
Motor Function Gauges If the cab gauges also appear normal, contact ___________ to help identify the problem.
TSF pg. 30
177
Motor Function Gauges Normal oil pressure at idle:
15 PSI pg. 30
178
Motor Function Gauges Normal oil pressure at speed:
35-45 PSI pg. 30
179
Motor Function Gauges Normal coolant temperature:
180-220 degrees fully warmed up
180
Motor Function Gauges Normal voltage:
13 to 14.5 volts pg. 30
181
Motor Function Gauges Normal Tranmission temperature:
Under 300 degrees is normal pg. 30
182
Motor Function Gauges Once an abnormal condition is confirmed or suspected stop operation as soon as possible. true or false?
true pg. 30
183
Motor Function Gauges A low voltage indication will gradually reduce motor _________.
RPM pg. 30
184
Motor Function Gauges High coolant temperature or low oil pressure could result in ___________ ______________.
motor damage pg. 30
185
Motor Function Gauges If an abnormal indication occurs while on scene take any steps necessary to prevent apparatus damage without endangering ________________ _________.
handline crews pg. 30
186
Motor Function Gauges The tachometer measures _____________ RPM and is located on the pump panel.
motor pg. 30
187
Motor Function Gauges The tachometer may be analog or digital and may be built-in to the governor control panel. true or false?
true pg. 30
188
Motor Function Gauges Always be aware of the motor ________ while pumping.
RPM pg. 30
189
Motor Function Gauges The coolant temperature gauge indicates the ________ cooling system temperature, not the pump water.
motor pg. 31
190
Pump water temperature can best be monitored by feeling the pump _____________.
piping pg. 31
191
Pump Cooler/Recirculator This valve controls a small discharge line that directs water to the ___________ _________.
booster tank pg. 31
192
Pump Cooler/Recirculator When opened it flows less than ________ and will remove hot pump water, to be replaced with cooler water from the supply.
25 GPM pg. 31
193
Pump Cooler/Recirculator If the pump is being supplied by a tanker or hydrant and this valve is open, you will eventually _______________ the booster tank
overflow pg. 31
194
Pump Cooler/Recirculator This valve is generally only needed when hose lines are charged but ______ ____________.
not flowing pg. 31
195
Thermal Dump Valve Some engines have a thermal dump valve. This valve is temperature activated at ______ degrees and discharges water into the booster tank or onto the ground.
120 pg. 31
196
Pump Cooler/Recirculator When the pump water cools down the valve must be manually reset. true or false?
false (reseats itself) pg. 31
197
Engine Cooler or Auxillary Cooler This valve operates as a ________ ______________.
heat exchanger pg. 31
198
Engine Cooler or Auxilary Cooler To prevent overheating while the pump is operating open this valve to discharge cool pump water through the __________________.
radiator pg. 31
199
Engine Cooler or Auxilary Cooler Within the radiator is a coil of tubing and pump water flows through this coil to reduce the ___________ ___________________.
coolant temperature pg. 31
200
Engine Cooler or Auxilary Cooler The pump doesn't need to be engaged for this valve to function. true or false?
false. (pump must be engaged) | pg. 31
201
Engine Cooler or Auxilary Cooler This valve should be opened any time the coolant temperature _____________ the normal level.
exceeds pg. 31
202
Pressure Governor A pressure governor can make automatic adjustments to _____________ pressure in order to compensate for variables in ____________ pressure.
discharge, intake pg. 33
203
Pressure Governor This device is designed to keep discharge pressure at a constant level making it safer for __________________ __________.
handline crews pg. 33
204
Pressure Governor Normally the pressure governor requires _________ adjustment once set by the engineer, and requires no maintenance.
little pg. 33
205
Pressure Governor The governor is integrated into the motor's fuel management system and controls pump discharge pressure (PDP) by changing motor _________.
RPM pg. 33
206
The pressure governor consists of only two major parts - the control box (located on the pump panel) and the pressure sensor (installed within the discharge manifold). true or false?
true pg. 33
207
Pressure Governor The pressure sensor monitors _______ and transmits the _______ signals to the control box.
PDP, PDP pg. 33
208
Pressure Governor The control box transmits signals to the motor's fuel management system to increase or decrease ________ as required to maintain the PDP as set by the engineer.
RPM pg. 33
209
Pressure Governor When the pump is engaged the cab throttle controls (accelerator pedal and high idle switch) are operable. true or false?
false (disabled) pg. 33
210
Types of Governors and Modes of Operation JFRD utilizes three types of pressure governors:
* Class 1 * Pump Boss 100 * Pump Boss 200 pg. 34
211
The Class 1 unit is installed on _________________ engines purchased before 2008.
two-staged pg. 34
212
Each governor has two modes of operation - _______ and ________.
PSI, RPM pg. 34
213
PSI Mode Selecting PSI allows the pressure governor to monitor and regulate ________.
PDP pg. 34
214
Once the engineer sets the PDP by utilizing the throttle, the governor is automatically "set". true or false?
true pg. 34
215
PSI Mode Any changes to the discharge pressure will be compensated by the governor through a change in ___________.
RPM pg. 34
216
PSI Mode The governor in this mode can be compared to an automotive "___________________".
cruise-control pg. 34
217
PSI Mode The governor will vary the RPM in order to maintain the set _________ much as a cruise control will vary RPM to maintain vehicle speed.
PDP pg. 34
218
PSI Mode The most common disruption to PDP is the
opening and closing of nozzles. pg. 34
219
PSI Mode Any change to intake pressure will be felt on the _______________ side of the pump, such as changing from tank supply to hydrant supply.
discharge pg. 34
220
PSI Mode The PSI mode can _______________ these fluctuations and provide a constant discharge pressure.
minimize pg. 34
221
The engineer must select PSI mode for the following fireground operations: (3)
* Pumping handlines * Pumping ladder pipes or ground monitors * Supplying a sprinkler or standpipe pg. 35
222
NOTE: Although the transfer valve also has a PRESSURE setting there is no relationship - the transfer valve and governor function independently. true or false?
true pg. 35
223
PSI Mode High rise pumping operations that exceed 300 PSI will require the engineer to change to RPM mode. true or false?
true pg. 35
224
The pressure sensor is disabled above _________ PSI.
300 pg. 35
225
RPM Mode Selecting the RPM MODE disables the pressure sensor and the governor will maintain the set _________ only.
RPM pg. 35
226
RPM Mode In this mode the governor works as a simple throttle, placing the engineer in ______________ _______________ of RPM and corresponding PDP.
complete control pg. 35
227
RPM Mode No automatic adjustments will be made to regulate PDP, and pumping multiple hoselines in RPM MODE may result in pressure ______________________.
fluctuations pg. 35
228
Engineers must select RPM mode for the following fireground operations: (4)
* Drafting * Relay pumping * Charging 5" hose * PSI mode malfunction pg. 35
229
During a _____________ operation, the pump may initially be empty.
drafting pg. 35
230
When there is no water in the pump the pressure sensor will not allow the ________________ to operate in PSI MODE.
governor pg. 35
231
In ___________MODE the pressure sensor is disabled, allowing the engineer to increase RPM in order to draft.
RPM pg. 35
232
Once a draft is established, change to __________________.
PSI MODE pg. 35
233
When _______________________ only the attack engine needs to operate in PSI MODE.
relay pumping pg. 36
234
Other engines (other than attack engine) in a relay supplying water can operate more efficiently in RPM MODE. This also applies to a tanker supplying an engine on-scene. true or false?
true pg. 36
235
When opening the ______________________ valve the PDP may drop suddenly.
LDH discharge pg. 36
236
When opening the LDH discharge valve the PDP may drop suddenly. The pressure sensor will detect this pressure drop and signal the motor to increase RPM. true or false?
true pg. 36
237
Change to ____________ before charging 5" hose when using other lines.
RPM MODE pg. 36
238
Operate all valves slowly. This will allow the governor to better maintain the PDP. Opening and closing valves quickly will result in ______ that are beyond the governor's ability to control.
pressure fluctuations pg. 36
239
If for any reason the governor does not seem to be working properly in PSI MODE there may be a ______________________________.
PSI mode malfunction pg. 36
240
During a PSI mode malfunction the most likely cause is a failure of the _____________________ or a loss of ____________________ between the pressure sensor and the control box.
pressure sensor, electronic signal pg. 36
241
During a PSI mode malfunction changing to ____________ allows the engineer to increase or decrease PDP as needed.
RPM MODE pg. 36
242
When operating in RPM MODE there is no automatic pressure ________________. Changes in intake or discharge pressure can effect hoseline safety - the engineer must closely monitor PDP.
protection pg. 36
243
With each governor type the following steps must be accomplished in the order listed to ensure proper operation. (4)
1. Engage the pump 2. Open TANK TO PUMP valve 3. Open appropriate discharge valve 4. Operate governor pg. 36
244
The pressure sensor must detect ________ in the pump to operate.
PDP pg. 36
245
If the governor will not increase PDP and you have ensured an adequate water supply, suspect ______________ in the pump.
air pg. 37
246
The digital readout may display LO PRESSURE or LO SUPPLY when the pressure sensor cannot detact PDP. true or false?
true pg. 37
247
To operate the Class 1 Governor: When the pump is initially engaged the Class 1 unit is in "_____________" mode.
standby pg. 37
248
To operate the Class 1 Governor: The digital readout on the control box will read "___________".
MODE pg. 37
249
To operate the Class 1 Governor: To apply power, press the "_________" button.
MODE pg. 37
250
To operate the Class 1 Governor: ___________ press selects the PSI MODE.
One pg. 37
251
To operate the Class 1 Governor: A ________________ press changes to RPM MODE.
second pg. 37
252
To operate the Class 1 Governor: ``` A MODE (PSI or RPM) must be selected before you can operate the throttle buttons or presets. ``` true or false?
true pg. 37
253
To operate the Pump Boss Governor: Once the Pump Boss governor is on and defaults to ____________. It is ready to pump.
PSI MODE pg. 37
254
To operate the Class 1 Governor: The digital readout will indicate the ________.
PDP pg. 37
255
To operate the Pump Boss Governor: Changing modes is accomplished by pressing and holding the MODE button or PSI/RPM button for ______________.
3 seconds pg. 37
256
Presets Each pressure governor has a PRESET button and both an RPM and PSI preset are programmed by ________.
TSF pg. 37
257
Presets The engine PSI preset is ___________ PSI and tanker PSI preset is _________ PSI.
110, 50 pg. 37
258
Presets The RPM preset for both engines and tankers is __________ RPM.
1100 pg. 37
259
Presets Using the PRESET button is ______________.
optional pg. 37
260
Presets You can press the PRESET button at any pressure or RPM. true or false?
true pg. 37
261
Presets On the Class 1 Governor the RPM preset is disabled if the pump is engaged. true or false?
true pg. 37
262
Presets On the Pump Boss governor, both presets are available with the pump engaged true or false?
true pg. 37
263
The pressure governor can also serve as a ________ ____________ control in RPM MODE with the pump disengaged.
high idle pg. 37
264
Engines and tankers also have a HIGH IDLE switch in the cab. true or false?
true pg. 37
265
Idle Button The governor has an IDLE button which can be used at any ___________.
time pg. 37
266
When the idle button is depressed on the Class 1 unit the motor returns to idle RPM and the unit returns to ________________ mode.
standby pg. 37
267
Idle button At idle on the Class 1 governor to throttle up you will have to again press _________ to apply power and select PSI or RPM.
MODE pg. 37
268
Tips for Pressure Governor Operation Operate two-stage pumps routinely with the transfer valve in __________________.
VOLUME pg. 38
269
Tips for Pressure Governor Operation The discharge pressure at idle will be ___________ PSI.
30-40 pg. 38
270
Tips for Pressure Governor Operation The engineer can switch from PSI to RPM and back at any time and at any pressure. No water hammer can occur from a MODE change true or false?
true pg. 38
271
If your water supply runs low the governor will attempt to maintain PDP by increasing RPM. true or false?
true pg. 38
272
If the pump cannot maintain at least ______ PSI PDP, the governor will return the RPM to idle. This is a safeguard to prevent cavitation.
30 pg. 38
273
Flow from the booster tank is limited to _______________ GPM on all JFRD engines.
700-800 pg. 38
274
If you need to supply the deck gun from the booster tank, use the fog nozzle at ________ GPM or a _______ or ________ tip.
500, 1-1/4", 1-3/8 pg. 38
275
When residual pressure gets low (below 10 PSI), the governor may sense a supply problem and return RPM to idle. true or false?
true pg. 38
276
When residual pressure gets low (below 10 PSI), if additional volume is not available and you can safely operate at this residual pressure, change to ______________ and continue pumping.
RPM MODE pg. 38
277
Attempts to pump low volume at high pressure (booster line) may cause mild cavitation in pump and governor may falsely interpret as low water supply and return the RPM to idle. true or false?
true pg. 38
278
The Class 1 digital readout may provide important messages during pumping operations. true or false?
true pg. 38
279
The Pump Boss provides only a few messages which are self explanatory. true or false?
true pg. 38
280
The governor is an electronic device and subject to voltage and current irregularities. true or false?
true pg. 38
281
If governor control box is without power after engaging pump, you may have to disengage pump, shut off motor/batteries, re-initiate starting sequence and re-engage the pump. true or false?
true pg. 38
282
The minimum hose inventory of each engine shall consist of:
• 5" - 1000 feet • 2-1/2 - 1000 feet • 1" Booster line. 200 feet • 10ft hard suction. 2 (two) sections • High Rise Pack. 150' of 1-3/4 hose • Pre-connected 1-3/4 attack lines. 2 (two) 200 foot 1-3/4 crosslays All other 1-3/4 attack lines length per Co. Capt. • Wildland Hose. 200' of 1" hose pg. 39
283
5" Hose 5" hose fitted with storz quarter-turn couplings are the primary supply hose. true or false?
true pg. 39
284
5" Hose Couplings can be placed in random locations, but must be staggered and cannot ________ ________ during layout.
flip over pg. 39
285
A rope "____________ _________" with a hydrant wrench and two 5" spanner wrenches shall be readily available for laying a supply line.
hydrant loop pg. 39
286
When connecting 5" hose to the intake valve, never place a left hand twist in the hose. It may uncouple upon charging. true or false?
false. (never place a right hand twist) | pg. 39
287
If a hose clamp is used when laying out, the clamp must be placed close to a coupling on the ______________ side.
supply
288
The 5" hose will extended horizontally when charged, so always clamp at least _________ back from the tail board.
25' pg. 39
289
A supply line connected to a hydrant at incident scenes shall be _____ or ___________.
5", larger pg. 39
290
WARNING: When loosening the hose clamp do not position yourself on the ________ _______ of the clamp.
hinge side pg. 39
291
The engineer shall direct the opening of the hydrant by: (3)
• portable radio or • by signaling with arms extended over the head (when the engine can be seen from the hydrant) • If the above methods are impractical utilize a runner pg. 39
292
Crossing 5" hose shall be done in a manner that minimizes the chance of hose or coupling damage. true or false?
true pg. 39
293
5" Hose Guidelines: (3)
* Lay 5" in a manner to avoid the path of vehicles if possible. * Any crossing should be done at an angle and not straight on. * If 5" hose must be crossed, only vehicles with high ground clearance should be permitted to do so. pg. 40
294
CAUTION: Rescue units as well as some engines and ladders have low suspension and cannot drive over an 5" hose coupling. true or false?
true pg. 40
295
5" hose has a comparatively small amount of friction loss compared to 2-1/2" hose but it too has __________________.
limitations pg. 40
296
5" Hose A flow of 1200 GPM has ______ PSI friction loss per 100' section of hose.
10 pg. 40
297
__________ GPM is the practical volume limit of 5" hose.
1600 pg. 40
298
5" Hose If a full bed load of 5" hose is used to supply an attack engine, an additional engine should "hook-up" to the hydrant and __________ _________ the supply line.
relay pump pg. 40
299
5" hose lays requiring multiple bed loads may require several in-line relay engines in addition to the engine at the hydrant. true or false?
true pg. 40
300
Pumping 5" hose requires two-stage pumps to be operated in _______________.
VOLUME pg. 40
301
5" Hose Maintain a minimum of _____ PSI residual pressure and never exceed _______ PSI PDP.
10, 200 pg. 40
302
Storz Adapters and Appliances 5" female to 5" storz adapter is located:
on the front or rear intake pg. 40
303
Storz Adapters and Appliances 4" female to 5" storz adapter is located:
on the LDH discharge valve pg. 41
304
2-1/2" female to 5" storz adapter is used for:
connecting 5" hose to the 2-1/2" outlet on a hydrant. pg. 41
305
4-1/2" female to 5" adapter is used as:
the standard JFRD hydrant connection, normally installed on 5" hose in the hosebed. pg. 41
306
2-1/2" Hose 2-1/2" hose shall be loaded in the hosebed with the male coupling ___________ top.
out/on pg. 41
307
2-1/2" Hose This hose is versatile and can be used for a variety of applications: (5)
* FDC - to supply a sprinkler or standpipe system. * Master Stream - to supply the ground monitor and mini-monitor. * Handline - can be used to extend 1-3/4 hoselines that are farther from the engine than the pre-connected length to reduce friction loss. * Supply - to transfer water between apparatus on scene. pg. 41
308
2-1/2" Pre-connected Handline Advantage: (2)
* Rapid Deployment * Up to 300 GPM pg. 42
309
2-1/2" Pre-connected Handline Disadvantage: (1)
• Relatively short lengths (200' or less) may be a limiting factor for large area structures. pg. 42
310
2-1/2" Static Load Advantage: (1)
• Ability to carry several hundred feet of hose so the proper length can be deployed. pg. 42
311
2-1/2" Static Load Disadvantage: (1)
• The engineer must break the coupling and connect to the desired discharge outlet. pg. 42
312
2-1/2" x 1-1/2" Gated Wye Every engine company should carry at least two - where are the located?
• one in the high rise bag and • one on the front bumper discharge. pg. 43
313
2-1/2" Siamese This adapter is used for: (2)
* For joining two 2-1/2" hose lines together to form one hose line. * Other uses include augmenting the FDC to increase sprinkler or standpipe flow. pg. 43
314
2-1/2" Smooth Bore Nozzle This stacked tip nozzle operates at 50 PSI nozzle pressure (NP) and flows thr following: 1" = 1-1/8" = 1-1/4" =
``` 1" = 200 GPM 1-1/8" = 250 GPM 1-1/4" = 300 GPM ``` pg. 43
315
2-1/2" Smooth Bore Nozzle WARNING: The maximum safe flow through a 2-1/2" handline is _________ GPM.
300 pg. 43
316
To compensate for friction loss in a 2-1/2" handlines add ______ PSI per 100' to the PDP. This standard works equally well for fog streams or smooth bore nozzles.
10 pg. 43
317
Akron Turbojet 2-1/2" Fog Nozzle Operates at 100 PSI NP with an adjustable flow range of _____, ______, ______, and _______ GPM.
125, 150, 200, 250 pg. 43
318
Akron Turbojet 2-1/2" Fog Nozzle Has a "break-apart" feature allowing ________ hose to be extended from the playpipe.
1-3/4" pg. 43
319
Akron Turbojet 2-1/2" Fog Nozzle WARNING: Rotating the bumper fully ____________ will shut off the nozzle even if the bale is open.
clockwise pg. 43
320
1-3/4" Hose and Nozzles 1-3/4" hose loaded in a pre-connected manner is the "_______________________" attack line of the JFRD.
bread and butter pg. 44
321
1-3/4" Hose and Nozzles The hose and nozzles are color coded for rapid recognition. What colors are for the crosslays?
RED and YELLOW pg. 44
322
1-3/4" Hose and Nozzles The hose and nozzles are color coded for rapid recognition. What colors are for the rear and bumper lines?
WHITE and ORANGE pg. 44
323
Akron Turbojet Nozzle - This nozzle has five settings from 30-200 GPM. however, JFRD recommends the _____, ______ or _______ GPM setting for initial interior firefighting.
95, 125, 150 pg. 44
324
Akron Turbojet Nozzle NOTE: Always check GPM setting at the beginning of your shift and prior to use. true or false?
true pg. 44
325
Akron Turbojet Nozzle NOTE: Be sure to add ______ PSI PDP per floor when operating above ground level.
5 pg. 44
326
There are two pressure variants of the Akron Turbojet nozzle. true or false?
true pg. 44
327
Akron Turbojet Nozzle The color coded versions require _______ NP, and the black version (used by the Hazardous Materials Teams) require ______ NP.
75 PSI, 100 PSI pg. 44
328
Akron Turbojet Nozzle The 100 PSI nozzle has greater reach but identical GPM settings. true or false?
true pg. 44
329
Akron Turbojet (75 PSI) Color-Coded Fog Nozzle A PDP of ______ PSI will allow the nozzle operator to select 95, 125, or 150 GPM on the nozzle and attain this flow.
110 pg. 44
330
Akron Turbojet (75 PSI) Color-Coded Fog Nozzle The nozzle operator can change the GPM setting with no adjustment in PDP. true or false?
true pg. 44
331
Akron Turbojet (75 PSI) Color-Coded Fog Nozzle A desired flow of 200 GPM requires an increase in PDP from 110 PSI to __________. Two firefighters may be required for safe handling.
150 PSI pg. 44
332
Akron Turbojet (100 PSI) Black Fog Nozzle A pump discharge pressure of _____ PSI will allow the nozzle operator to select 95, 125, or 150 GPM on the nozzle and attain this flow.
135 pg. 45
333
Akron Turbojet (100 PSI) Black Fog Nozzle The nozzle operator can change the GPM setting with no adjustment in PDP required. true or false?
true pg. 45
334
Akron Turbojet (100 PSI) Black Fog Nozzle A desired flow of 200 GPM requires an increase in PDP from 135 PSI to ________. Two firefighters may he requied for safe handling.
175 PSI pg. 45
335
There is greater tendency for handlines to ________ when used with the 75 PSI nozzle.
kink pg. 45
336
A quick remedy (kinks) is to ____________ initial PDP when charging, then reduce to the recommended PDP.
increase pg. 45
337
If the nozzle operator experiences a sudden PSI loss while advancing suspect a ____________ _______.
kinked line pg. 45
338
Akron Turbojet (100 PSI) Black Fog Nozzle All firefighters on scene shall be watchful for _________ and assist in feeding hose into and inside a structure
kinks pg. 45
339
If hose kinks become frequent the engineer can boost PDP by __________ PSI.
10-25 pg. 45
340
Akron SaberJet Nozzle This 1-3/4" nozzle has a dual position bale allowing the operator operator to select a fog or solid stream. true or false?
true pg. 45
341
Akron SaberJet Nozzle The fog ranges from a narrow angle to a wide-angle and cannot produce a ____________ ____________.
straight stream pg. 45
342
Akron SaberJet Nozzle The smooth bore can be configured for _______ or ________ tip.
7/8, 15/16 pg. 45
343
Akron SaberJet Nozzle it can flow both fog and solid stream simultaneously. true or false?
false. (can not) | pg. 45
344
Akron SaberJet Nozzle The solid stream setting will flow: (2)
* 150 GPM at 50 PSI NP (7/8) * 180 GPM at 50 PSI NP (15/16) pg. 45
345
Akron SaberJet Nozzle The fog stream setting will flow: (1)
• 135 GPM at 100 PDI NP pg. 45
346
Akron SaberJet Nozzle When the solid stream is selected this nozzle may require two firefighters for safe control. true or false?
true pg. 46
347
Akron SaberJet Nozzle If less volume is sufficient, this nozzle produces a quality fog and solid stream at lower pressures that can be handled by one firefighter. true or false?
true pg. 46
348
Akron SaberJet Nozzle The nozzle operator can change from fog to solid and back with _________ PDP adjustment required.
no pg. 46
349
Akron SaberJet Nozzle No PDP adjustment is required when changing from fog to solid because the change in GPM results in a corresponding friction loss (friction loss increases by ______PSI).
40-50 pg. 46
350
High Rise Nozzle This nozzle shall be located with the high-rise kit and it's designed for use from standpipes. true or false?
true pg. 46
351
High Rise Nozzle This nozzle combines a fog and solid stream nozzle and requires only ___________ NP for either option
50 PSI pg. 46
352
High Rise Nozzle The fog attachment provides ________ GPM
150 pg. 46
353
High Rise Nozzle The nozzle operator can shut off the nozzle bale and remove the fog tip revealing a. _____ smooth bore which woll flow 150 GPM.
7/8 pg. 46
354
Automatic Nozzles Some engines and tankers may utilize automatic nozzles for backup use. They can be easily identified by their ___________ bumper.
yellow pg. 46
355
Automatic Nozzles For 150' and 200' lines the PDP is 1 PSI per GPM desired, with a minumum _____ PSI PDP.
100 pg. 46
356
Automatic Nozzles These nozzles will have a corresponding increase in GPM as PDP increases. true or false?
true pg. 46
357
Automatic Nozzles WARNING: Automatic nozzles produce a good-looking stream at low pressures, however the GPM may be unsafe for interior firefighting. true or false?
true pg. 46
358
Each engine company shall maintain of _______ of 1-3/4" hose with nozzle for connection to a standpipe.
150' pg. 46
359
The high-rise bag shall include a 2-1/2" to 1-1/2" gated wye, 6' of 2-1/2" hose, spanner wrench, pipe wrench (at least _____), and a marking device.
14" pg. 46
360
All crosslays should be equipped with _____ short sections at the discharge pipe. These sections are useful when extending a line or placing a foam eductor in-line.
10' pg. 47
361
Booster Hose Each engine carries _______ of 1" booster hose. It is used for a variety of small fires, wildland fires, or overhaul.
200' pg. 47
362
Booster Hose Each booster hose is equipped with an automatic nozzle and will flow a maximum of _______ at _______ PDP. They will flow less volume at reduced pressure which is recommended.
70 GPM, 300 PSI pg. 47
363
Booster Hose Ensure transfer valves are set to PRESSURE when pumping booster hose at high pressure. true false?
true pg. 47
364
CAUTION: Sustained high pressures combined with low pumping volume can contribute to high pump temperature and impeller damage. true or false?
true pg. 47
365
Hard Suction Hose All engines carry two 10-foot sections of hard suction hose. There is (1) heavy duty hose and (1) drafting hose. Each hose has ____ threads to match the steamer connection
6" pg. 47
366
Hard Suction Hose Heavy duty hose is for drafting or connection to a ______________. This hose is heavy, not very flexible, and difficult to maneuver.
hydrant pg. 47
367
Hard Suction Hose The drafting hose is lightweight and flexible but is for drafting only and cannot be pressurized. true or false?
true pg. 47
368
Hard Suction Hose The 6" to 4-1/2" adapter and 6" to 2-1/2" adapter permit the hard suction hose to be connected to a _______________.
hydrant pg. 47
369
Each engine shall be equipped with a barrel-style strainer and rope for ____________ from a natural static source
drafting pg. 47
370
Low Level Strainer Two types of low-level strainers are in use to facilitate drafting from tanker basins. true or false?
true pg. 48
371
Low Level Strainer Each tanker carries a strainer with 4-1/2" threads. Also attached to this adapter is a 4-1/2" ____________ _________ adapter.
double male pg. 48
372
Low Level Strainer Connecting to 6" hard suction requires a ______________ adapter (also carry by tankers)
4-1/2" to 6" pg. 48
373
Low Level Strainer A newer type strainer with a check valve is carried by engines with ___________ ___________.
front intakes pg. 48
374
Low Level Strainer The newer type strainer is red in color and has 6" threads. true or false?
true pg. 48
375
Low Level Strainer With the newer type strainer the check valve can allow rapid drafting even when the primer is inoperative. true or false?
true pg. 48
376
Low Level Strainer The new type strainer is lightweight and may need to be _______________ down in tanker basin.
weighted pg. 48
377
Soft Intake Hose some engines may be equipped with soft intake hose 6" in diameter, _________in length.
25 feet pg. 48
378
Soft Intake Hose It has 6" threads on one end 4-1/2" threads on the other. This hose will flow up to _______ GPM.
2000 pg. 48
379
Attic Nozzle Ladder companies and some engines carry distributor nozzles that can be placed into attic spaces from the floor below. true or false?
true pg. 48
380
Attic Nozzle The complete set includes two lengths of 1-1/2" aluminum pipe (__________ and __________), a 1-1/2" to 2-1/2" increaser, and a standard play-pipe.
2 feet, 6 feet pg. 48
381
Attic Nozzles Flow for each: 1-1/2" fog stream = __________ 2-1/2" broken stream = __________ 1-1/2" broken stream = __________
160 GPM 495 GPM 140 GPM pg. 48
382
Class "A" Foam This is used primarily for _______________ fires and is not compatible with class B foams.
wildland
383
Class "A" Foam Class A foam is actually a wetting agent and can break down the ____________ _____________ of water permitting greater penetration of water into class A fuels.
surface tension pg. 49
384
Class "A" Foam It is educted at 1/4% to 1%. Do not use class B foams on class A fires. true or false?
true pg. 49
385
Each engine and tanker is equipped with class A and Class B foams and application appliances. true or false?
true pg. 49
386
Class "B" Foams Alcohol resistant versions of aqueous film forming foam (AR-AFFF) have proven to be effective on all types of Class B fires. true or false?
true pg. 49
387
Class "B" Foams Ansulite low-viscosity AR-AFFF and Thunderstorm AR-AFFF are the class B foams utilized by JFRD. true or false?
true pg. 49
388
Class "B" Foams They are equally effective on hydrocarbon fuels (gasoline, kerosene, diesel fuel) as well as __________ __________ (ethanol and ethanol blends, methanol and ketones).
polar solvents pg. 49
389
Class "B" Foams These foams are educted at 3% and are compatible with each other. true or false?
true pg. 49
390
Class "B" Foams NOTE: All gasoline now contains at least 10% ethanol. AR-AFFF and the Akron foam tube are required to achieve proper aeration to extinguish these fires. true or false?
true pg. 49
391
Engine 7 and 21 - These engines have built-in foam proportioners and tanks _____________foam is more compatible with these systems.
Mil-Spec pg. 49
392
Station 16 and 56 - Aviation fuel is a non-polar hydrocarbon fuel very similar to kerosene. ___________________ will be most effective
Mil-Spec AFFF pg. 49
393
Foam 37 / 371 - Although these tankers respond citywide their main purpose is to protect the Navy Fuel Depot which stores aviation fuel. Each tanker carries ____ gallons of foam concentrate.
1800 pg. 49
394
CAUTION: Mil-Spec 3% AFFF is NOT compatible with AR-AFFF and should never be mixed. Never add AR-AFFF to any apparatus foam tank. true or false?
true pg. 50
395
Each engine shall carry enough foam concentrate to convert booster tank water to finished foam. This calls for _ gallons of concentrate or 3 - 4 pails (3 gallons per 100 gallons tank cap.)
15-18 pg. 50
396
Ea. tanker shall carry enough foam concentrate to convert the 2500 gallon tank into finished foam. This calls for __ gallons of concentrate or 15 pails (3 gallons per 100 gallons of tank cap)
75 pg. 50
397
In addition to foam concentrate each engine and tanker shall carry basic foam nozzles and proportioning equipment. True or false?
True pg. 50
398
A foam eductor rated at 125 GPM. This device is adjustable from 1/4% to 6%. . It is used with the standard 1-3/4 handline. True or false?
True pg. 50
399
Akron Turbojet fog nozzle set at _____ GPM (75 100 PSI variant). The 100 PSI nozzle is more compatible with E-7 and E-21 foam proportioners incapable of greater stream reach.
125 pg. 50
400
Akron foam tube, provides aggressive aeration at nozzle instead of having to create a foam blanket by indirect methods. Foam tube attaches to 1-3/4 Akron TurboJet nozzle only. True or false?
True pg. 50
401
The foam eductor shall be set to match the foam concentrate. Example 3% concentrate educts at 3% setting True or false?
True pg. 51
402
If more distance is required between apparatus in the eductor use 2-1/2" hose and a ________ ________.
gated wye pg. 51
403
Maximum distance between eductor and nozzle is: 75 PSI nozzle the max distance is __________. 100 PSI nozzle the max distance is ________.
250' 150' pg. 51
404
The nozzle setting shall match the rate of flow of the eductor (125 GPM). The nozzle bale must be ___________ ____________ at all times.
fully opened pg. 51
405
The foam eductor requires an inlet pressure of _______ PSI. Nozzle pressure will not be excessive due to the friction loss that occurs within the foam eductor.
200 pg. 51
406
Foam concentrate will educt at lower PDP. For this reason it is possible to produce finished foam at lower PDP. however this creates ________ problems.
two pg. 51
407
Foam concentrate will educt at lower PDP. The GPM at this lower PDP may be far less than the 125 GPM selected. True or false?
True pg. 51
408
At less than 200 PSI the eductor will draw MORE foam than the eductor setting resulting in richer foam solution. You will use more foam and run out quicker. True or false?
True pg. 51
409
The proper water:foam ratio cannot be achieved unless the inlet pressure is ______ PSI.
200 pg. 51
410
Angus 240 GPM eductors in aerating nozzles are for use with ________ hose and carried by: ENGINES 1, 7, 11, 21, 30, 32, 34, 37
2-1/2 pg. 51
411
Caution: The maximum Inlet pressure for the Angus 240 eductor is 120 PSI. If the inlet pressure exceeds 120 PSI this eductor will not draw foam concentrate. True or false?
True pg. 51
412
The Hazmat teams and Station 37 carry several large caliber master stream appliances for foam and dry chemicals. True or false?
True pg. 52
413
Used w/ 2-1/2" hose and the 2-1/2" Akron Turbojet nozzle, allows up to 300' between eductor and nozzle. True or false?
True pg. 52
414
JFRD maintains emergency stockpiles of foam at ______ and __________________ The total JFRD foam capacity is approximately 20,000 gallons
TSF, Station 37 pg. 52
415
The shelf life of class A foam is indefinite. It is provided and square pails to avoid confusion with class B foams. True or false?
True pg. 52
416
Class B foam concentrate is supplied in five gallon round pails. It is considered a hazardous material to the environment and requires care when handling. True or false?
True pg. 52
417
AR-AFFF Specifications (4)
* Compatible with dry chemicals. * Ansulite AR-AFFF is yellow in color; Thunderstorm AR-AFFF is green. * Cannot be used for subsurface injection. * Can be used with fresh or salt water.
418
AFFF concentrate will store for many years without issue. True or false?
True pg. 52
419
The following ground ladders shall be carried by all engine companies: 24ft Extension Ladder (3)
* First Story Roof Access * Second Story Window Access * Second Story Balcony Access pg. 53
420
The following ground ladders shall be carried by all engine companies: 14ft Roof Ladder (3)
* First Floor Roof Access * Interior Access (tall ceilings) * Roof Work with Hooks Deployed pg. 53
421
The following ground ladders shall be carried by all engine companies: 10ft Attic Ladder (3)
* Interior Scuttle Access * Interior Attic Access * Some First Story Windows pg. 53
422
The following ground ladders shall be carried by all engine companies: Little Giant (1)
• This versatile ladder can be arranged as a wall ladder, extension ladder, or an A-frame. It is carried by some engine companies. pg. 53
423
The following extrication equipment shall be carried but all engine companies: 8)
* High-lift jack w/ lifting hook * Air chisel and 3 blades (long flat, short flat, panel) * Come-A-Long * Chains in length of 6 ft, 12 ft, 15 ft, * J Hook w/shackle * Ladder cribbing minimum of on * Step chocks (minimum of 3) * Ladder cribbing (minimum of 1) * Assortment of 4x4 cribbing pg. 54
423
The following extrication equipment shall be carried but all engine companies: 8)
* High-lift jack w/ lifting hook * Air chisel and 3 blades (long flat, short flat, panel) * Come-A-Long * Chains in length of 6 ft, 12 ft, 15 ft, * J Hook w/shackle * Ladder cribbing minimum of on * Step chocks (minimum of 3) * Ladder cribbing (minimum of 1) * Assortment of 4x4 cribbing pg. 54
424
Some engines are equipped with battery powered hydraulic tools that have no power unit, no hoses, and require no set-up time. True or false?
True pg. 54
425
These tools have a int. hydraulic pump which can operate in hostile environ. where gas pwr unit might fail and provides more cutting/spreading force and conventionally in it. True or false?
True pg. 54