HVAC Flashcards

(61 cards)

1
Q

What are the five parts of the HVAC system?

A

motors, ducts, fans, controls, and heat exchange units

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

Purpose of the HVAC system is to add or remove __ and __ to order to maintain the desired environmental conditions

A

heat and moisture

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

Summer

A

Cooling system is used to remove heat from air
this is usually accompanied by removing moisture
sources of cooling: Chiller, packaged unit or heat pump

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

Winter

A

heating system is used to add heat to the air
this is usually accompanied by adding moisture
sources of heat; gas fired heater, boiler or heat pump

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

Most cooling equipment uses a vapor compression cycle and phase changes to transfer heat
chillers, package units, split-units, fridges, freezers, etc.

A

Vapor Compression Cycle

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

What are the four main components of the vapor compression cycle?

A

Compressor, condenser, expansion valve, evaporator

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

Vapor Compression cycle __ the pressure and the temperature of refrigerant as it goes around the cycle

A

raises

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

A ton is a measure of power

A

One ton of air conditioning = 12,000 Btu/hr

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

A ton-hour is a measure of energy

A

One ton-hour of air conditioning = 12,000 Btu

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

12,000 Btu/hour is the power needed to melt __ __ of ice

A

one tone

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

Applies to both heating and cooling
= Energy moved
Energy input

= Power heat flow
Power input

The most important parameter to be measured
As the temperature changes, so does this

A

Coefficient of Performance (COP) =

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q
Cooling equipment performance
= Btu/hr of output / W of electric input 
= COP * 3.412Btu/ Wh
= EER / 3.412
Btu
Wh
A

EER

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

kWin/ ton = 12/ EER = 3.517/COP

A

Coefficients for determining equipment performance

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

predicts chiller efficiency at the Air Conditioning Refrigeration Institute’s (ARI) Standard Rating Point.
(AHU) and (FCU)

A

Integrated Part Load Value

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

A typical __ system sends __ water through a tall building to transfer cooling and then the air handler changes water to air to cool each space

A

chiller

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

__ __ works to evaporate water into the atmosphere

Each pound of liquid evaporated will send 1,000 Btu of heat to the atmosphere

A

Cooling Towers

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
17
Q

Uses heat instead of electric power to drive a refrigeration cycle
can use waste heat but high maintenance

A

Absorption Chiller

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
18
Q

Oil free variable speed compressor that can be installed as a retrofit to an existing chiller

A

magnetic bearing centrifugal chillers

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
19
Q

Chilled/ hot water is circulated in the coil of the AHU, where a fan blows air to the duct system
allows control of the mix of fresh air and return air

A

ducted distribution systems

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
20
Q

supplies at the same volume and temperature to the entire zone.

A

single zone systems

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
21
Q

can be at different different temperatures OR flow rates

air is mixed and conditions within the machanical room adn then ducted to each zone

not used today

A

multizone systems

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
22
Q

supplies both hot and cold air in separate ducts which are blended at the point of use to provide required conditions
inefficient and expensive

A

Dual duct systems

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
23
Q

air is cooled to the lowest required temperature

temp is controlled by reheat coil

A
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
24
Q

temperature is controlled by controlling the volume of air that is discharged into the space
energy efficient and widely used today

A

VAV system variable air

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
25
small localized air handler unit which serves a single space a fan in the unit draws room air and blows it across a coil of hot water or chilled water and back into the room
fan coil systems
26
ventilation requirements reduce carbon dioxide concentration so that it doesn't exceed ___ ppm
1,000
27
whenever the outside air is cooler than the cooling set point temperature only distribution energy is required to provide cooling with outside air return damper is closed 100% so that al return is exhausted and 100% air introduced without cooling happens in thermally heavy buildings where internal loads are high
economizer cycle
28
precondition the outdoor make up air with the exhaust air | less inefficient
Energy Recovery ventilators
29
recover heat from ~200 degree hot refrigerant gas exiting the compressor domestic cole water (50-60 degrees) can be heated to 140-160 degrees) Heat available to recover is about 2,500 Btu/h (per ton capacity of an air to air heat pump or cooled air chiller)
HRU - DeSuperheater
30
Used in CRF and Chilled Beam applications and some VAV types treats outdoor air to meet ventilation requirements sized to handle the latent loads generally include heat recovery wheels with latent capacity
DOAS
31
simultaneous cooling and heating - basically exchange heat from one room to another. Multiple units used to expand capacity - condensing units are controlled by at VFD. Evaporators vary on style and locations
VRF
32
signficantly reduces fan energy and cooling costs. chilled water clws through the coil and air around the coil is cooled and falls into the room
chilled beams
33
chilled water supply mounted in box. Chilled water supply should be above room dewpoint. Requires a separate air supple that takes care of ventilation and latent requirements
passive chilled beam
34
compared to traditional VAV, uses reduced amount of pre-treated supply air and then further conditions the air within the occupant space
active chilled beams
35
the energy required to change the temperature of a substance with no phase change for air it refers to changing the temperature without changing the moisture content
sensible heat
36
the energy required to change the phase of a substance | for air, it refers to the energy required from the change of moisture content
latent heat
37
enthalpy
combination of sensible and latent heat
38
q = m*Cp*DeltaT q = CFM * .075lb/ft^3 * 60 min/hour * .24 Btu/lb Degree * Change in temperature q = CFM * 1.08 * deltaT
Air sensible heat transfer equation
39
ft^3/minute
CFM
40
M =
overall mass flow rate of air
41
Cp
the specific heat (0.24 Btu / lb Degree) for air
42
q = m*Cp*delta T = GPM * 500 * change in temperature = GPM * 8.34lb/gallon * 60 min/ hour * 1Btu/1lb Degree Fahrenheit
water heat sensible heat transfer equation
43
``` q = m*delta h q = CFM * .075lb/ft^3 * 60min/hour * change in enthalpy q = CFM * 4.5 * change in enthalpy ```
Air sensible and latest heat transfer equation
44
change temperature without adding moisture (humidity ratio remains constant)
Sensible heating and cooling
45
increase temperature with addition of moisture to maintain desired relative humidity
heating and humidification
46
decrease temperature with with reduction of moisture through condensation (humidity ratio decreases)
cooling and dehumidification
47
Reduce temperature by evaporating into some water, usually effective in hot and dry conditions (humidity ratio increases)
Evaporative Cooling
48
momentum or resistance to change A property of the mass of a building which enables it to store heat, providing "intertia" against temperature fluctuations
Thermal Mass
49
buildings interior conditions respond quickly to weather vs interior conditions respond slowly to weather
thermally light buildings vs thermally heavy buildings
50
infiltration/ventilation conduction solar gain internal loads
Heat Gain
51
infiltration/ventilation | conduction
heat loss
52
heat is ___ through the building envelope. is the inverse of resistance heat lost/gain through __ depends on: exposed surface area, temperature difference, wall/roof/window construction imagine standing inside and walking through the walk q = area* change in temp sum of R-values of different materials
heat condution
53
= L/K or = L/C
R = Conductivity "k" L = thickness in inches k Units = Btu * in / hr * ft^2 * F Conductance "C" C = conductance
54
on exposed surfaces | we also have to account for the convection that occurs on the material surface
heat convection
55
U Value for heat transfer
U-Value | U = 1 / Sum of R values
56
Heat flow equation
q = U * A * Change in Temp UA is the value of. the product and is often referred to as the Building Load Coefficient
57
an approximation for geographic weather Used to predict the amount of heating and cooling needed average building has desired temp of 70 degrees 5 degrees is supplied by internal heat **common base for computing degree days is 65 degrees fahrenheit
Degree Days
58
Q = 24U * A * DD energy __ loss through the envelope to get fuel consumption divide by COP or the heating systems efficiency
Seasonal (heat or cool) energy losses through the envelope
59
``` __ __ __ Impacts depends on a number of factors: solar radiation intensity time of day orientation availability of shading type of glass ```
Solar heat gain
60
the ratio of transmitted solar radiation to incident solar radiation less is better
solar heat gain coefficient
61
__ __ needs high solar reflectance and thermal emissivity | the higher the solar reflectance, the __ the surface
Cool roofs | cooler