Fire Protection Flashcards

(35 cards)

1
Q

What are the Fire Pump Auto Starts?

A

Motor Driven Fire Pump - 140# for ≥ 2 Sec
East Diesel FW pump - 130# for ≥ 15 secs
West Diesel FW Pump - 120# for ≥ 25 secs

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

What is the Diesel Fire Pump Trip?

A

Engine overspeed @ 2112 RPM

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

For any given fire, what are the most fire pumps you should expect to see running?

A

2 Pumps max for a Main Transformer Fire

- Electric FW Pump and East Diesel FW Pump

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

Can you parallel the two supply power sources to the fire pump house?

A

No, you cannot parallel them due to the two sources being out of phase

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

Which unit can manually open ZMO-10 and ZMO-20?

A

Either unit has the ability to open ZMO-10 and ZMO-20

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

Which unit is required to manually close ZMO-10 and ZMO-20?

A

Both units are required to close ZMO-10/20 after them being open

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

Which fans will trip on high temp (400°F) on thermistor string?

A

AFX
CPR
CIPX
TSC Filtration Unit

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

At what temp does the pre-alarm for the fans with the charcoal bed come in?

A

150°F-220°F

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

Which fans have charcoal filter fire water protection?

A
AFX - Spent Fuel Exhaust
CPR - Containment Pressure Relief
CIPX - Instrument Room Purge Exhaust
TSC Filtration 
AES - Engineered Safety Features
ACRF/CRP - Control Room Pressurization
SATFU - SAT Room
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

ZMO-10/20 will auto open upon receipt of any of the following fire signals from these areas

A
  • Drumming area
  • New fuel receiving area
  • Any charcoal filter supplied by fire water system
  • Push button for Auxiliary building hose reels
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

Will general aux building elevation area fire detectors open ZMO-10/20?

A

No they will not open ZMO-10/20. They just send an alarm.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

What area do each of the CO2 Tanks Protect?

A
71/2 Ton - Old Office Building and Generator Degas
17 Ton Areas:
- 4KV Room
- EDG Rooms
- EDG Fuel Oil Pump Room
- Aux Cable Vault
- CRCV
- Switchgear room cable vault
- Quads 1-4
- MT Lube Oil Tank Rooms
- Lube Oil Tank Rooms
- CRD room
- Hose Reels
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

How does the CO2 Master Valve fail on loss of 250V DC?

A

Fails open (Pilot denergizes)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

How does the CO2 Pilot Valve fail on loss of 250V DC?

A

Fails open

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

How does the CO2 Master Valve fail on loss of pilot pressure?

A

Fails closed

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

With a fire in the U2 CRCV, what automatically actuates for fire protection?

A

Halon and Fire Water Sprinkler

17
Q

With a fire in the U1 CRCV, what automatically actuates for fire protection?

18
Q

What must you manually actuate for a CRCV fire to both units?

19
Q

Is Turbine lagging fire protection automatic?

A

No, fire has to be locally verified and manually actuated from control room (ZRV-40/41)

20
Q

If Halon is actuated at the cylinder manually, will the extended Halon bottles actuate?

A

No, they will not

21
Q

What is the purpose of the INDIVIDUAL ISOLATION SWITCH?

A

Prevents all auto actuations of CO2 to a protected area

22
Q

What happens on a temp Pre-alarm in the charcoal bed?

A

CR gets an alarm and procedure directs opening of FP Isolation vlv

23
Q

How does the CO2 Selector Valve fail on loss of power?

24
Q

What is the capacity and of the pegging pump and at what pressure does it keep the header

A

50 GPM

150 psi

25
How long do the charcoal filter deluge valves actuate for
They ever cycle 20-30 seconds
26
What do the CO2 Master Valves do
Sends CO2 to various area selector valves
27
What do the CO2 Pilot Valves do
Provide pilot pressure to the master valves on CO2 system activation
28
Are CO2 Pilot Valves normally energized or de-energized
Energized
29
What do CO2 Selector Valves do
Admit CO2 to its area on a fire signal
30
Are CO2 Selector Valves normally energized or de-energized
Normally de-energized
31
What are actuation methods for Halon
Automatic Manual-Electric (Control Room pushbutton) Manual - At Automan (Pull Pin-Push button) Manual - At Halon Cylinders (Pneumatic Actuator)
32
How many extended Halon discharge cylinders are there
Three
33
How long after the main Halon discharge do the extended Halon discharge cylinders actuate
3 minutes 45 seconds
34
How long does the main Halon discharge last
45 seconds
35
How long does extended Halon discharge last
4 minutes