JM Electrician Flashcards

(65 cards)

1
Q

Max Distance between straps for a straight 1” rigid conduit run is? (RMC/GRC)

A

Table 344.30 (B)(2)

12 FEET

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

NM cable is “not Permitted” in concrete.

A

334.12 (A)(9)

True

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

What is the classification for a receipt. 16”AFF in a garage?

A

511.3(A)

Unclassified

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

Define Motor Controller.

A

430.2-controller

Make and break current only

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

What is the max. Resistance of Rod and Plate Electrodes?

A

250.56

25 OHMS

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

Type UF cable “cannot” be used as a…

A

340.12(1)

Service Entrance Cable

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

Where is a disconnect prohibited?

A

230.70(A)(2)

Bathrooms

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

How deep must a 30A Type UF cable used for landscape lighting at a residence be buried?

A

Table 300.5

6 inches

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

Overhead conductor clearance for swimming pools is?

A

Table 680.8

22 1/2 feet

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

What is the min. size wire you can use for parallel feeders?

A

310.4

1/0 awg

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

Wet-Niche underwater luminare forming shells in contact w/pool water must be?

A

680.23(B)(1)

Brass or other approved corrosion resistant metal.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

What is required for taps made on direct burial cables?

A

110.14(B) or 300.5(C)

listed means

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

The use of a ladder to access or remove without damaging the building is considered to be…..

A

100 definitions

Accessible

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

What size schedule 40 PVC is required for 5 conductors that have across sect. area of 3 1/2?

A

Chap. 9 Table 4

3 1/2 inches

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

How far must your cable be installed from the edge of a stud to be protected from damage?

A

300.4(D)

1 1/4 inches

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

How far must you strap a cable leaving a box w/ breakers and conduit seals?

A

501.15(A)(1)

18 inches

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
17
Q

In walls w/ combustible material, the box must be?

A

312.3

Flush w/ the wall or project there from

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
18
Q

How many switched receipts. are required in a storage area?

A

210.70(A)(3)

1

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
19
Q

If there is more than one service disconnect on the same property….

A

225.33(A)
They must be grounded together.
No more than 6 disconnects

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
20
Q

NM cable is permitted in a unfinished basement!

A

334.15(C)

True

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
21
Q

What is the min. depth of wiring space if you are servicing 277V circuit w/ exposed live parts on both sides?

A

Table 110.26(A)(1)

4 feet

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
22
Q

What receipt. rating are you allowed on a 20A circuit breaker?

A

Table 210.21(B)(3)

15 and 20 Amp recepts.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
23
Q

What is the minimum bend radius for NM cable w/a radius of 1/4”?

A

334.24
(.25x5=1.25)
1 1/4 inch
- The bending radius shall not be less than 5x the diameter of the cable.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
24
Q

How many type TW #14 wires can you put in 3/8” FMC w/ the fitting on inside of conduit?

A

348.22 / Table 348.22

2

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
25
Devices mounted on finished surfaces that are flammable(wood) shall be...
314.20 | mounted flush with or project there from
26
Over current protection “shall not” be required for conductors from a battery rated less than _____ volts if the battery provides power for starting, ignition, or control of prime movers.
48 volts
27
Boxes at ceiling-suspended fan outlets “can not”support more than….
35 lbs | unless they are listed for and marked w/ the max weight to be supported.
28
3 phase Y transformer?
0
29
Elect. equipt. w/ exposed parts on one side requires a working distance of?
3 feet
30
A JW encounters a sub-panel fed w/ type SE cable. What must he do?
Make sure all grounded and ungrounded conductors have insulation
31
The code recognizes 2 conditions for the derating of conductors, it is the combo of these that ultimately determines the amount a conductor can be derated.
1. Ambient temp. | 2. # of conductors in a conduit
32
Is it permitted to use steel pipe and alum. fittings and also alum. RMC w/ steel fittings where not subject to corrosive influences?
YES
33
An NM cable is installed in an air duct, is this allowed?
NO!
34
What is the max distance you can run #12 w/ a load of 8amps?
150 feet
35
What size NM cable for 240V, 15,000VA?
#4
36
In a crawl space where there is no storage area or equipment, do you need to install a switch or receipt.?
NO!
37
The reason for parallel feeders is to?
Reduce inductive heat
38
Why must there be ventilation in a room where you store batteries?
To prevent an explosive air/gas mixture
39
Which method is approved for the bonding of a clothes dryer?
None of the above
40
When there is more than 1 ground rod, how far must the second be placed?
6 feet
41
What is the max. number of switches that may be used as the disconnecting means for a feeder?
6
42
Service mast as supports must be...
225.17 or 230.28 | ADEQUATE STRENGTH or be supported by braces or guys to safely withstand the strain imposed on it.
43
Parallel feeders must have...
``` 310.4 (1-5) Must be terminated in the same manner/ Same size/ Same Material/ Insulation type/ Length ```
44
The min. headroom required for switchboards is?
110.26(E) | 6 1/2 feet
45
Are GFI receipts. required in bathrooms and attached garages?
210.8(A)(1-8) YES Bathrooms, Garages, outdoors, crawlspaces, unfinished basements, kitchen, boathouse, laundry/ utility/ wet bar
46
Why must you install conduit in a continuous manner?
300.10 | Far a safe continuity path back to the service.
47
Electrical Signs are to be...
600.3 | LISTED! and installed in conformance w/ that listing, unless otherwise approved by special permission
48
How far must you strap NM cable from an NM box?
334.30 | 12 inches
49
What does the interrupting rating of a circuit breaker protect?
100 definitions | Max current/amps of conductor
50
The two main safety concerns in a hospital in a power outage are...
517.33 | Illumination and telephone Equipt. rm
51
What is the min. ampacity for a 3 phase, 23v, 15hp inductive type motor?
Table 430.250 | 42 Amps
52
What circuit must operate in the “life safety” branch of health facilities?
Automatically operated doors used for building egress
53
How many 20 amp lighting circuits are required for a 3000 sqft residence?
5
54
What is the min. length of cord on kitchen waste disposal?
18 inches
55
Objectionable current flow...
Installed at different location
56
What is the inverse time circuit breaker required for a motor rated for 20a?
20x250%=50A
57
What is the classification for a garage w/out vents where flammable material is stored?
Class 1, Div.2
58
“Sample” A metal box w/clamps is to contain 2- 14/2 NMC w/GRD, 1- 14/3 NMC w/GRD and one receipt. what is the min. size box(in cu. in.) permitted?
``` 314.16 (B)(1.5) 7#14@2.0 cu.in.= 14 cu.in 1-clamp(#14)= 2 cu.in 2-strap(#14)= 4 cu.in 1-ground(#14)= 2 cu.in 22 cu.in ```
59
“SAMPLE” A conduit has 3 #12 thru the riffing; 2-#12 that enter and splice in the fitting; 2-#12 that leave the fitting. What is the min. cubic inch capacity that the manufacture must have marked on the fitting?
``` 314.16(C)(2) / 314.16(B)(1) table #12= 2.25 cu.in *a conductor which passes thru counts as 1. 3-#12- 3x2.25=6.75 4-#12- 4x2.55=9 6.75+9=15.75 cu.in 15.75 cu.in ```
60
“SAMPLE” What is the ampacity of 4 - 4/0 THHN copper conductors in a raceway installed thru an smb. temp. of 40*C
``` Table 310.15(B)(2)(a) 4-6 conductors 80% 4/0 230A 230x.80=184A 82% derate for 45*C 184Ax.82=150.88 150.88A ```
61
1. Abandoned Cond. & cords
NO unless approved
62
2. Smoke detectors
SHALL NOT
63
3. Show windows
18” within
64
4. Service disconnect
Inside and out of building
65
5. Clark County New
Concrete Encased