med gas Flashcards
(20 cards)
what two types of copper tube can be used for medical gas piping?
type L and type K
what is the minumum size of copper tube permitted for medical gas distribution piping?
1/2”
medical gas piping must be free of ______ or ________ that could combine with the contents resulting in an explosion or fire
oil, grease,
small diameter piping under 1/2” may be joined using
threaded fittings
the approved method of joining copper tube and fittings must be joined using
silver brazing
flux is permitted when joining ________ metals
dissimilar
what gas must be present in the pipiing system while joints are being brazed?
nitrogen
what is the maximum horizontal support spacing for 1/2” pipe?
1.8m
what is the maximum horizontal support spacing for 3/4” pipe?
2.4m
colour coding for exygen pipie is ______ lettering with a _______ background
green lettering/ white background
colour coding for nitrogen piping is _____ lettering with a ____ background
black lettering/ white or silver background
the approved cleaning materials for degreasing copper tube and fittings are ______ and ______
trisodium phosphate and sodium carbonate
what temp must water be when used for cleaning and rinsing copper tube and fittings?
HOT
what is the minimum test pressure for medical gas distribution system?
1030kpa 150psi
what is the maximum test pressure for a medical vacuum system?
415kpa 60psi
what is the minimum test pressure for nitrogen system designed to operate at 120 psi
120 x 1.5 = 180psi
during the 24 hour test, is any pressure fluctuation permitted ina medical gas piping system?
a pressure change during the 24 hour test of a medical gas piping system is only allowable if it is caused by a change in ambient temp in the areas around the medical gas piping
to complete a cross connection test on each medical gas piping system individually, the piping is pressurized to 345kpa 50psi using ______ or ________
oil free dry air or oil free nitrogen
each system must be tested at every
terminal unit
all medical gas piping systems and medical vacuum systems must be provided with a _________ in case of power failure or low supply in the primary system
back up system