A 480/240 volt step down transformer where the primary current is 200 amperes, the approximate secondary current will be ____ amps
a) 100
b) 200
c) 300
d) 400
100 Amps —- Uglys Book pg 61
Ep x Ip = Is / Es
480 x 200 / 240 = 400
What is the secondary current of a single phase step up transformer if the primary voltage is 120 volts, the secondary voltage is 600 volts and the primary current is 10 amps?
a) 2 amps
b) 5 amps
c) 10 amps
d) 50 amps
2 amps —— Uglys book pg 61
Ep x Ip / Is = Is
120 x 10 / 600 = 2
Where the outside feeder disconnect means consists of more than one switch or circuit breaker determining the rating of the disconnecting means shall be permitted to be done by ____
a) adding all the circuit brakers and dividing by 2
b) adding the connected load and diving by 1.732
c) combining all the ratings of the switches or circuit breakers
d) calculating the load by taking the first 3000 va at 100%
combining all the ratings of the switches or circuit breakers
NEC 225.39
The inverter output of a stand alone photovoltaic system shall be permitted to supply 120-volts to a single phase, 3-wire 120/240 volt service where there are no ____ on the system.
a) motor loads
b) transformer loads
c) multiwire branch circuits
d) appliance branch circuits
multiwire branch circuits
NEC 690.10 and 710.15 (C)
Where a combination of transformer and utilization equipment are supplied by feeders over 600-volts, the conductor ampacity shall not be less than the sum of the nameplated rating of the transformers and the equipment that will be operated simultaneously at ____ percent.
a) 80
b) 100
c) 125
d) 150
125 percent
Art 215.2 (B)(2)
A 20-amp circuit breaker can be used to protect a maximum electric heating load of ____ amps
a) 10
b) 12
c) 16
d) 20
16 amps
The typical rule of thumb is to use 80% of the circuit breaker rating for continuous loads.
Art 424.3(B), electric heat is considered continuous load
Where a 15-amp circuit breaker is supplying two or more receptacles, the maximum permitted load on any one receptacle shall be _______
a) 7.5
b) 10
c) 12
d) 15
12
Art 210.21(B)(2), table 210.21(B)(2)
Maximum permitted load is 80% of overload protection
If 10 pieces of utilization equipment draw 2 amperes each and are supplied by 120 volts, the total volt amps will be _______
a) 10
b) 20
c) 2,400
d) 200
2400
VA= IxE , 2x10=20 , 20x120=2,400
Total volt amps can be calculated using the formula: Total VA = Number of devices × Amperage per device × Voltage.
To serve a 15,700 va non-continuous load, how many 120 volt 15-ampere circuits are required? The answer is _______
a) 5
b) 7
c) 9
d) 11
9
15 amp circuit = 1,800VA
15,700/1,800 = 8.72 or 9 circuits
or
15,700/120 = 130.83
130.83/15 = 8.72 0r 9
Each 15-ampere circuit can support a maximum of 1800 VA (15A × 120V).
In regards to dwelling units, all of the following areas require arc fault interrupter protection except _______
a) parlor, library, and den
b) attic, bathroom, and garage
c) sunroom, closet and hallway
d) media room, dining room and living room
Attic, bathroom and garage
Art 220.12(A
Certain areas are exempt from arc fault protection as per code regulations.
Which of the following occupancies require arc fault circuit interrupter protection? _______
a) recreational vehicles
b) detached dwelling unit garages
c) a boat house
d) at a hotel or guest room with permanent cooking facilites
d) at a hotel or guest room with permanent cooking facilites
Art 210.17 , 210.12(A)
Arc fault circuit interrupters are required in various types of occupancies for safety.
Ground fault interrupter protection is required for dwelling unit receptacles in all of the following locations except _______
a) outdoors
b) bathrooms
c) detached garages
d) finished basements
finished basements
Art 210.8(A)
Where must cables installed in concrete or poured masonry for electrical heater floors in bathrooms and hydromassage tub locations be?
a) GFCi protected
b) AFCI protected
c) supplied by a minimum 20-amp circuit breaker
d) have a minimum of 2-inches of concrete or masonry cover
GFCI protected
Art 424.44(E)
What is the maximum ampere rating permitted for the overcurrent protective device protecting an 18 AWG conductor for a class 1 circuit?
a) 5
b) 7
c) 10
d) 15
7 amperes
Art 725.43
When cartridge fuses are accessible to other than qualified personnel, what does the code state about disconnects?
a) any voltage
b) over 110 volts
c) over 150 volts
d) over 240 volts
A disconnect shall be provided on the supply side of the fuses when the voltage to ground is over 150 volts
Art 240.40
Edison base fuses are permitted only for which type of work?
a) new work
b) replacement
c) motor circuits
d) lighting circuits
Replacement
Art 240.51(B)
What is the minimum size equipment grounding conductor required for a rooftop air conditioning unit fed with a #6 AWG copper conductor terminated on a 70-amp circuit breaker?
a) 14
b) 6
c) 10
d) 8
8 AWG copper
Table 250.122
How is the equipment grounding conductor required to be identified?
a) blue insulation
b) white insulation
c) gray or white insulation
d) bare or green insulation
Bare or green insulation
Art 250.119
What is the minimum required size of THW conductors for a three-phase 208 volt 40 KW load given the presence of harmonic currents?
a) 1/0 b) 3/0 c) 2/0 d) #1
2/0
40,000/208/1.732 = 111 amps
111 amps / .80 / .88 = 157.68 or 158
2/0 cu conductor with an ampacity of 175 amps should be used
At what intervals shall flexible metal conduit be supported by an approved means?
a) 1
b) 3
c) 4-1/2
d) 6
4 1/2 Art - 348.30(A)
The interior of a raceway installed underground is considered a _______ location.
a) dry
b) wet
c) damp
d) classified
wet
Art 300.5(B)
A cable tray is prohibited to be installed in which of the following locations?
a) plenums
b) storage rooms
c) basements
d) passing through a wall
plenums Art 300.22(C)(1)&(2)
Optical fiber cables shall be permitted in the same raceway with conductors of _______.
a) communication circuits in accordance with article 800
b) sensitive electronic equipment
c) class 1 remote control circuits installed in accordance with article 725
d) non power limited fire alarm system cabling in accordance with article 760
communication circuits in accordance with article 800
Art 770.133(B)(3)
Given the cross-sectional area of 10 copper conductors is 836 square inches, what is the minimum size RMC required?
a) 1
b) 1-1/4
c) 1-1/2
d) 2
1-1/4
Chapter 9 Table 4 RMC
60% fill 24 or less
1-1/4 with a .916 square inches as 60% should be used