General Questions Flashcards

(42 cards)

1
Q

Dwelling services are sized at what %

A

83%

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

Non-coincidental loads are sized at what percent of highest load

A

125%

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

Feeders less than or equal to 100 amps use what column

A

60 degree C

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

Capacitors are rated for what percent of total amps

A

135%

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

How many feet of show window requires it’s own recept

A

12 ft

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

How many feet above sidewalk must service entrances conductors be

A

10 feet

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

What is the minimum disconnect size for a commercial building

A

60 amps

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

What size grounding electrode conductor must be protected from physical damage

A

6 or smaller

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

Minimum ground rod diameter

A

5/8”

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

Minimum ground rod spacing

A

6’

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

Minimum ground ring wire size

A

2

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

When sizing a disconnect, you must round down if the amperage is below

A

800 amps

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

Elementary schools require what type of recept

A

Tamper Proof

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

Car wash recepts are what type of location

A

Wet location

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

Minimum light pole hand hole size

A

2”x4”

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

General use snap switches at good for what percent of its rated use?

A

80%

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
17
Q

What is the maximum surface temperature of T2A

18
Q

In hospital general care areas, each bed location needs how many recepts

19
Q

In hospital critical care areas, each bed location needs how many recepts

20
Q

How many inches must separate class 1 and class 2/3 circuits

21
Q

What is the smallest size conductor that can be run in parallel

22
Q

Wire for services is sized using what temp column

23
Q

What percent of FLA must motor conductors be sized for?

24
Q

What percent of motor FLA must a disconnect be sized for?

25
For taps between 10’ and 25’, each motor feed must be able to carry what percent of the load
1/3
26
How many watts per HP
746
27
How big is a straight through junction box
Largest Pipe size x 8
28
How big is a angle pull junction box?
Largest pipe x 6 + all other pipes
29
What is the voltage drop formula to find circ mils
(2KIL)/((VD%)(v))
30
What do you multiply voltage by for all 3 phase equations
Square root of 3
31
How do you find single phase neutral amps
Amp difference between 2 legs
32
How do you find 3 phase neutral amps
Total amps / 2
33
Motor overcurrent protection table
430.52
34
How far under waterline must a wet niche fixture be?
18”
35
Conduit to wet niche fixtures must be corrosion resistant and made of
Rigid brass
36
Electrical wires going over a pool must be how high
22.5’
37
Fixed metal parts within 5’ of pool must be
Bonded
38
Minimum distance from the edge of stud to a cable in wall
1 1/4”
39
At what voltage does direct burial cable have to be shielded
2000 volts
40
Minimum space between recessed light fixture and insulation
3 in
41
Conductors supplying several motors shah be rated for
The sum of all motors plus 25% of largest
42
You must use mc or conduit if occupancy is over
100 people