IP Review Flashcards
(231 cards)
What is the minimum size vent for a manhole within a building?
2 inch
What does 1 Imperial grain per gallon equal in parts per million?
14.3ppm
What is the maximum distance of a 3” trap arm before it is vented?
3.6 meters, 12 feet
Where, in relation to the flood level rim, should the critical level of a pressure vacuum breaker be installed?
300mm, 12”
2.6.2.10.(4)(a)
True or False
An air admittance valve is permitted to individually vent a bathtub provided that the vent is in an accessible location
True
Air admittance valves are permitted on individual vents and dual vents provided they are left in an accessible location
What is the minimum size air break when a 3/4” pipe drains into a 4” floor drain?
1”
Minimum 25mm or at least the NPS of what’s draining, whichever is larger
2.3.3.11.(2)
What is the maximum length of a braided flex serving a water closet?
750mm, 30”
A storm building drain has a hydraulic load of 12,000L and drains into a combined sewer which receives 261FU from the sanitary building drain. What is the total hydraulic load on the combined sewer?
14,375.5L (9.1x260=2375.1 +12000)
2.4.10.5.(1)(b)
When water testing, a water sample is found to have a Ph of 9. We consider this to be what?
Slightly alkaline
When using air to test a drainage system, you must apply how many kPa for how many minutes?
35kPa for 15 minutes
2.3.6.5.
What is the maximum change of direction between a clean out and the pipe it serves?
45 degrees
2.4.7.4.(4)
True or False
A 2” reduced pressure principal backflow preventer requires a minimum air gap of 1”
False
An air gap must be 1” minimum or twice the size of the diameter of the supply.
A 2” RP requires a 4” air gap
When may a drum trap be used as a fixture trap?
A drum trap may not be used as a fixture trap unless required to serve as an interceptor and access for servicing is provided.
2.2.3.1.
How many fixture units can drain into a 3” stack from any one story?
18FU
Which type of pump would be used for hydrostatic testing?
Positive displacement pump
Can a normally closed back water valve be installed on a basement branch of fixtures which drain into the building drain?
Yes, a normally closed backwater valve can be used on a branch or fixture drain
2.4.6.4.(2)
A building has a roof sun deck and this is the only place where the plumbing vent can go to stay nominally vertical.
How high above the sun deck must the vent terminate?
2 meters
A-2.5.6.5.(4)
On which boot should the green triangle be located?
Right boot
What must be done to protect the surrounding suites from fire when installing a 3” cast iron pipe through a floor?
Fire caulking around the pipe
What is the minimum length a washing machine stand pipe?
600mm
What does piping and pickup refer to in hydronic heating?
The difference between gross output rating and net rating
When installing a solar hot water heating system, which direction should the panels be placed in order to receive optimal sunlight?
South
When must a wet vent stay full size to outside air?
When there is a wet vent stack over 4 storeys high
An air conditioner produces a semi-continuous flow of 2.5L/s and drains into a storm sewer.
What is its hydraulic load on the storm sewer?
What would be its hydraulic load if it drained into a sanitary building drain?
What size trap would this load require?
The hydraulic load on the storm sewer would be 2250L (900L for each L/s of flow)
2.4.10.3.(2)
The load on a sanitary building drain would be 79.25FU
2.4.10.3.(1)
This load would require a 4” trap