EDG Controls and Protections Flashcards

1
Q

EDG Trips

3
5**Defeated by Trips Defeat Switch

A
  • Manual
    * Trips Fuel Racks
  • Over-speed: 1040 RPM
    * Trips fuel racks
  • 10 Second Over-Crank: Less than 200RPM in 10 seconds (From LSR)
    * Shuts the Air Start Valves
    * EDG will only try to auto-start once, EDG will have to be locally started after problem corrected.
  • Start Failure **: Less than 200RPM in 10 seconds (From LSR)
    * Energizes the Governor S/D solenoid which will set the fuel racks to 0 (close)

-Engine Running Trips :
* Enabled 20 seconds after start by ERR
*Energizes the Governor S/D solenoid which will set the fuel racks to 0 (close)
A) High Crankcase Pressure
- +0.5” H2O
B) Low Lube Oil Pressure- 18psig
C) Low Jacket Water Pressure
- 9psig
D) High Jacket Water Temperature**- 205F

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

Generator Trips: (Opens the output breaker)

A
  • Reverse Power: Prevents motorizing the generator and possibly damaging the diesel.
  • Over Power: prevents damage to the generator if there is a fault in the electrical system.
  • Over Current: Dual indication on breaker and will lock in on APP-010-A1
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

EDG Room Fire Suppression System Actuation:

A
  • If a fire suppression system for the EDG Room actuates, the following occur automatically:
    * Secures associated Room Supply and exhaust fans
    * Secures associated DFO Pump
    * Closed supply and exhaust dampers to room.

-EDG will have to be declared inoperable by ITS due to no room cooling or fuel oil available.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

LSR (Low Speed Relay)

RPM
11 actions

A
  • Energized at 200RPM
  • Performs the following actions:
    • Stops the pre-lube oil pump, standby oil pumps and oil heater.
    • Stops the standby coolant pump
    • Stops the jacket water heater.
    • Energizes the Exp tank level control so water can be added as level requires.
    • Shuts the air start valves
    • Flashes the generator field
    • Opens the service water TCV’s
    • Deactivates the 10 second timer for Start Failure/Over-Crank Trips. (TD2)
    • Energizes the RED EDG running light
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

ERR (Engine Running Relay)

RPM
4 actions

A

-Energized at 810 RPM

  • Performs the following actions:
    • Starts the EDG Room exhaust fan and supply fan.
    • Activates the 20 second timer delay for trips. (TD3)
    • Energizes the Engine Run-hour Meter
    • De-energizes the GREEN EDG stop light
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

Appendix R switches:
How many?
Normal position?
Why?

A
  • 4 total on RTGB
  • 2 for each E-Bus (Supply breakers 18B, 17B E1, and supply breakers 28b, 27B E2)
  • 2 EDG output breakers, and 2 E-Bus normal supply breakers
  • Remove control power to breaker controls at the Generator Control Panel
  • Normally in isolate on RTGB
How well did you know this?
1
Not at all
2
3
4
5
Perfectly