List 5 things you can do to a space?
Heat it
Cool it
Dehumidify
Humidify
Two ways to get fresh air into a house?
Infilitration
Ventialtion
Sizing a HRV into a house, whats the percentage ?
40%
House us 2000sqft. 8ft ceiling, find cubic feet ? 40%
20F outside
70F inside
Remember (.4) and (60%) Find CFM -> remember (1.08) and use equation with TD
20008=16,000c.u.FT4
.4 from the 40% = 6400 cu.FT/HR. Divide it by 60
6400/60= 107cfm
Qs= 1.08CFMTD -> Qs= 1.08107 50, TD from 70-20=50
5,778Btus/HR
3 Ton Evap
Too much cause coil to ice up (T/F)
Less would cause coil to ice up
(T/F)
Too much in coil is (False)
Less in coil is (True)
400
Difference between comfort cooling coil compared to commercial comfort coil is ?
Radiator is tighter in comfort cooling
Commerical coul is wider
Per ton how many CFM
400
Whats summer temp comapred to winter temp ? Offsets what ?
Summer is 75/50
Winter is 70/35 and winter tempature offests with humidity.
Where is the distributer?
Before the Evaporator.
3 ways heat leaks into a building?
Infiltration
Conduction
Convection
Which one will increase or decrease heat gain?
Hint (All the above)
Direction the house is facing
Insulation
Types of window/door
Dx direct expansion
Geothermal
Evaporation cooling
Location of common parts refridgeration components?
Metering device- in where the evaporator coil is, inside unit
Accumalator- outdoor, suction line, before compressor
Difference between sensible and latent heat?
Lowering wet bulbs or humidity is latent heat
Lowering measurable temp is sensible heat
75 Air 50% humidity - measuring in the plenum, what will happen to thr relative humidity?
Relative humidity goes higher
It’ll be 38 in the Evap 55F out the evap temp, 6 degree difference.
15
Multiple thermostat, houses parts diff temp?
ZONE SYSTEMS
Lower Amp Draw ?
Undercharge
Walk in cooling with TXV, whats the charging method?
Subcool
If fixed bore = superheat
Medium temp refrigerant low on charge?
Superheat will be much higher than normal.
In a refrigerant system low superheat is?
Overcharge
See higher then expected AMP draw?
Overcharge, dirty coil, airflow issues
High side pressure, convert into tempature, liquid line temp subtract from that what’re you looking at?
Subcool
3 careers that are involved in installing AC unit?
Mechanical
Electrical
Sheet metal