EDGS Flashcards
(24 cards)
What are the EDG Trips available Without DC Power?
- Mechanical Overspeed (112% of 514 RPMs)
- Worthington/Manual Fuel Valve (MFV)
What are the only EDG TRIPS available after the EDG Auto Starts on an SI or Load Shed? (With 250 VDC Available)
- Gen Phase Differential
- Electronic Overspeed (110%)
- Manual Push Button
What are the EDG Starts?
- CR Control Switch
- Local Push Button
- Load Shed (loads to bus)
- SI (does not load to bus)
- Worthington/Manual Starting Air Valve (allows start during loss of 250VDC control power)
How do the starting air valves fail on a loss of 100# ctrl air?
Fail as is
What happens on a failure of the electronic governor?
EDG will speed up until Mechanical Governor takes over
set point for mech governor is 60.8-61 hz
Where does the field flash come from on a fast speed start?
From the 1kV inverter
Where does the field flash come from on a slow speed start?
From residual magnetism
From 1kV loads IF button is used to flash the field
What are the 1KV inverter Loads?
- Field Flash (Fast Start) (Slow Start if button is pushed)
- Bearing Temp Monitor (SG-40)
- Speed Transmitters
- Local/Remote Control Transfer Relays
How long does the Throttle Control Cylinder (TCC) extend for on a EDG Trip and why?
TCC will extend for 2 minutes on trip to prevent re-start of EDG
Will a EDG start with a loss of 100 psi Ctrl Air?
NO!
TCC extends on loss of 100 psi control air
it will trip if running, also
What causes Load Shed to be disabled?
EDG output breaker control switch is in close or lockout
When do run relays energize to allow power to bus?
At 95% running speed
start aux equip, input to load cons and provide interlocks/permissives
If an emergency start signal initiates at any time during the slow start, what will happen?
The slow start circuit automatically drops out and an emergency start takes place (Fast Speed)
Are the EDG trip relays energize or de-energize to trip?
Energize to Trip
Are the EDG start relays energize or de-energize to run?
De-Energize to run
(1 per bus – want to run if lost power)
Why is the EDG considered Inop during a surveillance?
Because the Load Shed signal is deactivated
How is ctrl air designed to fail on a loss of 250V DC?
so that control air will be available to the TCC
What is the auto trip available with a loss of 250V DC?
Mechanical Overspeed
(112% of 514 rpms)
What supplies power to the EDG 1Kv inverter
250v DC Charger/Battery (Train Specific)
What loads sequence on during a load shed WITH a SI?
CCP
SI pump
RHR pump
CCW pump
ESW pump
MDAFW pump
CTS pump (Starts when Phase B active)
NESW pump (Starts/Then Trips if CTS/Phase B active)
Will the loss of HVAC make the EDG INOPERABLE?
YES
What ventilation is required by TS LCO 3.8.1 for an EDG to be OPERABLE?
Supply Fan, Exhaust Fan and Cabinet Fan
When is the field flash disabled during a fast speed start?
80% Speed
What happens to an EDG in standby if a CO2 discharge occurs in the EDG CD room?
The CO2 actuation signal trips the 87X relay. It must be reset or the EDG will not start when needed