Feedwater Heating Flashcards

(9 cards)

1
Q

What happens on a rise of 4th Pt heater?

A
  1. LV4 modulates open
  2. LV24 modulates open
  3. Hi alarm
  4. LV24 full open
  5. LV5 closes
  6. LV75s close
  7. hi-hi alarm
  8. Trips HDL pump
  9. MOV22 & NRV23 from 9th stage ESS close
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

What happens to the LP heater string on a Hi-Hi lvl of the 1st or 2nd pt heater?

A

The string will isolate (MOV32 & 33 close)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

What happens when the hi-hi condition clears on the 1st and/or 2nd pt heater?

A

The isolation valves will stop where they are when the condition clears.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

What is the purpose of the min flow for the 4th pt heater?

A

Keeps the pump cool

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

What is the purpose of the LV2 in the FWH sys?

A

Control level in the 2nd pt drain tank

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

What happens as 5th pt heater level increases?

A
  1. LV5 opens
  2. LV25 opens
  3. Hi alarm
  4. LV25 full open
  5. LV6 closes
  6. Hi-Hi alarm
  7. MOV28 closes
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

What position does LV6 fail in the FWH system?

A

Fail Closed

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

What happens as 6th pt heater level increases?

A
  1. LV6 modulates open
  2. LV26 modulates open
  3. Hi alarm
  4. LV26 full open
  5. LV65 close
  6. Hi-Hi alarm
  7. MOV3 & AOV81 close
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

What is the Rule of Thumb as hi level alarm come in on FW heaters?

A

On Hi Lvl: water sources isolate
On Hi-Hi Lvl: steam sources isolate

How well did you know this?
1
Not at all
2
3
4
5
Perfectly