What are the trips of the EDG’s during normal operation?

A

“BIG C FLANGE” and Manual

  1. Bearing temperature high.
  2. Incomplete start.
  3. Generator over current.
  4. Cardox actuated.
  5. Fuel Oil extreme lower pressure.
  6. Lube oil lower pressure.
  7. Air chest pressure high.
  8. Neutral ground over current.
  9. Generator phase differential.
  10. Electric over speed.
  11. Manual.
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

What are the trips of the EDG’s during an emergency conditions?

A

“GEMI”

  1. Generator phase difference.
  2. Electrical over speed (110%).
  3. Manual push buttons in the CR and the EDG room.
  4. Incomplete start.
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

What is the Tech. Spec. minimum level for the EDG Fuel oil day tank?

A

.101.4gal indicated = 70gal usable. This gives the diesel enough fuel to start and power the electric fuel pumps to start supplying the diesel.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

What is the Tech. Spec. minimum level for the EDG Fuel oil storage tank?

A

.46,000gal. This gives one diesel enough fuel to run for 7 days at full load.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

When is the Worthington stop control knob available?

A

Only on loss of DC.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

What is the purpose of the EDG’s?

A

To supply an independent automatic emergency source of power to safeguard busses if normal and reserve power is lost.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

What happens if you have the EDG’s in standby and you suffer a load shed followed by an SI?

A

A load shed occurs.
EDG starts and the feeder breaker from the RCP bus to the T-bus opens.
When the EDG reaches 95% speed and 80% voltage, the EDG output breaker closes.
The load shed clears and loads sequence on: CCW,
ESW, Motor Driven Aux Feed Pump, and NESW

SI occurs
Load conservation occurs (pumps already started trip)
ECCS pumps start: CCPs, SI, RHR as well as CCW, ESW, AFW, NESW
If a Containment spray signal exists the NESW pp. would trip and the CTS pp. would start.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

What happens if you have the EDG’s in standby and you suffer a loss of power to the safety buses?

A

A load shed occurs.
EDG starts and the feeder breaker from the RCP bus to the T-bus opens.
When the EDG reaches 95% speed and 80% voltage, the EDG output breaker closes.
The load shed clears and loads sequence on: CCW, ESW, Motor Driven Aux Feed Pump, and NESW.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

How quickly does an EDG come up to speed and voltage during an emergency?

A

10sec.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

When is the Worthington start control knob available?

A

Anytime.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

When is the mechanical over speed trip available?

A

Only on loss of DC.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

What does ESW do for the EDG’s?

A

First cools the Air after coolers then the water flows through the lube oil coolers, then the water flows through the jacket water coolers.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

What is the locations of the EDG fuel oil storage tanks?

A

CD north east of the unit 1 track bay.

AB south of unit 2 track bay.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

What is the output of a EDG?

A

3500kw AC.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

What are the auto starts of the EDG’s?

A

Load shed.

SI.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

If you are running a EDG loaded to the buss for a surveillance, what happens if you receive a SI signal?

A

The output breaker for the EDG trips open.

17
Q

How can you stop an EDG if you suffer a loss of DC power?

A
  1. Manual pull button on Worthington control module.

2. Mechanical over speed (112%).

18
Q

With the EDG modified for Appendix R what trips are available?

A
  1. Manual pull button on Worthington control module.

2. Mechanical over speed (112%).

19
Q

Why do we blow down the petcocks on the EDG before we run it?

A

To remove any oil or water that has collected in the cylinders.

20
Q

What is the minimum Tech. Spec. level for the EDG lube oil tank?

A

500gal. standby.

300gal. running.