What is the criteria for using a feedforward control strategy?
A load disturbance on the CV that is unacceptable but also measurable
What are the 3 steps to implementing feedforward control?
1) Measure the load disturbance
2) Build a model of the load disturbance relative to the CV like a transfer function, energy, or mass balance
3) Implement feedback trim so the CV can be measured and controlled
If the load disturbance is unacceptable and unmeasurable what can be done to resolve the issue?
Gain scheduling/adaptive gain control
What is the advantage of Feedforward system with feedback trim?
1) Helps deal with unmeasured load disturbances
2) Helps deal with model degradation overtime
What is the disadvantage to feedforward control with feedback trim?
Model has to be accurate
In dynamic FF control, the T1L should be __________ than T1P.
more
T/F Static FF models are used when processes are extremely fast and dynamics are negligible
True