Fire Alarm Flashcards
(266 cards)
What is the recommended coded signal designation for a building supervisory signal from the basement?
3 - 1 tempora
10.12.2
Prior to the installation or alteration of fire alarm equipment or wiring, what governing authority must be notified?
The authority having jurisdiction
“AHJ”
10.20.2
How long must maintenance,inspection and testing records for FA system be maintained for?
Until the next test and for 1 year after.
Splices or joints in a public FA reporting system conductors shall:
be permitted in listed boxes
An auxiliary FA system which is connected through the municipal FA system to the fire service communications center shall be which of the following types?
Local energy and shunt
A FA system shall incorporate how many independent and reliable power supplies?
2
What is the maximum number of SMOKE alarms(initiating devices) that may be interconnected where the interconnecting means is SUPERVISED in dwellings?
42
Unless specifically designed and listed for the conditions, smoke detectors shall not be installed in which of the following ambient conditions?
Temperatures above 100 degrees F
How long after an initiating device activates must the alarm notification appliances begin annunciation at the protected premises
10 seconds
Smoke detectors installed in single family dwellings shall be replaced at what intervals?
10 years
How many visible notification appliances shall be located in a corridor that is 200 feet long?
3
FA wiring inside buildings including circuits and disconnecting means shall be identified by the use of which of the following?
Red covers or doors,red markings, “public fire alarm circuit” markings
In order to monitor the circuit integrity of a FA system loop, interruption due to a bad connection at a device is expected to send a trouble signal to the FA control panel. in order to assure a trouble signal is sent,two and four wire detector connections must employ which of the following in order to be considered a supervised circuit?
Duplicate terminals
The maximum number of unmonitored small alarm devices that can be interconnected is.?
12
The number of initiating devices that can be interconnected on a household fire alarm system is.?
18
A Carbon monoxide detector shall be located within 10 ft from a bedroom door.
10 ft
The maximum number of UNMONITORED small alarm devices that can be interconnected is.?
12
By code a ceiling is a level ceiling if the slope is
Equal to or less than 1 in 8
Fire alarm equipment shall be designed so that it is capable of performing at ambient temperature of a minimum of ?
32 degrees and a maximum of 120 degrees.
What is the lowest range of heat detector ?
100- degrees F
Transformers and other devices supplied from the power supply conductors supplying power to a power limited fire alarm panel. Shall be protected by an overcurrent device rated not over ?
20Amps.
When an audible notification appliance is in a sleeping area of a college dorm. They shall have a sound level of 10 db above ambient sound level and minimum output of 75db.
No Answer just statement
What is the maximum number of HEAT alarms (initiating devices) that may be interconnected where the interconnecting means is not supervised in a dwelling?
18
Which fire alarm circuit class is considered the most reliable because of its abilty to remain fully operational when a single open or ground fault?
Class A