Elevators June 2024 Flashcards
(176 cards)
When accessing an Elevator machine room, where should the ABC type fire extinguisher located?
8.6.1.6.5
Shall be located convenient to the access door.
What is the max relief valve setting on Group 2 hydraulic elevator?
Title 8 3068 (1) (b)
125%
When a power loss to building occurs, How long should emergency lights stay on?
2.14.7.13
4hours
Minimum illumination at corridor at the entrance sill on group 2, group 3, and group 4 elevators
10fc
An elevator designated as a medical emergency elevator should have the international symbol known as the Star of life, how many symbols are to be posted on each floor or attached to the hoistway door frame?
2
VRC enclosure/pit needs to reject what size ball?
2” inches
An inspector enters the building to inspect a bank of elevators after checking in with the building complex person, the inspector may expect to find the keys for the elevator machine room where?
Title 8 3011 (D)
Shall be kept in the elevator pit of the elevator with the lowest identification state number
An elevator inspector found a group 2 electric elevator machine room temp extremely hot in the summertime the inspector will most likely write
104 temp
What is the max capacity of on a LULA elevator?
1400lbs
Max speed allowed on a LULA elevator?
30fpm
What is the max rise of a LULA?
25ft
What is the governor trip speed of a LULA?
75fpm
What is the platform area of a LULA?
18 sq ft
What is the minimum and maximum tripping speed for an overspeed valve?
110% - 140 %
What is the minimum and maximum speed for the safety bulkhead?
5fpm/15fpm
Protrusions or setbacks in hoistway shall not exceed what?
2” inches
When alteration info is required on data plate & shall be placed in the elevator machine room to specify the ________ in effect at the time & alteration installation?
8.6.1.5.1
Code & edition
What is the most oil to be accumulated in the pit?
5 gallons
According to California Electrical Code in conjunction with safety orders warning signs are mounted on or near the disconnecting means for multiple car jobs regardless of group or install date the warning sign reads?
WARNING Parts of this panel are not DE-ENERGIZED by this switch
Light switch control is located on?
Lock side of door
The force required to prevent closing of power Car/ hoist way doors?
30ft/lb
When the car is outside the unlocking zone? What is the max inches allowed for doors to be opened?
2.12.5.1
4 inches
What is the minimum headroom allowed under a suspended A/C in machine room?
2.7.4.1
84 inches
What groups required a 5 year load test
Groups 2,3,4