1

What is Approach Temperature?

Delta T between evaporator coil temp and chiller water leaving temperature

2

What is the purpose of an Expansion Tank?

Located above boiler to give space for air initially trapped in system and for expanded water when heated

3

What type of pump is used for a circulator?

Centrifugal Pumps

4

What are the advantages of a HEPA Filter?

Very high-eff (0.3um and lower), remove 99.99%

5

How is a Purge Unit connected to a system?

It is connected to the top of the condenser to collect and remove the air

6

What is Ventilation?

Process of supplying and removing air by natural or mechanical means to and from a space

7

Where is a Balancing Valve installed on a heating terminal unit?

Installed on the return side of each heating unit

8

What are the types of Cooling Tower Air Flow?

Cross-Flow (air in thru side, pulls air out thru top) and Counter-Flow (air in thru btm, up thru top)

9

What is the purpose of the Load Limiter?

To sense the motor amperage and partially close the guide vanes to limit the compressor amperage to the full-load value

10

How is capacity control done on a Rotary Screw Compressor?

Slide valve that blocks suction gas before entering. Typically by differential pressure in the system

11

What does a normal gas flame look like?

Blue with slight orange tips

12

What are the types of Fan Switches?

Temperature (in the air stream near Heat Ex) and Timer (non-adjustable)

13

What is the delta T between condenser refrig temp and ambient temp for a High Eff system?

20 degrees F

14

How does a Thermocouple work?

Two dissimilar metals welded at one end (hot junction). When heated, generates small V (15mV loaded (connected to coil) 30mV unloaded (w/o coil). Voltage travels to cold junction at gas valve

15

What is the ideal delta T between the evap refrig coil temp and the air entering the evap coil?

10-20 degrees F

16

What is the purpose of Guide Vanes?

At entrance of impeller eye to allow or reduce flow by pneumatic or electronic motors to open or close vanes. Also, guide refrig to impeller eye.

17

What is the condition of refrig entering the compressor?

Superheated Vapor

18

What should the delta T be between the condenser coil and the ambient air in a standard efficiency system?

30 degrees F

19

What conditions cause Centrifugal Compressors to surge?

Too high head pressure or evaporator pressure too low that the compressor can't overcome the pressure difference

20

Why do we use Crank Case Heaters?

To prevent refrigeration migration and to vaporize refrig that migrated to the compressor

21

Name the types of Evaporator Defrost methods:

Random or Off-Cycle, Planned (forcing comp off for short periods), Hot Gas, Electric

22

What is the purpose of a Gas Regulator?

Drops NG to usuable pressure (3.5" WC) and meters constant flow

23

Name the types of Low Ambient Head Pressure Control:

1. fan cycling using pressure control 2. fan speed control 3. air volume control using shutters and fan cycling 4. condenser flooding devices

24

Describe a flame with Primary Air Restriction:

Yellow

25

What is a Sling Psychrometer used for?

To obtain Wet-bulb and Dry-bulb temperatures

26

What are the basic furnace styles?

Horizontal, Uplow, Downflow, Low Boy, Multipoise

27

What is the minimum slope of horizontal flue pipe?

1/4" per foot

28

STUDY P/T CHARTS

Study it

29

What is the purpose of a Draft Diverter?

Prevent pilot blowout and main burner flame from being altered

30

What are the characteristics of Pictoral Drawings?

Shows location of each component as it actually appears to the person installing or servicing equipment