Final Practice Flashcards
(97 cards)
Proper ground conductors must be of a sufficient gauge to carry any _______, which may be imposed upon it.________
current, currents
Grounding protects automation systems from what four(4) potential damages?
A)operator system error
B) voltage fluctuations
C) loss of voltage
D) surges
E) short circuits
F) lighting
G) Power system harmonics
B) voltage fluctuations
D) surges
E) short circuits
F) lighting
Braided outer conductors or metal foil wrapped around 2 conductors in a signal line are called
(shields, shielding)
Instrumentation wires come in twisted pairs. One wire is black and the other is White. For DC electrical circuits, the following colour-coding designation is used for Polarity. (the majority of time!)
Match
White wires
Green wires
Black wires
- are designated to have positive polarity in DC circuits
- designated to have negative polarity in DC circuits
- are designated to be connected to ground in DC circuits (no polarity).
White wires are designated to have positive polarity in DC circuits
Green wires are designated to be connected to ground in DC circuits (no polarity).
Black wires designated to have negative polarity in DC circuits
The function of any grounding system is, therefore, to bring the voltages on all circuits within a system to the same reference or common point
A) True B) False
A) True
Multi-strand wires are the most common type of conductor in use in industry today.
A) True B) False
A) True
A Megger device is basically a small high voltage generator.
The Megger generates relatively high voltages in amounts of 1000V
A) True B) False
A) True
In general, effective grounding means:
A) The path to ground is continuous & permanent
B) be of sufficient capacity and made of aluminum
C) Any and all terminals on the ground system must be corrosion-free and tight, to avoid resistance at the terminal junctions
D) Terminated in a control room or enclosed wire way
A) The path to ground is continuous & permanent
C) Any and all terminals on the ground system must be corrosion-free and tight, to avoid resistance at the terminal junctions
The two types of coupling that exist are________and ________
(inductive, capacitive)
Usually the frame of an electrical device is a reference point, where all the circuits of the device eventually connect together
Chassis Ground (Common)
Is simply a point in a series of circuits where a common reference can be found.
System Common
common reference point where all circuits will lead to an earth-body connection.
Earth Ground
Usually caused by the double grounding of the neutral conductor in a system.
Ground Loops
Is a conductor, provided to ensure electrical continuity in any metallic non-current-carrying parts of electrical equipment
Bonding Conductor
Used to keep non-current carrying equipment equi-potential to each other
Bonding Jumper
noise introduced into circuits through conductors, and caused by switching transients
Conducted Noise
noise produced by communication radios, etc.
Radiated (Plane Wave) Noise
noice introduced into a system via electromagnetic field induction (capacitive or inductive).
Coupled Noise
Improper grounding of intrinsically safe barriers in IS applications. Depending on the application and model, some of these units shouldn’t be grounded!
A) True B) False
A) True
Instrumentation cabling and equipment is shielded to prevent accidental shock to personal.
A) True
B) False
B) False
Which of the following statements is true for a delta-connected three-phase system?
A) Phase voltage is higher than line voltage by a factor of 1.732
B) Line voltage is less than phase voltage by a factor of 1.732
C) Line voltage and phase voltage are the same
D) Line voltage is higher than phase voltage by a factor of 1.732
C) Line voltage and phase voltage are the same
A three-phase load has a phase voltage of 240V and a phase current of 18A. What is the apparent power of this load?
A) 22,449VA
B) 12,960 VA
C) 4320 VA
D) 7483 VA
B) 12,960 VA
An alternator with a line voltage of 2400V supplies a delta-connected load.The line current supplied to the load is 40A. Assuming the load is a balanced three-phase load, what is the impedance of each phase?
A) 26.4 ohms
B) 103.9 ohms
C) 34.7 ohms
D) 60 ohms
B) 103.9 ohms
Which of the following statements is true for a wye-connected three-phase system?
A) Line voltage is higher than phase voltage by a factor of 1.732
B) Phase voltage is higher than line voltage by a factor of 1.732
C) Line voltage and phase voltage are the same
D) Line voltage is less than phase voltage by a factor of 1.732
A) Line voltage is higher than phase voltage by a factor of 1.732