Final Test - Power Venters/ Draft Inducers, Ignition Systems, Oil Burners Flashcards
(16 cards)
A low limit is a normally _________ switch.
normally open
A high limit is a normally _________ switch.
normally closed
A L8124A type aquastat used for an oil hot water boiler has a low limit set at 160 degrees and the adjustable differential set at 20 degrees. At what temperature will the circulator turn on?
170 degrees
The primary voltage of an oil burner ignition transformer is ________ volts.
120 volts
A cad cell should have a resistance between ________ ohms when an oil burner is running properly.
300 to 1600 ohms
Resistance of a cad cell in darkness should be over _________ ohms.
20,000 ohms
An oil primary control with ignition which stays on through the entire βonβ cycle is called:
constant ignition
An oil primary control with ignition which turns off when flame is proven is called:
intermittent ignition
The _______ must prove there is draft with a field power venter before the main burner will light.
pressure switch
The voltage going to the power vent motor is ________ volts.
120 volts
A power venter does not shut off when the call for heat is over because it has a ________ timer.
a post-purge timer
If you use a CK-92F water heater control kit with a power venter, what is the water heater control?
24 volts AC
What is installed on the water heater gas valve to turn on the power venter on a call for hot water?
a pressure switch
If you install a draft inducer on a boiler, where does it get mounted?
on the flue/exhaust
What is the maximum flue temperature that a Tjernlund draft inducer inlet should have?
575 degrees