Fire Alarm Systems Flashcards

1
Q

In an addressable system initiating devices are connected to the FACP through a line referred to as?

A

DCL (Data communication Link) or
SLC (Signalling Line Circuit)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

In an addressable system, Modules are connected to the FACP through a line referred to as a

A

DCL OR SLC

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

In a conventional fire alarm circuit, the name of the small current that flows to indicate circuit integrity under normal conditions is called?

A

Supervisory current

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

The two types of fire alarm control units are?

A

Single stage and two stage

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

Relay modules are used for the control of?

A

Ancillary devices/ circuits

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

Examples of Ancillary devices are?

A

Magnetic door holders
Fan contractors
Fire pumps

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

What is the primary purpose of a Fire alarm circuit

A

To save lives!

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

Isolation modules are used to ?

A

Isolate a portion of the SLC (signalling line circuit)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

4 conditions of a fire alarm system are?

A

Normal
Trouble
Supervisory
Alarm

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

Monitor modules are used to monitor?

A

Conventional devices/circuits

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

In a conventional fire alarm system, what is used to provide circuit supervision?

A

End of Line Resistor (EOL)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

Conventional initiating circuits end with?

A

End of line resistors (EOL)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

Conventional monitoring circuits end with?

A

End of Line Resistors (EOL)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

A conventional fire alarm system does not provide identification of the specific device that initiated the alarm. What does it identify?

A

It will provide identification of the Zone (area) the initiating device is located

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

2 types of heat detectors are?

A

Fixed and Rate of rise

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

Conventional NAC circuits end with?

A

End of Line Resistors (EOL)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
17
Q

In addressable circuits what is polarity conscious?

A

All initiating and monitoring devices

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
18
Q

A SLC (signalling line circuit) or a DCL (Data communication link doesn’t end with a ?

A

End Of Line Resistor

19
Q

Addressable NAC circuits end with a?

A

End of line resistor

20
Q

When a heat detector pull station or a smoke detector is activated in a single stage fire alarm system what will initiate?

A

Audible evacuation signal

21
Q

On a two stage fire alarm system if 5 minutes pass and the signal has not been acknowledged what happens?

A

An alarm signal will activate

22
Q

When a heat detector pull station or smoke detector is activated a two stage fire alarm system will initiate a?

A

Audible alert signal

23
Q

When wiring a SLC or DCL what terminal do you leave on!

A

The B terminals

24
Q

List 3 sprinkler tree devices and the conditions each device will initiate through the FACP?

A

Gate valve- supervisory
Low water pressure switch- supervisory
Water flow switch- ALARM

25
In an addressable system if a device address is wrong, what condition will be displayed?
Trouble
26
In a conventional fire alarm circuit what is polarity sensitive?
Smoke detectors and Notification devices
27
What can be used to de energize an ancillary device?
Addressable relay module
28
What can be used to interconnect a conventional device/ circuit to an addressable fire alarm system?
Addressable monitoring module
29
What style is a Class A system?
Style 6
30
What style is a class B system?
Style 4
31
What are the 5 classes of Fires?
Class A = ordinary combustibles Class B= Flammable liquids Class C= Electrical Class D= Combustible metals Class K= cooking fires
32
The 3 major types of fire alarm systems are?
Conventional Multiplex Addressable
33
What are some notification appliances?
Strobes, bells horns and speakers
34
What are some visual appliances?
Strobes would be the only visual
35
What are some initiating devices?
Smokes, pull stations, heat detectors
36
3 half tones a pause and then repeats is?
Temporal 3
37
Pressure switch has what kind of contacts?
N/C contacts. Uses pressure to open it
38
Flow switch uses what kind of contact!
N/O contact! When water flows it closes causing an alarm
39
What contact does the gate valve use?
N/C held open contact, when closed it sends a supervisory alarm to the FACP
40
What are NAC circuits?
Notification Appliance circuits (Audible or Visual)
41
What are the color codes of resistors?
BBROYGBVGW GS and nothing Black 0 Brown 1 Red 2 Orange 3 Yellow 4 Green 5 Blue 6 Violet 7 Grey 8 White 9 Gold +/- 5% Silver +/- 10% No color = +/- 20%
42
What are two types of basic smoke detectors?
Photoelectric and ionization
43
Automatic devices are?
Heat and smoke detectors and The flow switch on the sprinkler tree
44
What are manual devices?
Pull stations either single or two stage