GTGs Flashcards

(7 cards)

1
Q

GTG Rating

A

3000 KW at 450 VAC, 4800 Amps, 60 Hz, 3 phase, 0.8 power factor

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

ZEDS

A

Zonal Electrical Distribution System

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

Electrical distribution system components

A
  • 3 GTGs
  • 3 Switchboards
  • 23 Load Centers
  • 10 Lighting Load Centers (LTG LCs)
  • Power Panels (PPs)
  • Power Distribution Boxes (PDBs)
  • Manual or Auto. Bus Transfer (MBT/ABT), and Static Automatic Bus Transfer units (SABT)
  • Lighting Distribution Panels
  • Lightin Distribution Boxes
  • Power and lighting Transformers
  • Casualty Power distribution system
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

ZEDS

Zones

A

1-5 Fwd –> Aft
6 –> 01 level up

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

Start Permissives for the GTG

A
  1. Cooling fan running or in auto
  2. RPM <600 for Bleed Air starts
  3. RPM <1215 for RIMSS start
  4. No shutdowns active or illuminated
  5. Not in Input/Output (I/O) mode
  6. Not motoring
  7. Hard Wire Fuel Trip (HWFT) off
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

Lubrication oil for the GTG

A

23699

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

Stages that Bleed Air is extracted from

A

5th, 10th, and 14th
5 &10: Are open to the atmosphere during start to prevent stalling of the compressor
14: Vented to the atmosphere using diffuser valves
- Primary source of bleed air for the ship

How well did you know this?
1
Not at all
2
3
4
5
Perfectly